Example of an error message  

”7 blinks – 1sec. pause – 2 blinks – 1 sec. pause – 1 blinks”.  

1.  There is an error on a local input 
2.  The error is on input X10.5, to which a rain sensor might be connected 
3.  The error is due to no connection to the sensor. 

 
If there are more errors on the MotorController simultaneously, they are shown with priority, i.e. the error message for the most 
critical error is shown first and repeated until rectified. Then the error message number 2 is shown and repeated as well until the 
error is rectified etc. Below table, list the most common errors. 

Error message

 

1. Blink sequence  

2. Blink sequence 

3. Blink sequence 

Number 
of blink 

Error on 

Number 
of blink 

Error on or error type  

Number 
of blink 

Error type  

System 

Internal error (Watchdog 
reset) 

 

 

Internal error (Program 
CRC) 

 

 

Actuator  

1-8 

X1-X8 (actuator output) 

Actuator configuration 

– check the actuators, 

check the configuration, when using ±24V 
standard actuators check the termination  

Expected number of actuators, the found and 
expected number of MotorLink

®

 actuators 

does not match 

– check actuator connections 

Internal error 

Local 
input 

17 

X9.1 (rain sensor) 

Termination 

– check connection of sensor as 

well as termnation 

10 

Power 
supply  

Internal error 

 

 

Mains 

– check connection  

 

 

Internal error 

 

 

 
If other errors 

or an “Internal error” are indicated, please contact WindowMaster.  

13 

Hardware error 

If there are any hardware error on the MotorController

 

it will be indicated by the diodes (yellow diode is lit). 

14 

Commissioning and test run 

In case of hardware error please see chapter 13 

“‘Hardware error”. To configure the

 

MotorController

 

press  

„↑“ and „↓“ (on the 

input card) at the same time for 10 seconds, see chapter 11. 
 
We recommend that the software of the MotorController

 

is updated the annual maintenance check! 

14.1 

The 

MotorController

 

is completely installed, without the operating voltage 

applied 

a)  Check all mechanical and electrical components for damage. 
b)  Check all screw and plug connections for tightness and/or firm seating 
c)  Check that all external components are installed: 

1) ±24V actuators: check polarity  

14.2 

With mains voltage 

Adhere to the relevant regulations!  
Connect the mains cables and reapply the mains voltage. 

14.3 

Ventilation keypad 

Closely observe the actuators during opening and closing. They must not be impaired in any position by the building structure. 
Observe that the actuator cables are

 

not being subject to pulling or pinching. Check each ventilation keypad individually. 

14.4 

Wind/rain detector 

a)  Open the actuators with the comfort ventilation keypads. 
b)  Wet the rain sensor, the actuators will fully close. 
c)  While the actuators are running, press the Open button at the keypad. The actuators must neither open nor stop! 

Exception: If a manual override time (Man. operation after auto comm.). 

 
If the start-up was successful, mount the door of the MotorController. 

 

If the start-up was unsuccessful (error with one of the test run processes), please 

see chapter 10 “Description of cards”. 

If necessary, check the wiring in accordance with the cable plan 

– see chapter 9 “Cable plan for connection to WCC 3xx”. 

Содержание MotorController WCC 310

Страница 1: ...K WindowMaster 2016 2017 WindowMaster is a registred trademark used under the license by WindowMaster International A S WindowMaster International A S Skelstedet 13 DK 2950 Vedbæk WCC 310 WCC 320 Standard versions Installation instruction MotorController Version 1711 for firmware from version 1 22 motorline card Save this installation instruction to the end user ...

Страница 2: ... Max cable length 24V standard actuators 9 8 1 3 Max cable length actuators with MotorLink 9 9 Cable plan for connection to WCC 310 320 Standard version 11 10 Description of cards and mains connection 12 10 1 WCC connection to mains and power supply units WCA 3P3 WCA 3P5 and WCA 3P6 12 10 2 Motor line card WCA 3M4 and WCA 3M8 13 10 3 Input card WCA 3KI 15 10 4 Power supply card WCA 3P6 17 11 Confi...

Страница 3: ...mage to assets The connection of the MotorController is reserved for qualified personnel Disconnect all poles of the MotorController from the supply voltage prior to opening installation or assembling Installation and use according to the national regulations 1 3 Application The MotorController is exclusively designed for the automatic opening and closing of windows flaps or doors Always check tha...

Страница 4: ...fieldbus interface for KNX If additional motor lines inputs or fieldbus connection is required a Plus version of the MotorController is necessary Motor groups and motor lines A motor group consists of one or more motor lines and all the motor lines are operated simultaneously All motor lines on the motor cards WCA 3M4 WCA 3M8 can be configured for either a 24V standard actuators or MotorLink actua...

Страница 5: ...er consumption of all the connected actuators must not exceed 10A or 20A depending on MotorController size Per motorline Per 10A MotorController Per 20A MotorController 24V Actuators MotorLink Actuators 24V Actuators MotorLink Actuators 4 Motorlines 24V Actuators MotorLink Actuators 8 Motorlines WMS 306 1 10 4 10 10 20 20 WMS 306 2 10 2 10 8 20 16 WMS 306 3 9 3 9 9 18 18 WMS 306 4 8 4 8 8 20 20 WM...

Страница 6: ...826 2 10 2 10 8 20 16 WMX 803 804 823 826 3 9 3 9 9 18 18 WMX 803 804 823 826 4 8 4 8 8 20 20 WML 820 825 10 0 10 0 20 0 WML 860 1 10 4 10 10 20 20 WML 860 2 10 2 10 8 20 16 WML 860 3 9 3 9 9 18 18 WML 860 4 8 4 8 8 20 20 WMB 801 802 max 4A connected to WMB WMB 811 812 10 2 10 8 20 16 Do not exceed the total power consumption of the motor line When having two locking actuators per motor line it mu...

Страница 7: ...n cable Actuators Other components flexible max 6 mm solide max 10 mm min 0 2mm max 1 5mm Operating conditions 5 C 45 C for indoor installation the MotorController may not be covered Max actuator activation duration duty cycle ED 40 4min per 10min Number of motor lines WCC 310 4 x 10A motor line for 24V standard or MotorLink motors WCC 320 8 x 10A motor line for 24V standard or MotorLink motors Ma...

Страница 8: ... are visible and well accessible Do not install behind protruding walls door panels or hidden by the building structure 7 5 Assembly instructions Always have assembly installation repair and maintenance of ventilation systems carried out by qualified personnel trained for this purpose Rules to be adhered to for setting up and installation The following safety relevant rules have to be adhered to w...

Страница 9: ...wire in the motor cable for communication Example Max actuator cable length with cable cross section 0 75mm2 and actuator current 2A 2 x 56 x 0 75 2 x 2 21m 8 1 2 Max cable length 24V standard actuators The actuator supply cable must have 2 wires If cable monitoring is requested min 3 2 wires current carrying 1 wire for monitoring 24V standard Actuators Do not use the PE wire green yellow wire cab...

Страница 10: ...oss section a Total actuator current I 3 wire 0 75mm 3 wire 1 50 mm 5 wire 1 50 mm 2 wire parallel 3 wire 2 50 mm 5 wire 2 50 mm 2 wire parallel 3 wire 4 00 mm 1A 42m 50m 2A 21m 40m 50m 3A 14m 28m 50m 47m 50m 4A 11m 21m 42m 35m 5A 8m 17m 34m 28m 50m 45m 6A 7m 14m 28m 23m 47m 37m 7A 6m 12m 24m 20m 40m 32m 8A 5m 11m 21m 18m 35m 28m 9A 9m 18m 15m 31m 25m 10A 8m 16m 14m 28m 22m 20A 4m 8m 7m 14m 11m ...

Страница 11: ...11 9 Cable plan for connection to WCC 310 320 Standard version Above connection plan shows a WCC 320 MotorController ...

Страница 12: ...r 3 2 10 1 WCC connection to mains and power supply units WCA 3P3 WCA 3P5 and WCA 3P6 The MotorController WCC 310 is supplied with a 305W SMPS power supply WCA 3P3 The MotorController WCC 320 is supplied with a 605W SMPS power supply WCA 3P5 The power supply is regardless of size placed in the bottom of the MotorController beneath the motor line and input card An AUX WCA 3P6 to which mains is conn...

Страница 13: ...pe the total power consumption of actuators connected to a motor line can max be 10A and the total max power consumption for both motor lines must not exceed 10A or 20A depending on type of MotorController Besides actuators also locking actuators espagnolettes actuators type WMB 801 802 and WMB 811 812 can be connected The power consumption of the locking actuators are not to be included in the 10...

Страница 14: ...ard can each be connected to one of the below shown combinations 1 single one window with one single window actuator Up to four windows each with one single window actuator can be connected 2 double one window with two double window actuators 3 triple one window with three triple window actuators 4 quad one window with four quad window actuators Cable monitoring When using actuators with MotorLink...

Страница 15: ...3KI and J6 på WCA 3M4 WCA 3M8 S3 X1 X8 For connection of comfort keypads For WCC 310 0410 with only 4 motorlines input X5 X8 have no function With the default values are input Active if the contact resistance is smaller than 2kΩ Inactive if the contact resistance is bigger than 3kΩ Input has pull up current of approx 0 8mA min 0 7mA max 1mA Example comfort keypad connected to input X3 Long push 50...

Страница 16: ...e supply voltage Input has pull up approx 1mA min 0 7mA max 1 4mA Connection of wind rain and rain sensors WLA 330 and WLA 331 the settings of the sensors are set on the sensor DIP switch 1 3 on WLA 330 must be set for wind speed tolerances Please refer to the installation instruction for WLA 330 for DIP switch settings If no wind rain or rain sensor is connected to S3X9 a 10kΩ resistor must be co...

Страница 17: ...he motor line card blinks after a configuration an error has occurred in the configuration see chaptor Fault detection via LED for identification of errors Actuators are to be connected on the motor lines 24V standard actuators and actuators with MotorLink can be connected to all motor lines but a motor line can only be connected to one type of actuators either 24V standard or MotorLink actuators ...

Страница 18: ...cated by the diodes yellow diode is lit 14 Commissioning and test run In case of hardware error please see chapter 13 Hardware error To configure the MotorController press and on the input card at the same time for 10 seconds see chapter 11 We recommend that the software of the MotorController is updated the annual maintenance check 14 1 The MotorController is completely installed without the oper...

Страница 19: ...software of the MotorController is updated the annual maintenance check The expected minimum lifetime for the MotorController is 10 years 15 1 Maintenance agreements WindowMaster offer maintenance agreements for the ventilation system Contact our service department for further information telephone 44 1536 510990 or info windowmaster co uk 15 2 Replacement 3M4 3M8 and 3KI card 1 Disconnect the 230...

Отзывы: