18
Example of an error message
”7 blinks – 1sec. pause – 2 blinks – 1 sec. pause – 1 blinks”.
1. There is an error on a local input
2. The error is on input X10.5, to which a rain sensor might be connected
3. The error is due to no connection to the sensor.
If there are more errors on the MotorController simultaneously, they are shown with priority, i.e. the error message for the most
critical error is shown first and repeated until rectified. Then the error message number 2 is shown and repeated as well until the
error is rectified etc. Below table, list the most common errors.
Error message
1. Blink sequence
2. Blink sequence
3. Blink sequence
Number
of blink
Error on
Number
of blink
Error on or error type
Number
of blink
Error type
1
System
1
Internal error (Watchdog
reset)
2
Internal error (Program
CRC)
5
Actuator
1-8
X1-X8 (actuator output)
1
Actuator configuration
– check the actuators,
check the configuration, when using ±24V
standard actuators check the termination
2
Expected number of actuators, the found and
expected number of MotorLink
®
actuators
does not match
– check actuator connections
4
Internal error
7
Local
input
17
X9.1 (rain sensor)
1
Termination
– check connection of sensor as
well as termnation
10
Power
supply
1
Internal error
2
Mains
– check connection
5
Internal error
If other errors
or an “Internal error” are indicated, please contact WindowMaster.
13
Hardware error
If there are any hardware error on the MotorController
it will be indicated by the diodes (yellow diode is lit).
14
Commissioning and test run
In case of hardware error please see chapter 13
“‘Hardware error”. To configure the
MotorController
press
„↑“ and „↓“ (on the
input card) at the same time for 10 seconds, see chapter 11.
We recommend that the software of the MotorController
is updated the annual maintenance check!
14.1
The
MotorController
is completely installed, without the operating voltage
applied
a) Check all mechanical and electrical components for damage.
b) Check all screw and plug connections for tightness and/or firm seating
c) Check that all external components are installed:
1) ±24V actuators: check polarity
14.2
With mains voltage
Adhere to the relevant regulations!
Connect the mains cables and reapply the mains voltage.
14.3
Ventilation keypad
Closely observe the actuators during opening and closing. They must not be impaired in any position by the building structure.
Observe that the actuator cables are
not being subject to pulling or pinching. Check each ventilation keypad individually.
14.4
Wind/rain detector
a) Open the actuators with the comfort ventilation keypads.
b) Wet the rain sensor, the actuators will fully close.
c) While the actuators are running, press the Open button at the keypad. The actuators must neither open nor stop!
Exception: If a manual override time (Man. operation after auto comm.).
If the start-up was successful, mount the door of the MotorController.
If the start-up was unsuccessful (error with one of the test run processes), please
see chapter 10 “Description of cards”.
If necessary, check the wiring in accordance with the cable plan
– see chapter 9 “Cable plan for connection to WCC 3xx”.