11

OPM-152/A

2. If the generator set is connected to an existing 

  distribution system, a fully isolated manual transfer switch 

  must be installed. The transfer switch prevents damage to 

  the generator and the other circuit components if main 

  line power is restored while the generator is connected. 

  Installing a transfer switch also permits the use of normal 

 fusing.

3.Many homes and construction sites are wired for at least 

  60 to 100 Amp entrance service, much greater than the 

  capacity of this portable generator. When installing 

  the generator at these sites, a secondary emergency 

  distribution panel may have to be installed. The 

  emergency distribution panel must be installed by a 

  licensed electrician according to all applicable codes. 

  The electrician will move the critical circuits to be 

  powered during the outage to the emergency panel. 

  Keep in mind only a limited amount of amperage is 

  available from the generator set. Some circuit breakers 

  may still have to be turned off to prevent an overload on 

  the generator during the initial start up. See the 

  nameplate on your generator for the amperage 

  capabilities of your unit.

CAUTION: EQUIPMENT DAMAGE

Failure to properly limit and balance the load applied to 

the generator will cause the generator to produce low 

voltage and may damage the engine generator set. It may 

also cause severe damage to the loads connected to the 

generator at that time. Improper loading of the generator 

set constitutes abuse and will not be covered by warranty.

Содержание WL12000HE-04/A

Страница 1: ...ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER ___________________________________...

Страница 2: ...AVR WIRING 13 GENERATOR CARE 14 EXERCISING THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING TABLE 14 WIRING DIAGRAM 15 CALIFORNIA EVAPORATIVE EMISSION CONTROL 16 LIMITED WARRANTY 16 SAVE T...

Страница 3: ...IRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke...

Страница 4: ...w enough free flow of fresh air to reach the engine generator set for cooling and will cause the unit to overheat damaging both the engine and generator Small compartments will also develop hot spots...

Страница 5: ...se motors are very hard to start and require 5 to 7 times as much starting current as running current Capacitor motors are easier to start and usually require 2 to 4 times as much starting current as...

Страница 6: ...ill with the recommended oil to the upper limit mark on the oil level dipstick Running the engine with a low oil level can cause engine damage This type of damage is not covered by the Distributor s L...

Страница 7: ...EGATIVE battery terminal to GROUND For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the Bat terminal Make sure all connect...

Страница 8: ...Turn the engine switch to the START position and hold it there until the engine starts If the engine fails to start within 5 seconds release the engine switch and wait at least 10 seconds before oper...

Страница 9: ...ngine generator described in this manual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage None 3690 61 5 125V Half 3600 60 0 120V Full 3510...

Страница 10: ...d which grounding you require If you are not sure what to do contact a competent professional to assist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO p...

Страница 11: ...ution panel must be installed by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in...

Страница 12: ...d by this engine for refuelling With the engine stopped and on a level surface remove the fuel filler cap and check the fuel level Refill the tank if the fuel level is low Never use stale or contamina...

Страница 13: ...ug that came in the engine and check gap before installing Spark plug gap is 0 030 Poor spark will also occur if spark plug wire does not fit firmly on spark plug If this happens reform the terminal t...

Страница 14: ...The high pressure spray could contaminate the fuel system and the generator components 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling...

Страница 15: ...15 OPM 152 A WIRING DIAGRAM GND GND GND GND N N N N G3 G3 G3 G3 G2 G2 G2 G2 G1 G1 G1 G1 GND GND N G3 G3 G2 G2 G1 G1 208V 230V 480V...

Страница 16: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Отзывы: