background image

46 
 

Mounting the Remote Sensor (Wireless) 

 
 
 
 
 
 
 
  
 

 

 
 
 
 
 
 
 
 
 
 
 
    
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

 
 

 
1.

 

Disconnect the controller wire from the side of Wine 
Guardian unit and save for future use. 

2.

 

Plan on mounting the remote sensor on a solid surface 
away from doors, corners, air outlets, drafts or heat 
generating equipment. Do not mount the remote sensor 
directly on an outside wall, wall adjacent to a boiler 
room, or other hot area as this runs the risk of 
influencing its temperature readings. The recommended 
height is four to five feet above the finished floor. 

 

3.

 

Remove the sensor face plate (Fig. 1). Mark the 
mounting points at the desired location within the wine 
cellar (Fig. 2).  

 

 

4.

 

Drill two one-eighth inch holes and insert anchors 
within the mounting surface. Anchors may not be 
required if securing to a wall stud or racking system. 
Insert screws to secure the sensor to the wall to ensure it 
mounts easily onto the two screws and slides down onto 
the slotted openings freely. 
 
 

5.

 

Input the three AA batteries. (Fig. 3) 
(only applicable with wireless installations)  
 
 

6.

 

Pair the sensor with the unit  
(See Page 46 for Pairing Instructions) 
 
 

NOTE: 

Once Paired the Remote Interface’s 

readings will be included into the system’s 
temperature and humidity averages.

 

 
 

7.

 

Mount the Remote Sensor on the wall (Fig. 4) 

 

 

8.

 

Reattach the sensor’s faceplate (Fig. 5) 
 
 
 

 

Fig.2 

Fig.2 

 

Fig. 1 

 

Fig. 2 

 

Fig. 3 

 

Fig. 4 

 

Fig. 5 

Содержание TTW009

Страница 1: ...novations com Wine Guardian reserves the right without notice to make changes to this document at its sole discretion Please visit out web site for the most current version of the Wine Guardian manual...

Страница 2: ...Duct Collar Adapter 11 Remote Temperature Humidity Controller 11 Remote Temperature Humidity Sensor 11 Heater Option 11 Humidity Option 12 Remote Temperature Humidity Sensor 12 Serving Temperature Opt...

Страница 3: ...andard Controller Functions 31 Alarm Codes 38 Installing the Optional Remote Interface Controller and Communication Cable 40 Additional Remote Interface 41 Controller Specification 41 Mounting the Opt...

Страница 4: ...quipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one o...

Страница 5: ...ng the air and condensing moisture out of the air The word evaporator refers to the evaporation of the refrigerant from liquid to gas phase in the coil The Evaporator Section is connected to or inside...

Страница 6: ...claim immediately WARNING DO NOT LIFT THE UNIT UP FROM ITS PLASTIC FRONT PIECES TO AVOID DAMAGING THEM THE UNIT SHOULD BE LIFTED FROM UNDERNEATH ITS BASE AT BOTH ENDS OF THE SYSTEM Review the Packing...

Страница 7: ...o sections the evaporator or cooling section and the condenser or heat rejection section Each section contains a coil to add or remove heat and a fan to move the air through the coil and into our or o...

Страница 8: ...temperature or humidity alarm The local and remote user interface controls employ user friendly menu driven programming features that can easily be accessed by holding the mode button on the control...

Страница 9: ...ts and reports alarms and temp humidity readings to remote user interface One way communication remote temp humidity sensor reports temp and humidity readings to main control Local User Interface Can...

Страница 10: ...troduce it back into the cellar An auxiliary drain port is located at the condenser end of the unit should there be a need to physically remove the excessive moisture Each system is provided with a pr...

Страница 11: ...ions at the tie in point to the remote location or outdoors Remote Temperature Humidity Controller The remote temperature humidity controller Remote Interface Controller is intended to provide a means...

Страница 12: ...e permanently lubricated motorized impeller blower This section also contains the compressor and the electrical controls Evaporator Section Wine cellar air is circulated through the evaporator section...

Страница 13: ...made of rugged ABS plastic and factory mounted to automatically seal to the chassis Air is introduced through the sides and bottom and discharged through the front perforated section Directional Louv...

Страница 14: ...14 Overview...

Страница 15: ...15 TTW018 and WG25...

Страница 16: ...16 TTW009 and WG15...

Страница 17: ...ets TURN OFF ALL POWER BEFORE OPENING PANELS USE THE LOCKOUT TAGOUT PROCEDURE Warning A WARNING message indicates a potentially hazardous situation which if not avoided could result in death or seriou...

Страница 18: ...s is limited to maintenance personnel working in and around the system When performing maintenance always use the Lockout Tagout procedure which is described in this chapter Observe the maintenance sa...

Страница 19: ...tem On Off Switch To shut down all high volt power internally the power cord must be removed from power outlet Energy Type Voltage Hazard Electrocution electrical burns and shock 60Hz Magnitude 120 Va...

Страница 20: ...1 phase 50Hz power sources only Always ground the outlet to provide adequate protections against voltage surges and built up static charges see Section 810 of the National Electric Code Refer all serv...

Страница 21: ...ntrol illuminates This indicates the system has power The built in timer prevents short cycling and keeps the system from turning on right away The system comes on and runs as long as the temperature...

Страница 22: ...rd Never place the unit where the power cord is subject to wear or abuse Do not use extension cords Never overload wall outlets Do not remove or open any cover unless the unit is turned off and the po...

Страница 23: ...nsulation and vapor barriers Locating the System Wine Guardian systems are typically installed at the user s eye level for ease of operation The Through the Wall system discharges warm air from its co...

Страница 24: ...s and remove the green wire connected to the power cord as shown 3 Re attach the ground lug onto the chassis and ensure the other two green ground wires are secure and attached back onto the chassis a...

Страница 25: ...h the hole in the bottom of the bracket until grommet snaps into place 8 At the wine room side of the unit attach each power cord wire to their respective chassis wire i e white to white black to blac...

Страница 26: ...l penetration should be no more than 14 1 2 wide by 16 1 4 high 36 83cm wide by 41 27cm high stud to stud dimension so modifying stud locations is not required CAUTION RISK OF PERSONAL INJURY OR DAMAG...

Страница 27: ...revent the system from horizontal movement After caulking add the kit supplied self adhesive insulate strips tight to the chassis and cover the wall sleeve flanges to prevent possible sweating Install...

Страница 28: ...n sink or condensate pump If you experience NO water you may wish to remove the plastic drain hose and install the plastic drain port cover included Priming the Drain Trap The internal drain trap prim...

Страница 29: ...ctrical Plug Configuration 50Hz Models Only This is the configuration of the factory supplied plug for European applications Alterations to this plug for alternative power sources would require factor...

Страница 30: ...w will allow the user to decrease settings SETTINGS The setting button will be used to select between HEAT COOL and AUTO MODE as well as entering the configuration settings Holding the SETTINGS button...

Страница 31: ...ss the Settings button once to display the Humidity setpoint Press the Up or Down arrows to adjust the humidity to the desired set point Note A Wine Guardian humidifier must be installed and Setting 6...

Страница 32: ...ty alarm set point Setting 4 Press Settings button to advance to Setting 4 Press the Up or Down arrow buttons to adjust to the desired setpoint Factory default is 5 High humidity alarm setpoint Settin...

Страница 33: ...essor anti short cycling time is the amount of allowable time between compressor stop and restart Rapid start stop of compressors can cause premature failure WINE GUARDIAN DOES NOT RECOMMEND SETTINGS...

Страница 34: ...tting is adjustable from 30 min at 0 zero 1 hour at 1 and then in 1 hour increments up to a maximum of 12 hours at 12 Room temperature offset Setting 13 Press Settings button to advance to Setting 13...

Страница 35: ...the Up or Down buttons to adjust to the desired setpoint This setting is the minimal allowable temperature difference between heating and cooling setpoints Maximum is 5 F 3 C minimum is 1 F 1 C Facto...

Страница 36: ...ne room RF channel select Setting 31 Press Settings button to advance to Setting 31 Press the Up or Down buttons to adjust to the desired setpoint Each system needs all devices to be on the same RF ch...

Страница 37: ...served for additional fields Default temperature Setting 70 Press Settings button to advance to Setting 70 No setting adjustment Initial temperature set point Will revert to this setting upon loss of...

Страница 38: ...along with symbol will remain on screen until humidity falls below the High Humidity Alarm setpoint Setting 5 Low humidity alarm Flashing humidity number Flashing humidity number along with symbol wil...

Страница 39: ...nsor Fault THE SYSTEM REMAINS OPERATIONAL DURING THIS ALARM Defrost sensor has been shorted disconnected or open 3 will remain on screen until the defrost sensor issue has been resolved 4 Communicatio...

Страница 40: ...n cable 50 15 25 meters of control cable is included with each controller with longer lengths available as an option Wirelessly connects wirelessly to the Wine Guardian unit by Radio Frequency connect...

Страница 41: ...o Change over Auto or manual Fan ON or AUTO Color Black only User interface Touch screen Auto defrost control Yes with Serving temp option Connection Communicating RJ 9 cable Wireless to base communic...

Страница 42: ...of the two mounting points Fig 3 Also mark the location of the penetration for the communication cable as this area will require sufficient clearance for the cable to exit the wall and attach to the b...

Страница 43: ...ve the back plate from the Remote Interface Controller Fig 1 4 Place the back plate against the wall and mark the mounting points at the desired location Fig 2 5 Drill two one eighth inch holes and in...

Страница 44: ...within the wall and or ceiling structure of the wine cellar to the desired controller mounting location 2 Plan on mounting the remote sensor on a solid surface away from doors corners air outlets draf...

Страница 45: ...enings freely Fig 3 5 Plug in the communication cable to the remote sensor and mount the Remote Sensor to the wall Fig 3 6 Reattach the sensor s faceplate Fig 4 7 If multiple sensors are being used ei...

Страница 46: ...ounting points at the desired location within the wine cellar Fig 2 4 Drill two one eighth inch holes and insert anchors within the mounting surface Anchors may not be required if securing to a wall s...

Страница 47: ...in this mode press the button once to change the device number Once each remote sensor has its own unique device number simply wait for the LED to stop flashing and the setting will be saved 2 To cha...

Страница 48: ...Maintenance WARNING BEFORE PERFORMING MAINTENANCE ON THE SYSTEM READ AND UNDERSTAND THE SAFETY INFORMATION CONTAINED WITHIN THE SAFETY CHAPTER OF THE WINE GUARDIAN MANUAL DANGER HIGH VOLTAGE RISK OF...

Страница 49: ...dule Monthly Or quarterly depending on experience with individual cellar Check for noise or vibration Check for short cycling of the system a turning on and off of the compressor unit more than eight...

Страница 50: ...y removing the plastic end cover Locate red push button using a flash light inside the condenser outlet section Reaching your hand inside or using a long screwdriver push in the button until it locks...

Страница 51: ...n the Thermostat Installation and Operating Instructions Changed settings on the thermostat A common problem is not waiting long enough for the internal timers to complete their timed delay Allow 5 mi...

Страница 52: ...to the cellar and compressor and condenser fans run Cellar temperature is low below 51 when unit is running Possible Cause Solution Thermostat set too low on cooling Thermostat not controlling tempera...

Страница 53: ...cellar Add Wine Guardian humidifier or room humidifier Humidity too low with optional humidifier Possible Cause Solution Humidifier not operating Humidifier operating Check wiring for loose broke or f...

Страница 54: ...ar Poor vapor barrier installation Humidifier malfunction refer to the humidifier instructions Add dehumidifier to surrounding space Other Miscellaneous Problems System is leaking water Possible Cause...

Страница 55: ...ange these warranties or assume any other obligations or liabilities for Wine Guardian in connection with the sale of its systems INDEMNIFICATION Purchaser agrees to indemnify hold harmless and defend...

Страница 56: ...the warranty claim If the original packaging has been discarded Air Innovations will send for a fee a replacement box and packaging materials for proper freight protection back to Wine Guardian factor...

Страница 57: ...e Guardian 7000 Performance Drive North Syracuse NY 13212 Toll free 800 825 3268 or Help wineguardian com Normal business hours are 8 a m to 5 p m Eastern Monday Friday Web site airinnovations com Ema...

Отзывы: