GROUNDING

All units must be grounded. Drive a 3/4 or 1” cop-

per pipe or rod into the ground close to the engine-

generator set. The pipe must penetrate moist earth. 

Connect an approved ground clamp to the pipe. 

Run a no. 10 Awg wire from clamp to the generator 

ground lug on the receptacle panel. Do not connect to 

a water pipe or to a ground used by a radio system.

The engine-generators covered in this manual were 

designed primarily for portable use.  If you are con-

necting into a building wiring system that is already 

grounded using the 14-60 4 wire plug, you do not 

have to ground the unit. 

 

WARNING: PERSONAL DANGER 

 

DO NOT OPERATE THIS GENERATOR INDOORS. 

The unit should be stored in a warm dry location. Dur-

ing a power outage, move the unit outdoors to a flat 

dry location such as a driveway or sidewalk

.

 

 

WIRING

Plug your tools such as drills, saws, blowers, sump 

pump and other items to be powered directly into 

the generator receptacles.  Before plugging in all the 

tools and cord sets, recheck the rating of the genera-

tor set.  Be sure it can handle the intended load and 

is compatible with the voltage, phase, and current rat-

ings.  ‘Hard Wiring’ this unit directly into a temporary 

construction site electrical system is

 NOT A SIMPLE 

DO-IT-YOURSELF JOB.

  For your safety, all wiring 

must be done by a qualified electrician and conform 

to the National Electric Code and comply with all 

state and local codes and regulations.  Check with 

local authorities before proceeding.

WARNING: PERSONAL DANGER

    A fully isolated, double pole double throw manual 

transfer switch must be installed any time a generator 

is being connected to an existing distribution system.

 

 

1.  These engine generator sets are designed for 

portable heavy duty commercial use.  Receptacles 

are provided on the control panel to permit 10 and 

40 volt portable appliances and tools to be plugged 

directly into them.  Please note that the 3-wire 40 

volt receptacle(s) on these units are designed to 

power only 40 volt tools. There are two hot leads 

and a ground wire, but no neutral connection, in the 

3-wire 40 volt receptacle.  A 4-wire receptacle (two 

hot, one ground, and one neutral) has been provided 

on the control panel for use in temporary power ap-

plications requiring 10/40 volt power.  Consult a 

licensed electrician for wiring the TemPower plug and 

connecting it as temporary service.  

To connect these units directly to an un-powered, 

isolated construction site TemPower panel, have 

your electrician connect to the control panel using a 

120/240 volt, 4-wire plug (14-60P). 

NOTE:  Never attempt to use the 40 volt three wire 

receptacle to wire into a building.  

.  If the generator set is be connected to an existing

distribution system, a fully isolated manual trans-

fer switch must be installed.  The transfer switch 

prevents damage to the generator and other circuit 

components if main line power is restored while the 

generator is connected.  Installing a transfer switch 

also permits the use of normal fusing.

3.  Many homes and construction sites are wired 

for at least 60 to 100 Amp entrance service, much 

greater than the capacity of this portable genera-

tor.  When installing the generator at these sites, a 

secondary emergency distribution panel may have to 

be installed, such as the Emergency Transfer/Service 

(ET/S) system available through your WINCO dealer.  

The emergency distribution panel must be installed 

by a licensed electrician according to all applicable 

codes.  The electrician will move the critical circuits 

to be powered during the outage to the emergency 

panel.  Keep in mind only a limited amount of amper-

age is available from the generator set.  Some circuit 

breakers may still have to be turned off to prevent an 

overload on the generator during the initial start up.  

See the nameplate on your generator for the amper-

age capabilities of your unit.

CAUTION: EQUIPMENT DAMAGE

    Failure to properly limit and balance the load ap-

plied to the generator will cause the generator to 

produce low voltage and may damage the engine 

generator set. It may also cause severe damage to 

the loads connected to the generator at that time. Im-

proper loading of the generator set constitutes abuse 

and will not be covered by warranty.

Содержание WL18000VE

Страница 1: ...INSTALLATION AND OPERATORS MANUAL INDUSTRIAL PORTABLE WL18000VE N WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com ...

Страница 2: ...eparation 5 Battery Installation 6 Basic Operation 7 INITIAL START UP 7 Electric Starting 8 Stopping Storage 9 Operating Speed 9 CONNECTING THE LOADS 9 Wiring 10 ENGINE CARE 11 GENERATOR CARE 12 TROUBLESHOOTING 13 CONTROL PANEL WIRING DIAGRAM 14 WARRANTY INFORMATION 15 PROPER USE AND INSTALLATION You must be sure your new engine generator set is Properly serviced before starting Operated in a well...

Страница 3: ...dren c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel only in an approved container and only in a well ventilated area f Follow local codes for closeness to combustible material 3 DEADLY EXHAUST GAS Exhaust fumes from any gasoline engine contain carbon mon...

Страница 4: ...are third party companies making enclosures for generators that have been properly engineered The use of these third party enclosures is acceptable as long as they have been certified and meet current code DO NOT attempt to operate at 50 cycles These units are designed and governed to operate at 60 cycles only UNIT CAPABILITIES GENERATOR CONNECTIONS WL180000VE 120 volt and 240 volt receptacles are...

Страница 5: ...en filling the crankcase the first time use the dipstick ref A to ensure that you do not over fill the crankcase Reference B shows the full oil level mark on the dipstick Oil is added to the engine by removing the oil fill cap ref C and adding oil at this point After filling the crankcase to the proper level be sure you properly tighten the oil fill cap NOTE This engine generator must be on a leve...

Страница 6: ...ll not burn properly The use of fuel additives such as STA BIL or an equivalent will minimize the formation of fuel gum deposits If a unit has been out of operation for an extended period of time it is best to drain old fuel from the engine and replace with fresh fuel before attempting to start See the engine manual for special instruction for operating this unit at over 5000 feet BATTERY INSTALLA...

Страница 7: ... before operating the generator Failure to properly restrict unit movement will allow the unit to move causing damage to the unit drop cords or loads OIL ALERT SYSTEM This WINCO Industrial generator is equipped stan dard with low oil shutdown systems The Briggs and Stratton engine uses an oil pressure switch system This low oil warning system will automatically stop the engine before the oil level...

Страница 8: ...an approved container c Start the engine and allow it to run until all the fuel in the carburetor and the fuel lines has been used up and the engine stops Note Running the engine to use up the fuel in the lines and carburetor will still leave a small amount of fuel in the carburetor It is best for extended storage to treat the fuel before draining d While the engine is warm drain the oil and refil...

Страница 9: ...o circu late throughout the engine A short warm up time will permit the engine to work more efficiently when the load is applied and will reduce the wear in the engine extending its life Receptacles have been provided to allow loads to be connected to the generator The loads should be added one at a time If a large motor is being started or multiple motors are being started they should be started ...

Страница 10: ...e are two hot leads and a ground wire but no neutral connection in the 3 wire 240 volt receptacle A 4 wire receptacle two hot one ground and one neutral has been provided on the control panel for use in temporary power ap plications requiring 120 240 volt power Consult a licensed electrician for wiring the TemPower plug and connecting it as temporary service To connect these units directly to an u...

Страница 11: ...e oil level is maintained Fill to the FULL mark on the dipstick 3 Dual Element Air Filter Clean and or replace foam pre cleaner and air filter annually or every 100 hours Service more often under dusty conditions WARNING EQUIPMENT DAMAGE Never start or run the engine with the air filter re moved a Loosen snaps Ref A and remove cover Ref B VanguardEngines com sengaged osition Figure 4 Operate the e...

Страница 12: ...ry out any moisture that has accumulated in the windings If left this moisture can cause corrosion in the winding Frequent operation of the engine generator set will also insure that the set is operating properly should it be needed in an emergency 2 Generator Maintenance Any major genera tor service including the installation or replacement of parts should be performed only by a qualified electri...

Страница 13: ...Defective receptacle No residual magnetism in generator Defective stator Defective rotor field Shorted capacitor Shorted diodes on rotor GFCI Receptacle tripped GENERATOR SPECIFICATIONS Generator manufacturer MECC Alte Spa Generator model number S20F 230A Part number 16428 002 Rotor resistance 8 04 Ohms Stator resistance 0 056 Ohms Cap winding resistance 0 41Ohms Capacitors 2 35 mF 1 31 5 mF Capac...

Страница 14: ...3110 00 14 60706 239 CONTROL PANEL WIRING DIAGRAM ...

Страница 15: ...t WINCO Authorized Service Center or to WINCO Inc at Le Center Minnesota THERE IS NO OTHER EXPRESS WARRANTY To the extent permitted by law any and all warranties including those of merchantability and fitness for a particular purpose are limited to 24 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the dur...

Страница 16: ...URER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or replaced by WINCO OWNER S WARRANTY RESPONSIBILITIES As the generator owner you are responsible for performance of the required maintenance listed in your owner s manuals WINCO recommends that you retain a...

Отзывы: