Winco WL22000VE/A Скачать руководство пользователя страница 10

10

REV A

OPM-110

YOURGEN 

The WINCO YourGen meter allows you to see useful information about 

your generator from the front panel by displaying RPMs, Voltage, 

frequency, load, hours, and maintenance reminders. It also has the 

ability to display warnings if any parameter gets outside of normal 

operation range. 

Cycle Button (      ) -

During normal operation, the display will toggle through on fixed delay. 

If you want to see any specific item, you can press the cycle button to 

move it to that setting. Once the display is selected, the delay before it 

starts toggling is approximately 5 seconds. This button is also used to 

reset maintenance reminders.

RPM - 

The meter will display the RPMs of the engine. This number is 

calculated based upon frequency and is not directly measured from the 

engine. The engine-generator must be run at the correct speed in order 

to produce the proper electrical voltage and frequency.

CAUTION: EQUIPMENT DAMAGE

The output voltage should be checked to ensure the generator is 

working properly prior to connecting a load to the generator. Failure to 

do so could result in damage to equipment plugged into the unit and 

possible injury to the individual.

Operating Speed 

All engines have a tendency to slow down when a load is applied. 

When the electrical load is connected to the generator, the engine is 

more heavily loaded, and as a result, the speed drops slightly. This 

slight decrease in speed, together with the voltage drop  within the 

generator itself, results in a slightly lower voltage when the generator 

is loaded to its full capacity than when running no load. The slight 

variation in speed also affects the frequency of the output current. 

This frequency variation has no appreciable effect in the operation of 

motors, lights, and most appliances. However, electronic equipment 

and clocks will be affected if correct RPM is not maintained. See Load 

vs. Output chart.

Although individual units and models vary slightly, the normal voltage 

and frequency of the engine-generator described in this manual are 

approximately as follows, under varying loads:

LOAD vs. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

120V 

Recpt

240V 

Recpt

None

3690

61.5

120V

240V

Half

3600

60.0

120V

240V

Full

3510

58.5

120V

240V

To connect these units directly to an un-powered, isolated construction 

site TemPower panel, have your electrician connect to the control panel  

using a 120/240 Volt, 4-wire twist-lock plug (14-60P).

NOTE:

 Never attempt to use the 240 Volt 3-wire receptacle to wire into 

a building. This is a GFCI circuit and is designed for 240 Volt output 

only. It has no neutral connection. If you attempt to draw 120 Volt from 

this receptacle, the GFCI breaker will trip.

2. If the generator set is connected to an existing distribution system, 

a fully isolated manual transfer switch must be installed. The transfer 

switch prevents damage to the generator and the other circuit 

components if main line power is restored while the generator is 

connected. Installing a transfer switch also permits the use of normal 

fusing.

3.Many homes and construction sites are wired for at least 60 to 100 

Amp entrance service, much greater than the capacity of this portable 

generator. When installing the generator at these sites, a secondary 

emergency distribution panel may have to be installed. The emergency 

distribution panel must be installed by a licensed electrician according 

to all applicable codes. The electrician will move the critical circuits to 

be powered during the outage to the emergency panel. Keep in mind 

only a limited amount of amperage is available from the generator set. 

Some circuit breakers may still have to be turned off to prevent an 

overload on the generator during the initial start up. See the nameplate 

on your generator for the amperage capabilities of your unit.

CAUTION: EQUIPMENT DAMAGE

Failure to properly limit and balance the load applied to the generator 

will cause the generator to produce low voltage and may damage 

the engine generator set. It may also cause severe damage to the 

loads connected to the generator at that time. Improper loading of the 

generator set constitutes abuse and will not be covered by warranty.

Содержание WL22000VE/A

Страница 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS WL22000VE A GENERATOR MANUAL...

Страница 2: ...lowed during installation and maintenance of the generator Read and understand all instructions in the manual before starting and operating the generator USING THIS MANUAL Congratulations on your choi...

Страница 3: ...J1 Spark Plugs 792015 Air Filter 692519 Pre Cleaner Filter 692520 Oil Filter 842921 Fuel Filter 845125 Spark Plug Gap 0 030 in Intake Valve Clearance 0 004 0 006 in Exhaust Valve Clearance 0 007 0 009...

Страница 4: ...tion B Guard against electric shock C Avoid contact with live terminals or receptacles D Use extreme care if operating this unit in rain or snow E Use only three prong grounded plugs and extension cor...

Страница 5: ...This generator is capable of producing 79 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage to insure compatibility Remember that power taken from C redu...

Страница 6: ...keeping the crankcase full cannot be overemphasized Engine failures resulting from inadequate or improper lubricant are considered abuse and not covered by the generator or engine manufacturer s warra...

Страница 7: ...o the Bat terminal Make sure all connections are clean an tight Reverse the sequence when disconnecting disconnect the negative cable first These engines produce enough direct current to keep the batt...

Страница 8: ...gasoline is blended to improve starting Do not use summer grade gasoline 2 HOT WEATHER A Use the proper oil for the temperature expected B Use only summer blended gasoline Using gasoline left over fr...

Страница 9: ...hich grounding you require If you are not sure what to do contact a competent professional to assist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO port...

Страница 10: ...ne generator described in this manual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 120V 240V Half...

Страница 11: ...L1 and Line 2 L2 1 25 25 50 50 75 75 100 It is good practice to monitor the YourGen Meter when applying load This will ensure the generator is balanced Balanced Unbalanced 120 Volt and 240 Volt recep...

Страница 12: ...ain valve for your convenience Attach a neoprene hose and drain the oil into an approved container 3 Remove the oil filter and dispose of it properly 4 Before you install the new oil filter clean the...

Страница 13: ...ely dirty replace with a new filter You can use pressurized air not to exceed 30 psi to clean the filter Always blow the compressed air from inside to the outside 6 Wash the pre cleaner F in liquid de...

Страница 14: ...ly should it be needed in an emergency GENERATOR MAINTENANCE Any major generator service including the installation or replacement of parts should be performed only by a qualified electrical service t...

Страница 15: ...15 REV A OPM 110 G1 G1 G2 G2 G2 N N N N N N N GND GND GND GND GND GND G2 G2 G2 G2 G2 G2 G2 G2 G1 G1 G1 G1 G1 G1 G1 G1 G1 RECEPTACLE WIRING DIAGRAM...

Страница 16: ...e consumables or labor This warranty does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment WIN...

Отзывы: