Accessories and Optional

 

附件和选项

 

Heating Coils 

An optional heating coil is built-in and requires no additional power source. The electric 
heating option is factory installed and includes primary and secondary over-temperature 
protection devices per UL and NEC. 

加热线圈

 

一个可选的加热线圈是内置的,不需要额外的电源。电热选项是工厂安装,包括初级和根据

UL

NEC

二级的超温保护装置。

 

Water Cooled Option 

A  water  cooled  option  is  available  that  uses  a  tube-in-tube  heat  exchanger  in  place  of  the 
condenser  coil and fan. Waste heat  from the refrigerant  is  transferred to  the water. A control 
valve is used to regulate the flow of water to maintain head pressure. 

水冷方案

 

 

水冷选项是放置在一个筒中的管式换热器,水冷方案可避免使用冷凝器线圈和风扇。制冷剂的
废热量转移到水中。控制阀是用来调节水流量,以维持冷凝器部分的头部压力。

 

Duct Collars and Flexible Ducts 

Ducting for the Wine Guardian is sold in kits by size for each unit. Each kit contains two 
adapter collars, one 7.3 meter length of round flexible duct and two straps. The number of duct 
kits needed depends on the layout. The size of the kit depends on the model Wine Guardian 
selected. Follow installation instructions carefully. Poorly or incorrectly installed ducts can 
degrade the performance of your unit dramatically. 

管领和柔性管道

 

酒卫主机的管道按不同主机大小分别成套出售。每个套件包含两个管领适配器,一个

7.3

米的

圆形柔性管和两根皮带。风管套件所需的数量取决于设计图纸。该套件的大小取决于选定的酒
卫主机型号。仔细按照安装说明。不佳或不正确的管道安装可以降低主机的工作性能。

 

Extended Compressor Warranty 

The Wine Guardian uses only the best commercially available compressors on the market. 
However, since the compressor is the single most expensive component in the unit, it is 
recommended that you purchase the extended warranty option. 

延长压缩机保修

 

该机组采用了市场上最好的商用压缩机。然而,由于压缩机是在机组中最昂贵的部件,建议您购
买延长保修选项。

 

Low Ambient Option 

A factory installed Low Ambient option is available which makes the Wine Guardian capable 
of exposure to low ambient temperatures. This feature controls the condenser fan operation 
based on head pressure and heats the oil reservoir. The Low Ambient Option (LAO) is 
recommended whenever the condenser section is exposed to air temperatures below 50°C. This 
can occur if the unit is placed in a garage or under an outdoor canopy or if the unit is located 

Содержание D025

Страница 1: ...5 Manufactured by Wine Guardian 76 551 126 2017 6 Wine Guardian division of Air Innovations Inc Syracuse NY wineguardian com airinnovations com Wine Guardian reserves the right without notice to make...

Страница 2: ...m for D025 D050 D050V WG40 and WG75 13 D025 D050 D050V WG40 WG75 Wiring diagram for D025 D050 D050V WG40 and WG75 cont 14 D088 D088V WG100 Wiring diagram for D088 vertical model D088V and WG100 15 D08...

Страница 3: ...38 Reducing Noise from the Unit 38 Installing the Unit Outdoors 39 The Wine Guardian is NOT designed nor approved for direct outdoor installation If it is located outdoors it MUST be protected with a...

Страница 4: ...Power Switch Light is On and the Thermostat Light is On 82 Unit is Operating and Blows Evaporator Air but the Supply Air is Not Colder Than the Return Air from the Cellar 83 Problems Controlling Cell...

Страница 5: ...or Coil is Freezing 89 High Pressure Switch Keeps Tripping Even After Checking for Obstructions and Dirty Filters Coils 89 Unit Cycles on and off more than 8 times hr 89 High Pitched or Loud Rubbing N...

Страница 6: ...ion Sciences et D veloppement conomique Canada applicables aux appareils radio exempts de licence L exploitation est autoris e aux deux conditions suivantes 1 L appareil ne doit pas produire de brouil...

Страница 7: ...lar The word condenser refers to the condensation of the refrigerant from gas to liquid phase CE Certificate of European conformity CE Exhaust Air The air leaving the evaporator or condenser section o...

Страница 8: ...it does to return the cellar to its set point temperature after some new load is introduced such as people or new cases of warm wine entering the cellar Return Air The air leaving the cellar and retur...

Страница 9: ...ies Before opening the container inspect the packing crates or boxes for obvious signs of damage or mishandling Write any discrepancy or visual damage on the bill of lading before signing Inspect all...

Страница 10: ...it accessories If any items listed on the packing slip do not match your order information contact the place of purchaseimmediately Check the unit for An electrical power cord A thermostat with commun...

Страница 11: ...contains a coil to add or remove heat and a fan to move the air through the coil and into or out of the cellar or adjacent space The Wine Guardian unit is designed to be used either as a free blowing...

Страница 12: ...ature This may cause overheating problems in the summer months especially with high humidity Exhaust the hot air to the outside In the winter this heated air can help to heat the surrounding space 15...

Страница 13: ...components and wiring 1 6mm Both the evaporator and the condenser coils have pre filters on the inlet to prevent dust and dirt from fouling the coils thereby reducing capacity Each unit has at least t...

Страница 14: ...eded depends on the layout The size of the kit depends on the model Wine Guardian selected Follow installation instructions carefully Poorly or incorrectly installed ducts can degrade the performance...

Страница 15: ...is furnished with an electronic digital humidistat to control the humidity in the cellar The humidifier mounts directly onto the Wine Guardian unit and uses the common drain The humidifier requires a...

Страница 16: ...d between the evaporator coil and the blower and is complete with contactor s and limit controls Electrical Controls Most of the electrical components and controls are located in a separate area acces...

Страница 17: ...pressure switch and a manual reset high pressure switch For the low ambient option an automatic pressure switch controls the operation of the condenser blower and a heating element is added to the co...

Страница 18: ...12 Overview Illustration of the Wine Guardian Unit Refrigeration Illustration Vapor Compression System...

Страница 19: ...13 D025 D050 D050V WG40 WG75 Wiring diagram for D025 D050 D050V WG40 and WG75...

Страница 20: ...14 D025 D050 D050V WG40 WG75 Wiring diagram for D025 D050 D050V WG40 and WG75 cont...

Страница 21: ...15 D088 D088V WG100 Wiring diagram for D088 vertical model D088V and WG100...

Страница 22: ...16 D088 D088V WG100 Wiring diagram for D088 vertical model D088V and WG100 cont...

Страница 23: ...17 D088 D088V WG100 Wiring diagram for D088 vertical model D088V and WG100...

Страница 24: ...18 D088 D088V WG100 Wiring diagram for D088 vertical model D088V and WG100 cont...

Страница 25: ...19 D200 WG175 Wiring diagram for D200 and WG175...

Страница 26: ...20 D200 WG175 Wiring diagram for D200 and WG175 cont...

Страница 27: ...21 D025 D050 Wiring diagram for water cooled D025 and D050...

Страница 28: ...22 D025 D050 Wiring diagram for water cooled D025 and D050 cont...

Страница 29: ...23 D088 D200 Wiring diagram for water cooled D088 and D200...

Страница 30: ...24 D088 D200 Wiring diagram for water cooled D088 and D200...

Страница 31: ...each grille A Width mm 356 559 559 559 B Height mm 356 356 356 457 C Length mm 889 991 991 1092 D Cond discharge location mm 540 591 591 660 E Evap discharge location mm 137 137 137 137 F Inlet openin...

Страница 32: ...3 254 254 295 I mm 202 282 282 381 J mm 368 419 419 457 kg 36 3 56 7 65 8 88 4 134A g 539 737 964 1417 Safety Before installing or maintaining the Wine Guardian Unit do the following 1 Read these inst...

Страница 33: ...ication Danger A Danger message indicates an imminently hazardous situation which if not avoided results in death or serious injury Messages identified by the word DANGER are used sparingly and only f...

Страница 34: ...eath or serious injury Following is a typical example of a Warning message as it could appear in the manual WARNING RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT Modification to the equipment may cau...

Страница 35: ...ithin its designed specifications To avoid personal injury or damage to equipment or property when installing or operating this equipment it is essential that qualified experienced personnel perform t...

Страница 36: ...to installation and servicing this equipment More than one source of power may be present Disconnect all power sources to avoid electrocution or shock injuries Hot Parts Hazards Electric Resistance h...

Страница 37: ...ical system Main Power Switch The main power switch is located on the side of the Wine Guardian unit See Overview Illustration on page 14 It shuts off the power to the unit 8 Energy Type Electrical Ha...

Страница 38: ...essive force against the access panels Fan impellers continue to turn free wheel after the power is shut off CAUTION Clean only with a dry cloth Never pressurize equipment above specified test pressur...

Страница 39: ...0Hz power sources only 230 50Hz Always ground the outlet to provide adequate protection against voltage surges and built up static charges Refer all servicing to qualified service personnel Servicing...

Страница 40: ...ce Plug in the system Press the on off switch control illuminates This indicates the system has power ON OFF The built in timer prevents short cycling and keeps the system from turning on right away T...

Страница 41: ...uipment DANGER This equipment is heavy Place the unit on the floor or on a level and stable surface that can support the full weight of the unit Do not modify the equipment it may cause damage to the...

Страница 42: ...e or open any cover unless the unit is turned off and the power cord is plugged in Use only dedicated power outlet boxes of the correct capacity and configuration for the unit model CAUTION RISKOF PER...

Страница 43: ...ellar or out Do not use an extension cord Does the condenser heat exhaust need to be ducted away Where to locate the thermostat Where to run the drain line Are all the parts here to complete the insta...

Страница 44: ...cessary grilles for installing ductwork between the unit and the cellar If desired use the grilles as wall grilles inside the cellar The return air or inlet to the unit must connect to the return air...

Страница 45: ...bove the ground on a solid waterproof base to protect the unit from ground water Do not locate it where grass clippings or leaves can blow into the unit Keep the area around the unit clean and free of...

Страница 46: ...ort it on both sides of the wall Use floor or knee braces to transfer the load of the unit to the floor or wall Ceiling Mounting Construct a structurally sound level platform to place the unit on when...

Страница 47: ...ifier to dehumidify the basement so as to not overload your Wine Guardian Installing the Drain Line The drain line must extend from the unit to an external drain or disposal site Do not use drain tubi...

Страница 48: ...rimes itself automatically once the unit has run for a period of time and after the unit cycles off This is confirmed by water dripping from the drain Wiring the Unit for Power DANGER ELECTRICAL SHOCK...

Страница 49: ...IN ANY WAY Do not use extension cords Electrical 240 1 50 Electric Heat Amps Opt 4 4 Locked Rotor Amps 18 5 Humidifier Amps opt 0 3 Compressor RLA 2 4 Crankcase Htr Amps opt 0 4 Condenser Fan Amps 0...

Страница 50: ...ecommended wired directly to the Wine Guardian unit through an RJ 9 communication cable 50 15 25 meters of control cable is included with each controller with longer lengths available as an option RJ...

Страница 51: ...ased and installed within the wine cellar 30 53 30 60 WG RJ 9 40 12 34 97 1 36 2 1 1 2 93 10 IMPORTANT Regardless of wired or wireless each Wine guardian System can have a maximum of two 2 Remote Inte...

Страница 52: ...cold surface The recommended height is four to five feet above the finished floor b 4 5 2 Remove the back plate of the controller Fig 2 by removing two 2 screws that hold it in place on the remote in...

Страница 53: ...ce controller backing plate Fig 5 5 5 a If using multiple Remote Interfaces either connect each Sensor to each other in series using RJ9 cable or purchase a RJ9 Splitter to be used on the unit a RJ 9...

Страница 54: ...ate it from a hot or cold surface The recommended height is four to five feet above the finished floor 2 4 5 3 Unscrew and remove the back plate from the Remote Interface Controller Fig 1 3 1 4 Place...

Страница 55: ...4 7 Insert the three AA batteries only applicable with wireless installations 7 AA 8 The system will automatically acknowledge a wireless device Remote Interface or Remote Sensor Go to Setting 30 to...

Страница 56: ...lar to the desired controller mounting location 1 2 Plan on mounting the remote sensor on a solid surface away from doors corners air outlets drafts or heat generating equipment Do not mount the remot...

Страница 57: ...freely Fig 3 4 3 5 Plug in the communication cable to the remote sensor and mount the Remote Sensor to the wall Fig 3 5 3 6 Reattach the sensor s faceplate Fig 4 6 4 7 If multiple sensors are being u...

Страница 58: ...the desired location within the wine cellar Fig 2 3 1 2 4 Drill two one eighth inch holes and insert anchors within the mounting surface Anchors may not be required if securing to a wall stud or racki...

Страница 59: ...RF 31 1 To change the remote sensor s device number see the following instructions 1 a Use a pin to press the button for about half a second and release Fig 1 a 1 b Observe the LED on the side of the...

Страница 60: ...he button a 5 LED b The LED will flash a number of times to portray which RF channel it is set to and repeat a total of 3 times b LED 3 c To change the RF channel press the button once to increment th...

Страница 61: ...55 5 6 1 2...

Страница 62: ...56 1 2 2 50 F 10 C 3 3 65 F 18 C 4 4 5 5 5 95 6 6 0 0 1 2 5...

Страница 63: ...57 7 7 0 0 1 8 8 10 3 5 9 9 1 0 10 10 25 40 39 1...

Страница 64: ...58 11 11 35 50 40 10 1 F C C F 41 F 12 12 0 30 1 1 1 12 12 13 13 5 F 5 F 0 55 F 13 C 15 4 59 F 15 C 14 14 RH 10 0 RH...

Страница 65: ...59 15 15 1 F 55 F 13 C 17 3 F 58 F 14 C 16 16 5 F 3 C 1 F 1 C 2 F 1 C 17 17 0 1 0 18 19 20 21 29...

Страница 66: ...60 30 30 1 1 2 2 3 1 4 2 RF 31 31 RF 0 RF 1 12 RF 12 32 39 1 40 40 2 41 41...

Страница 67: ...61 3 42 42 4 43 43 44 49 50 50 0 1 51 69 70 70 71 71...

Страница 68: ...62 72 72 1 2 3 3 2 5 4 1 1 57...

Страница 69: ...63 2 CS 2 CS 3 3 4 4...

Страница 70: ...dustfrom the floor Locate the supply or return air grille where it is blocked by bottles boxes or cases Locate the supply air grille where it blows directly on the thermostat Relocating a grille on th...

Страница 71: ...WG40 200 200 200 150 WG75 250 250 250 200 WG100 250 250 250 200 WG175 300 300 300 250 200 150 Recommended Insulated Flexible Ductwork Sizing Chart Evaporator Coil Condenser Coil Single Outlet Double...

Страница 72: ...information about which panels are available for duct connections and service 8 Remove the panels or grilles from the openings to connect the ductwork Check that all the fan blades move freely Check f...

Страница 73: ...damage or bend the gasket Not Using Ductwork The supply and return grilles stay on the unit if no ductwork is used The supply and exhaust grilles may be relocated to any of three openings Refer to th...

Страница 74: ...he cellar to the supply air inlet at the Wine Guardian unit Connect the return air ductwork from the cellar to the return air inlet at the Wine Guardian unit Warm Air to from Condenser Connect ductwor...

Страница 75: ...stallation drawings For questions or helpregarding installation call customer service at or 00 1 315 452 7434 fax 00 1 315 452 7420 or email info wineguardian com a sketch of the proposed area where t...

Страница 76: ...83 295 346 WG100 DUAL OUTLET 202 254 283 295 346 WG175 INLET 303 479 381 549 448 WG175 OUTLET 303 295 381 346 448 WG175 DUAL OUTLET 252 295 381 346 448 SIZE WG40 202 267 283 295 346 WG40 202 203 283 2...

Страница 77: ...71 Dual Outlet Duct Installation...

Страница 78: ...ines and trap installed properly Ductwork fittings and grilles installed properly All cold duct surfaces insulated Low ambient control included if freezing condition present No obstructions to air flo...

Страница 79: ...rom access inside the unit Turn on the Unit Plug in the unit Turn on the rocker switch on the side of the unit The rocker switch lights up to indicate power to the unit The unit may not come on right...

Страница 80: ...the cellar temperature decrease to 13 C the supply temperature differential decreases 6 to 7 C colder 24 8 C 11 C 13 6 7 C Cycling the Unit The fans continue to free wheel for several minutes when th...

Страница 81: ...nitor the Cellar Temperature place thermometers in various locations in thecellar to monitor the temperature zones Change the temperature in various zones by shifting the air flow patterns Changing th...

Страница 82: ...the Lockout Tagout procedure before opening panels CAUTION SHARP EDGES RISK OF SEROUS INJURY Sharp edges are present on the fan wheels housing fins and coils Maintenance on Wine Guardian units requir...

Страница 83: ...fans are permanently lubricated and require no maintenance Some maintenance to the unit may be required due to dust or dirt in the air stream Cleaning the Filters The evaporator and condenser coils a...

Страница 84: ...soiled pour some hot water mixed with liquid bleach diluted solution along the length of the pan to flush the dirt down the drain tube Continue this treatment until the drain appears clean and free of...

Страница 85: ...Low Ambient Option The purpose of the Low Ambient Option is to protect the compressor and refrigerant system It has two distinct components a crankcase heater to keep the oil in the compressor warm an...

Страница 86: ...r and condenser coils for dirt use a vacuum with a brush attachment to clean the coils Clean condensate pan under the evaporator coil by flushing Be careful to keep the drain pans clear of any and all...

Страница 87: ...ied service company Check the following table for some solutions before calling a service technician Typical Start up Problems Possible Cause Solution Loose improper or defective Check power and therm...

Страница 88: ...on Turn on switch No power to outlet Check circuit breaker and wiring Unit not plugged in Plug in the unit Power Switch Light is On and the Thermostat Light is Off Possible Cause Solution No power to...

Страница 89: ...switch is open Reset HP switch See reset instructions on page 42 42 Problems Controlling Cellar Temperature Problems are occurring even though the unit seems to be fully operational evaporator fan blo...

Страница 90: ...d the ductwork Check and clean filter and coil Coil frozen shut off unit for two hours Cellar loads are too high Install additional insulation Replace with larger sized unit Problems Controlling Cella...

Страница 91: ...optional humidifier Possible Cause Solution Humidifier not operating Check wiring for loose broken or frayed connections Check humidistat set up Check for water flow solenoid valve operation Check da...

Страница 92: ...l openings around doors gasket and sweep Humidity too high when unit is running and cooling Possible Cause Solution Too much moisture in cellar Poor vapor barrier installation Humidifier malfunction r...

Страница 93: ...s a manual reset high pressure switch in the refrigeration system This switch shuts the compressor and condenser down if the head pressure in the system is too high It is intended to protect the compr...

Страница 94: ...ng labeled High Press Manual Reset Switch Remove panel or grille to access Locate the high pressure switch near the compressor a cylindrical device piped into the refrigeration system with two wires a...

Страница 95: ...ssible Cause Solution Charge too low Check sight glass Check for leaks Add refrigerant High Pressure Switch Keeps Tripping Even After Checking for Obstructions and Dirty Filters Coils Possible Cause S...

Страница 96: ...Solution Fans loose or malfunctioning Repair or replace Excessive compressor vibration Replace TXV malfunctioning TXV Repair or replace Replacing the Blowers When replacing the fan or motor replace t...

Отзывы: