Figure 10 overview of the smoke panel and how the different components are connected it.
4.2 Configuration
See previous examples for the configuration of the motor lines, motor groups, break glass unit, comfort
keypads and BMS.
4.2.1 Configuration of the CAN bus
To configure the CAN bus
In section 1
Press “Configuration”
“arrow down”
“CAN”
Set the “MC ID” = 1
Set the “CAN bus mode” = “Independent buses”
In section 2
Press “Configuration”
“arrow down”
“CAN”
Set the “MC ID” = 2
Set the “CAN bus mode” = “Independent buses”
4.2.2 Configuration of Smoke area 1
In section 1 associate
a. motor line S4.x1 with motor group 1.
b. motor line S5.x2 with motor group 2.
c. motor line S5.x3 with motor group 3.
d. motor groups 1, 2 and 3 with smoke zone 1.
e. The break glass unit with smoke zone 1.
In section 2 associate
a. motor line S3.x1 and 3.x2 with motor group 1.
b. motor line S4.x1 and 4.x2 with motor group 2.
c. motor groups 1 and 2 with smoke zone 5.