Safety information 

__________________________________________________________________________ 

 

 

 

Only allow correspondingly trained, qualified 

 

and skilled personnel to carry out installation work. 

 

Reliable operation and the avoidance of 

 

damage and hazards is only guaranteed if 

 

installation and settings are carried out carefully

 

in accordance with these instructions. 

 

Check the technical data on the system plate. 

 

Hazards to persons ensuing from flaps and 

 

wings operated by electric motors. 

 

The forces occurring in the automatic mode can 

 

be such that parts of the body could get crushed. 

 

When open

 

ed, actuators could protrude into the 

 

room. 

 

For this reason, measures have to be taken

 

prior to starting up the actuators which exclude 

 

the danger of injury. 

 

With wings tilting inwards or outwards, the wing 

 

must be protected from hinging down once the 

 

actuator is unhooked (e.g. for window cleaning). 

 

For safety reasons we recommend the use of 

 

catching shears. 

 

In the event that wings or flaps are subjected to 

 

high wind loads, we recommend to connect the 

 

central control unit to a wind detector which

 

 will 

 

automatically close the flaps. 

 

The fastening methods are exclusively intended 

 

for the intended use for which they are designed

 

The manufacturer does not assume any liability 

 

for possible damage resulting from inappropriate 

 

use. 

 

Can cause death, severe injury or considerable 

 

damage to assets. 

 

The connection of the control system is reserved 

 

for qualified personnel. 

 

Disconnect all poles of the unit from the supply 

 

voltage prior to opening, installation or 

 

assembling. Adhere to the national regulations.

 

 

230V AC  dangerous voltage 

 

 

 

 

 

Field of application 

 

Maintenance work 

 

Cable routing and electrical connection 

 

Leave the insulation of the power supply 

 

cable in place up to the mains terminal. 

 

Manufacturer's declaration 

 

The central control system is exclusively designed 

 

for the automatic closing of smoke extraction 

 

systems, windows, flaps or doors. 

 

Always check that your system meets the valid 

 

regulations. 

 

Pay particular attention to the opening cross section, 

 

the opening time and opening speed. The cable cross

 

 sections depend on the cable length and current 

 

consumption (amperage). 

 

Where devices are used in smoke and heat 

 

extraction systems, ensure that they are checked, 

 

maintained and, if necessary, repaired a

 

t least once 

 

per year.

 

Remove all soiling from the devices, 

 

check the fastening and clamping screws for firm 

 

seating. Trial run the entire system. 

 

Defective devices may only be repaired in our factory

 

Only use original spare parts. 

 

The supplied accumulators are subject to regular 

 

checks and must be replaced every 4 years. 

 

Fuse the 230V AC power supply cable separately on 

 

site. 

 

Adhere to the DIN and VDE regulations (Germany) 

 

or equivalent in your country. 

 

Establish the cable types, if necessary, wi

 

th the local 

 

approval bodies or the fire protection authority. 

 

Do not conceal flexible cables. Junction box 

 

must be accessible for maintenance purposes. 

 

Disconnect all poles of the mains voltage and the

 

accumulators prior to starting maintenance work or 

 

making changes to the system. 

 

Secure the system to prevent unintentional switching 

 

on again. 

 

Design cable types, lengths and cross sections in 

 

accordance with the technical information. 

 

Route all low voltage cables (24V DC) separate from 

 

the power

 

 current cables. 

 

The devices have been inspected and manufactured 

 

in accordance with the European directives. 

 

A corresponding manufacturer's declaration is 

 

available. 

 

You are only authorised to use the devices if a 

 

conformity declaration is issued for the entire system. 

 

.  

  

Attention!

 

Adherence to the following information is mandatory:

 

Содержание WSC 304 6102

Страница 1: ...able of contents Safety information Operating elements and fuse review Technical data Installation Cable lengths table Cable plan Standard wiring diagram Various wiring diagrams Commissioning Maintena...

Страница 2: ...e insulation of the power supply cable in place up to the mains terminal Manufacturer s declaration The central control system is exclusively designed for the automatic closing of smoke extraction sys...

Страница 3: ...Operating elements and fuse review ____________________________________________________________________________ 3...

Страница 4: ...moke control unit the red LED in the break glass unit and the red LED at the tripped automatic detector extinguish Resetting a trip caused by high temperature The smoke extraction system can be closed...

Страница 5: ...rated in the button Ventilation closed The actuators close after pressing the CLOSED button Display The ventilation open LED in the ventilation button has extinguished only with LED integrated in the...

Страница 6: ...at there is no fault An alarm signal has first priority SW 1 2 ON Forwarding the alarm signal WSA 301 After 3 min it will stop SW 1 2 OFF Forwarding the alarm signal WSA 301 as long as the alarm is tr...

Страница 7: ...terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded control units to the break glass unit connected to the master smoke control unit Alarm message 1 x change over contact max l...

Страница 8: ...y every 2 min Review of fuses Mains 630mA slow blow Motor 4 A slow blow Battery 630mA medium slow blow Type of connection to external Mains screw terminal plug screw terminals 0 5 2 5qmm Cable monitor...

Страница 9: ...control and remove the housing top section door from the housing bottom section Fasten the housing bottom section in the wall cut out cut out dimension 335 x 350 x 95 and refit the housing top sectio...

Страница 10: ...imum cable length always routed from the central smoke control unit to the last junction box Actuating current Sum of all motor currents per group module Note Do not use the green yellow wire Per moto...

Страница 11: ...Cable plan ____________________________________________________________________________ 11...

Страница 12: ..._____________________________________________________ 12 WLA 330 WLA331 WSA 300 WSC 304 6102 WSK 320 WSK 330 First or secundary Break glass unit If only one break glass unit usa a main break glass uni...

Страница 13: ...Various wiring diagrams ____________________________________________________________________________ 13...

Страница 14: ...from one face of the supplied foam rubber Glue each foam rubber to the bottom side of the accumulators Connect the accumulators to the black accumulator bridge according to the wiring diagram then co...

Страница 15: ...b The green mains and operating LED s are OFF the yellow accumulator Led is flashing control unit in the accumulator mode The malfunction message at the break glass unit is ON c The ventilation butto...

Страница 16: ...and clamping screws for firm seating Carry out a test run of the entire system see chapters Start up and Test Run Only have defective units repaired in our factory Only install original spare parts C...

Отзывы: