GENERATOR CARE

Proper care and maintenance of the generator is necessary 

to ensure a long trouble free life.

EXERCISING THE GENERATOR

The generator should be operated every three to four 

weeks. It should be operated for a period of time sufficient 

to warm the unit up and to dry out any moisture that has 

accumulated in the windings. If left, this moisture can cause 

corrosion in the winding. Frequent operation of the engine-

generator set will also ensure that the set is operating 

properly should it be needed in an emergency.

GENERATOR MAINTENANCE

Any major generator service, including the installation 

or replacement of parts, should be performed only by a 

qualified electrical service technician. USE ONLY FACTORY 

APPROVED REPAIR PARTS.

  A. Bearing - The bearing used in these generators is a 

    heavy duty, double sealed ball bearing. They require 

    no maintenance or lubrication.

  B. Receptacles - Quality receptacles have been utilized. If a 

    receptacle should become cracked or otherwise 

    damaged, replace it. Using damaged or cracked 

    receptacles can be both  dangerous to the operator 

    and destructive to the equipment.

CLEANING

Remove dirt and debris with a cloth or brush. DO NOT 

use high pressure spray to clean either the engine or the 

generator. The high pressure spray could contaminate the 

fuel system and the generator components.

1. Keep the air inlet screen on both the engine and 

  generator free of any dirt or debris to ensure proper 

  cooling. At least yearly, remove the blower housing on 

  the engine and clean the chaff and dirt out of the engine 

  cooling fins and fly wheel. Clean more often if necessary. 

  Failure to keep these areas clean may cause overheating 

  and permanent damage to the unit.

2. Periodically clean muffler area to remove all grass, dirt, 

  and combustible debris to prevent a fire.

3. On engine mufflers equipped with spark arresters, the 

  spark arrester must be removed every 50 hours for 

  cleaning and inspection. Replace if damaged.

TROUBLESHOOTING TABLE

Problem

Possible Causes

Won’t start

Low oil level
Fouled spark plug
Out of fuel
Start switch in OFF position
Fuel Valve turned off
Plugged fuel filter
Blown fuse in key switch

Voltage too low

Engine speed is too low
Generator overloaded
Defective stator
Defective rotor (field)
Adjust AVR
Defective AVR

Circuit breaker trips

Defective load
Defective receptacle
Excessive load

Voltage too high

Engine speed is too high

Generator overheating

Overloaded
Insufficient ventilation

No output voltage

Short in load (disconnect)
Tripped or defective circuit breaker
Broken or loose wire
Defective receptacle
No residual magnetism (in generator)
Defective stator
Defective rotor (field)
GFCI receptacle tripped
Adjust AVR
Defective AVR

Содержание WL12000HE-04/A

Страница 1: ...ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ___________________________________...

Страница 2: ...AVR WIRING 13 GENERATOR CARE 14 EXERCISING THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING TABLE 14 WIRING DIAGRAM 15 CALIFORNIA EVAPORATIVE EMISSION CONTROL 16 LIMITED WARRANTY 16 SAVE T...

Страница 3: ...IRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke...

Страница 4: ...w enough free flow of fresh air to reach the engine generator set for cooling and will cause the unit to overheat damaging both the engine and generator Small compartments will also develop hot spots...

Страница 5: ...se motors are very hard to start and require 5 to 7 times as much starting current as running current Capacitor motors are easier to start and usually require 2 to 4 times as much starting current as...

Страница 6: ...ill with the recommended oil to the upper limit mark on the oil level dipstick Running the engine with a low oil level can cause engine damage This type of damage is not covered by the Distributor s L...

Страница 7: ...EGATIVE battery terminal to GROUND For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the Bat terminal Make sure all connect...

Страница 8: ...Turn the engine switch to the START position and hold it there until the engine starts If the engine fails to start within 5 seconds release the engine switch and wait at least 10 seconds before oper...

Страница 9: ...ngine generator described in this manual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage None 3690 61 5 125V Half 3600 60 0 120V Full 3510...

Страница 10: ...d which grounding you require If you are not sure what to do contact a competent professional to assist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO p...

Страница 11: ...ution panel must be installed by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in...

Страница 12: ...d by this engine for refuelling With the engine stopped and on a level surface remove the fuel filler cap and check the fuel level Refill the tank if the fuel level is low Never use stale or contamina...

Страница 13: ...ug that came in the engine and check gap before installing Spark plug gap is 0 030 Poor spark will also occur if spark plug wire does not fit firmly on spark plug If this happens reform the terminal t...

Страница 14: ...The high pressure spray could contaminate the fuel system and the generator components 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling...

Страница 15: ...15 OPM 152 A WIRING DIAGRAM GND GND GND GND N N N N G3 G3 G3 G3 G2 G2 G2 G2 G1 G1 G1 G1 GND GND N G3 G3 G2 G2 G1 G1 208V 230V 480V...

Страница 16: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Отзывы: