28
Joining Communication Cable
Important
Wine Guardian cooling systems are supplied with 15 meters of 6 wire, Cat 3 twisted pair
communication cable with RJ11 type connectors. Caution must be taken when connecting
two lengths of communication cable (splicing) to ensure uniform wire color before and
after splice. An RJ11 Modular 6 wire STRAIGHT THROUGH type coupler is the
ONLY coupler approved for splicing Wine Guardian twisted pair communication cable.
Changing Jumper Positions
(Averaging readings from Remote Sensor)
Jumper position 1
Jumper position 2
If using multiple Remote Temperature/Humidity sensors in
your application, refer to the photos showing the need to
change the jumper locations internal to the control board on
each remote sensor (up to 3 maximum).
For the control to average all of the sensors utilized (if
more than one), the jumper must be in different positions on
the pins.
As you can see, there are three pin settings. To access the
jumper:
1. Remove the two-set screws holding on the plastic cover.
This procedure allows the control to go to each remote
sensor in sequence to average. Failure to perform this
procedure will result in the system reading only one
sensor and not the average of multiple sensors.
NOTE: If multiple sensors control the WG unit,
change factory default in configuration setting 10 to
“averaging.” You will need access code from Air
Innovations service to use in configuration 8 to reach
configuration 10