Instruction manual DXB heater
page 10
4.5 Checks before taken into operation
Perform the following checks before taking the heater into operation.
•
Wiring, Ensure the heater is free of electricity by removing the plug from the socket outlet.
Now check that the connection is OK and that the wiring is connected properly.
•
Fuel leaks, Check that the oil system is leak-free and does not contain air.
•
Supply voltage; check if the supply voltage is sufficient.
•
Transport and combustion air flow, Check if the transport and combustion air exhaust is
free from any obstacles. In this way, you will prevent the heater from continuing to
operate while the air exhaust is blocked.
•
Burner pump pressure, The heater will not operate if the burner pressure is too high or too
low; refer to Measuring the burner pressure
•
Flame detection, Flame detection is by means of an LDS photocell. The LDS photocell
measures the brightness of the flame that arise when there occurs a flame. When the
measured brightness of the flame does not arise or is to low the heater will not function.
•
CO-value and CO2-readings in the combustion air too high a level of CO and/or CO2 in
an enclosed space can be harmful to people, animals and crops. You should therefore
always verify that the CO value and the CO2 content in the flue gas comply with the
requirements; refer to Measuring combustion values
•
General heater operation.
5
Function of the heater
5.1 Function service/reset button on the heater
On the left side of the control box there is a external service/reset button situated. This
service/reset button has several functions:
When the button is pushed for 5 seconds (b
in
the display) the heater will start to burn.
When the button is pushed again for 2
seconds the heater will stop. The heater will
remain in the burn mode for maximal 24
hour. Every hour the heater will perform a
safety shutdown and will automatically
restart.
When the button is pushed for 7 seconds (F
in
the display) the heater will start to ventilate
(without burning). The heater will stop to
ventilate when the button is pushed again for
2
seconds.
When the heater is in error A(x), it can be reset by pushing this service/reset button once.