 Operation and Use 

 

24

 

 

 

 

2. 

Parameter list and breakdown table 

2.1 Electronic control fault table

 

Can be judged according to the remote controller failure code and troubleshooting

 

 

Protect/fault

 

Fault

 

display

 

Reason

 

Elimination methods

 

Standby

 

Non

 

 

 

Normal boot

 

Non

 

 

 

Inlet Temp Sensor Fault

 

P01

 

The temp. Sensor is broken or 
short circuit

 

Check or change the

 

temp. Sensor

 

Outlet Temp Sensor Fault

 

P02

 

The temp. Sensor is broken 
or short circuit

 

Check or change the

 

temp. Sensor

 

Hotwater Temp Sensor Fault

 

P032

 

The temp. Sensor is broken 
or short circuit

 

Check or change the

 

temp. Sensor

 

AT Sensor Fault

 

P04

 

The temp. Sensor is broken 
or short circuit

 

Check or change the

 

temp. Sensor

 

Coil temp Sensor Fault

 

P153

 

The temp. Sensor is broken 
or short circuit

 

Check or change the

 

temp. Sensor

 

Suction temp Sensor Fault

 

P17

 

The temp. Sensor is broken 
or short circuit

 

Check or change the

 

temp. Sensor

 

Exhaust temp Sensor Fault

 

P181

 

The temp. Sensor is broken 
or short circuit

 

Check or change the

 

temp. Sensor

 

Exhaust Overtemp Fault

 

P182

 

The compressor is overload

 

Check whether the system of the compressor 
running normally

 

Exhaust Pressure Sensor Fault

 

PP1

 

The pressure Sensor is broken

 

or short circuit

 

Check or change the pressure Sensor or 
pressure

 

Suction Pressure Sensor Fault

 

PP2

 

The pressure Sensor is broken

 

or short circuit

 

Check or change the pressure Sensor or 
pressure

 

EVI Inlet Temp Sensor Fault

 

P001

 

The temp. Sensor is broken or 
short circuit

 

Check or change the

 

temp. Sensor

 

EVI Outlet Temp Sensor Fault

 

P002

 

The temp. Sensor is broken or 
short circuit

 

Check or change the

 

temp. Sensor

 

Low AT Protection

 

TP

 

The ambient temp. is low

 

 

Flow Switch Protection

 

E032

 

No water/little water in water 
system

 

Check the pipe water flow and water pump

 

Electric Overheat Protection

 

E04

 

The electric-heater protection 
switch is broken

 

Check to see whether the electric heater 
has been running under the temperature

 

over 150

 for a long time

 

Compressor Overcurrent 
Shutdown Fault

 

E051

 

The compressor is overload

 

Check whether the system of the compressor

 

running normally

 

Communication Fault

 

E08

 

Communicat ion failure between 

wire controller and mainboard

 

Check the wire connection between remote 
wire controller and main board

 

Communication Fault(Fan )

 

E081

 

Speed control module and main 

board communication fail

 

Check the communication connection

 

HP Protection

 

E11

 

The high-pressure switch is 

broken

 

Check the pressure switch and cold circuit

 

LP Protection

 

E12

 

The low-pressure switch is 

broken

 

Check the pressure switch and cold circuit

 

 

Anti-freezing Prot

 

 

E171

 

 

Use side water system temp. is low

 

1. Check the water temp. or change the

 

temp. Sensor

 

2. Check the pipe water flow and whether

 

water system is jammed or not

 

Prim Anti-freezing Prot

 

E19

 

The ambient temp. is low

 

 

Secondary Anti-freezing Prot

 

E29

 

The ambient temp. is low

 

 

 

DC Fan Motor 1 Failure

 

 

F031

 

1.  Motor  is  in  locked-rotor  state 
2.The  wire  connection  between 
DC-fan motor module and fan

 

motor is in bad contact

 

1. 

Change a new fan motor

 

2. 

Check the wire connection and make sure 

they are in good contact

 

 

DC Fan Motor 2 Failure

 

 

F032

 

1.  Motor  is  in  locked-rotor  state 
2.The  wire  connection  between 
DC-fan motor module and fan

 

motor is in bad contact

 

1. 

Change a new fan motor

 

2. 

Check the wire connection and make sure 

they are in good contact

 

Содержание PRO 20 EVI

Страница 1: ...HIGH PERFORMANCE INVERTER HEATER PRO 20 EVI Installation and Instruction Manual...

Страница 2: ...pump 9 2 Choose a right heat pump unit 10 3 Installation place 10 4 Installation method 10 5 Water loop connection 11 6 Power supply connection 11 7 Location of the unit 11 8 Transit 12 9 Trial Runnin...

Страница 3: ...saving and environment friendly equipment which is mainly used for house warming It can work with any kind of indoor unit such fan coil radiator or floor heating pipe by provide warm or hot water One...

Страница 4: ...fully and understand the following information correctly Mark Meaning WARNING A wrong operation may lead to death or heavy injury on people ATTENTION A wrong operation may lead to harm on people or lo...

Страница 5: ...r fire Move and repair Meaning Entrust When the heat pump need to be moved or installed again please entrust dealer or qualified person to carry it out Improper installation will lead to water leakage...

Страница 6: ...t lack of circuit breaker can lead to electrical shock or fire Operation Meaning Check the installation basement Please check the installation basement in a period one month to avoid any decline or da...

Страница 7: ...nce and structure of the heat pump Wi3 20 114 PH EVI 32 Air outlet in horizontal direction The longest distance of installing the remote controller is 200 meters Water outlet tube Water intlet tube Re...

Страница 8: ...tion DB WB 35 C 24 C outlet inlet 7 C 12 C Heating working condition DB WB 7 C 6 C outlet inlet 35 C 30 C BS EN 14511 1 2013 Air conditioner whole liquid cooling machine electric compressor Part2 Test...

Страница 9: ...7 Specification 3 Unit dimension Model Wi3 20 114 PH EVI 32 Water outlet 1 1 4 Water inlet 1 1 4 125 55 650 1040 1030 437 395 1315...

Страница 10: ...ly friendly refrigerant R32 which is harmless to the ozone sphere 3 Heating in frigid environment Optimized designed unit can achieve the heating function normally even when the ambient temperature is...

Страница 11: ...house office hotel and so forth which need heating or cooling separately with each area need to be controlled 3 Installation place The unit can be installed on any place outdoor which can carry heavy...

Страница 12: ...n of the switch is normal and controlled by the controller Try to avoid air stayed inside of the water pipe and there must be air vent on the top point of the water loop There must be thermometer and...

Страница 13: ...controller to see if there is any failure indication The gas gauge can be connected to the check valve to see the high pressure or low pressure of the system during trial running Trial running Start t...

Страница 14: ...Operation and Use 1 Main interface display and function 13...

Страница 15: ...ile green represents enabled Timer setting Click this key to set the timer White represents not enabled while green represents enabled Setup key Click this key to check the unit status time factory pa...

Страница 16: ...e main interface shows 1 In shutting down interface on off key is in gray status press on off key can start up the machine 2 Note In starting up interface on off key is in red status press on off key...

Страница 17: ...ting mode icon then the display will go into hot water heating mode interface 5 tapping hot water cooling mode icon then the display will come to hot water cooling mode interface Note If what you have...

Страница 18: ...arget temp is being set pop up keyboard is shown as following Note means the new target temp under current setting 1 5 Unlock screen Click the lock screen key again while the screen has been locked po...

Страница 19: ...n and Use Note Input the password of 22 or 022 click the enter key and the screen will be unlocked 1 6 Timer setting Click the timer setting key to enter the timer setting and the interface display is...

Страница 20: ...ck this key to start or turn off the timed shutdown function Hour of timer on Hour of Timer on is shown Minute of timer on Minute of Timer on is shown Hour of timer off Hour of Timer off is shown Minu...

Страница 21: ...setting Click this key to set the unit mute function mode Factory parameter Click the key and enter the password to enter the factory parameter settings and status parameters interface System time set...

Страница 22: ...Operation and Use 21 2 Tapping system time setting button then the interface display is shown as follows...

Страница 23: ...ace display is shown as follows Note When the unit starts the automatic mode the icon is displayed as When the unit is enabled to activate the mute function the icon is displayed as When the unit is e...

Страница 24: ...Occurrence time of the fault Day month and year hour minute Click this key to clear all fault records 1 8 Color Display Calibration Keep click quickly at the blank area on any interface till you hear...

Страница 25: ...circuit Check or change the temp Sensor Low AT Protection TP The ambient temp is low Flow Switch Protection E032 No water little water in water system Check the pipe water flow and water pump Electric...

Страница 26: ...er Board F12 Frequency conversion board and main board communication failure Check the communication connection IPM Overheat Stop F13 The IPM module is overheat Check and adjust the current measuremen...

Страница 27: ...Operation and Use 26 3 Interface diagram...

Страница 28: ...utlet 12 AI12 Hotwater temperature 13 AI13 No use 14 AI14 No use 15 AI15 No use 16 AI16 No use 17 AI17 No use 18 AI18 No use 19 AI19 No use 20 AI20 No use 21 AI21 No use 22 AI22 No use 23 DI01 The hig...

Страница 29: ...controller thermostat 50 CN7 485 2 Driver board 51 CN7 485 3 DTU 52 RO18 No use 53 RO17 No use 54 RO16 Alarm output 55 RO15 Secondary pump 56 RO14 No use 57 RO13 No use 58 RO12 Hot water three way val...

Страница 30: ...fers main unit 1 in the legend and the other modules which are indispensable fittings are provided by users or installation company 2 The unit which of code contains the letter B has water pump inside...

Страница 31: ...waer supply please screw down the pressure to adjust the screw B 4 When the system need fill water at first wrest the handle A of filled water Then the handle A can return close when the system is fu...

Страница 32: ...r pressure in the backwater side is higher than the set pressure outlet Appendix 4 The way of assistant heat source connection Unit provides the connection of assistant heat source which can not be on...

Страница 33: ...its useful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent applia...

Страница 34: ...250A 30mA less than 0 1 sec 186 224A 2 95mm2 95mm2 280A 30mA less than 0 1 sec 2 Three phase unit Nameplate maximum current Phase line Earth line MCB Creepage protector Signal line No more than 10A 3...

Страница 35: ...Code 20181207 0001...

Отзывы: