WIPCOOL P16 Скачать руководство пользователя страница 5

06

07

feeling for more

feeling for more

2M

8M

Green light on when working      

If the air conditioner does not have a liquid level switc, it can 
also connect to other alarm devices or refer to fig.

Power cord:  (L) fire wire: Brown  (N) zero line: Blue  (E) ground wire: flower
Signal line:   (NC) normally closed: purple  (COM) common line: red  
                    (NO) normally open: blue

Air Conditioner 

Indoor Unit

Liquid Level Switch

Condensate

Pump

L N E

L N E

L N E

L

N

E

N

.

C

 

Purple 

COM

 

Red

N

.

O

 

Blue

L N E

L

N

E

L N E

N E

AC Contactor

(7) Connect the water tank and pump with 6x9 silicone tube and fasten it with tie, make 
      sure the length of the water pipe is less than 2m ( as shown below )

(8) Connect the 6x9 water pipe to the water outlet, tie the water pipe, make sure that 
      the discharge head is less than 8m and the length of the water pipe is less than 
      25m. ( as shown below )

(9)

 

The condensate pump is equipped with a signal indicating light. When the pump is 

     working and draining normally, the green light is on. When the water level is in 
     alarm, the red light is on. (as shown below)

2M

(10) Power supply wiring, in order to avoid leakage of condensate pump, please 
       connect the alarm signal line and the "Normally Closed" and "Normally Open" signal 
       terminals according to the requirements of different working conditions 
       (as shown below).

N

.

C

 

Purple 

COM

 

Red

N

.

O

 

Blue

 Red light on when alarm

Condensate

Pump

 Air Conditioner

 Outdoor Unit

If there is no liquid level switch, it can also use an appropriate 
AC contactor to control the air conditioning power.

Air Conditioner 

Indoor Unit

 Air Conditioner

 Outdoor Unit

Содержание P16

Страница 1: ...OPERATION MANUAL feeling for more WENLING WIPCOOL REFRIGERATION EQUIPMENT CO LTD Website www wipcool com feeling for more Reliable And Durable Silence Running P16 P32 CONDENSATE PUMP ...

Страница 2: ...e condensate pump to avoid loss caused by power failure or water leakage 3 Non professional personnel should not install it to avoid danger 4 The condensate pump is not waterproof Do not place it in the open air outdoors or in a place prone to flooding 5 The condensate pump power supply needs to be independent to maintain permanent power supply For details of connecting with air conditioning syste...

Страница 3: ...7 53 16 7 7 12 17 85 6 48 3 40 No 1 2 3 4 No 5 6 7 8 No 9 10 11 Part Name Water inlet pipe Tank Filter net Upper cover Part Name Upper cover plate Air hole φ6x20 Water pipe φ6x1500 Induction signal line Part Name Power cord Water outlet pipe Condensate pump assembly 2 Dimension 3 Technical Data Model Voltage Discharge head Max Flow rate Max Tank capacity Mini splits up to Sound level at 1m Ambient...

Страница 4: ...re the tank is placed smoothly and the outlet pipe of the air conditioner is tightly connected with the water pipe of tank as shown below 3 Connect the vent pipe with the air hole as shown below 4 Place the pump in the position beyond the ceiling as shown below 5 The use of shockproof materials ensure the water tank and condensate pump stuck firmly low vibration to avoid noise 6 Pay attention to t...

Страница 5: ...to the water outlet tie the water pipe make sure that the discharge head is less than 8m and the length of the water pipe is less than 25m as shown below 9 The condensate pump is equipped with a signal indicating light When the pump is working and draining normally the green light is on When the water level is in alarm the red light is on as shown below 2M 10 Power supply wiring in order to avoid ...

Страница 6: ...tion is not horizontal 2 There is sludge inside tank 1 A B C WARNING Problem Cause Action Pump makes loud noise Pump can t start working Adjust the tank make it level Clean the inside of tank and probe surface 1 The water is siphoning back in the pump Check whether the outlet pipe is lower than pump thus result in siphoning raise the condensate pump position 1 Installation is not horizontal 2 The ...

Отзывы: