14

OPM-139/E

Voltage  

 

 

3.0V DC

Battery Type 

 

CR2032 

Lifetime 

   10 

Years

The battery has a 10 year lifetime, in the event you need to 

change the battery, follow these instructions: 

The battery is located in the control box near potentially live 

AC terminals. To prevent electrocution while changing the 

battery disable the unit by disconnecting the main battery, 

spark plug wire and then open the receptacle panel. Locate 

the backside of the YourGen meter. Gently pry the back 

plate off using the slot located on top. 

 

Once open, the battery will be located at the top. Using a 

needle nose plier, carefully pull out the battery. 

Replace the battery having the POSITIVE (+) side down. 

Ensure the battery is secured between the battery 

connections. 

Replace the back plate of the meter and close the receptacle 

panel using the screws to secure it. Reconnect the unit’s 

main battery.

Battery

Install Battery Between These Two Points

It is good practice to monitor the YourGen Meter when 

applying load.

This will ensure the generator is balanced. 

 

 

 

Balanced                        Unbalanced

120 Volt and 120/240 Volt receptacles are provided for 

connection to various loads. 

The diagram below represents this 10,800 watt (rated 

output) generator. A & B represent the 120 volt output legs 

of this generator. Up to 5400 watts at 120 volts (45 Amps) 

can be drawn from the receptacles attached to either A 

or B output legs. This generator is capable of producing 

45 Amps of 240 volt current at C. Check the appliance 

or tool nameplates for the current and voltage to insure 

compatibility. Remember that power taken from C reduces 

the power available at equally both A and B and vice versa.

Change Oil Warning -

After the first 50 hours, the engine oil should be changed. 

The YourGen meter will light up the oil icon (         ) and the 

word ‘change’ will flash. Once the oil has been changed, 

press and hold the cycle button for approximately 5 

seconds until the warning has been removed from the 

display to reset the warning. The meter will then remind 

you of oil changes on the appropriate schedule for your 

generator. It is important to remember that the engine 

manufacturer recommends changing the oil on a calendar 

schedule even if the total number of operational hours have 

not been reached. Certain operating environments may 

also require more frequent oil changes.

Alarms  - 

The display will start blinking and toggle to the first 

parameter that is out of specification. The panel will remain 

flashing until the fault condition returns to within the 

acceptable range, see following table.

Acceptable Range

Frequency

57-63 Hz

Voltage

110VAC-130VAC

VAC1-VAC2

220VAC-260VAC

Battery - 

When the unit is off, the YourGen meter will display the 

hours continuously using a coin cell back-up battery inside 

the meter. Once the unit is running, the meter will get 

power from the main unit battery. 

Содержание WL12000HE-03/A

Страница 1: ...ld ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________...

Страница 2: ...E 17 WIRING DIAGRAM 18 WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation...

Страница 3: ...set or fuel tank D Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in an approved container and only in a well ventilated...

Страница 4: ...Generator Model Number S20FS 160 A Part Number 351836 1 Rotor Resistance 6 57 Ohms Stator Resistance 0 124 Ohms Cap Winding Resistance 0 60 Ohms Capacitors 31 5 mF Capacitor Part Number 300323 112 ENG...

Страница 5: ...e performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle asse...

Страница 6: ...out the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard starting load such as an air compre...

Страница 7: ...ine in a level position fill with the recommended oil to the upper limit mark on the oil level dipstick Running the engine with a low oil level can cause engine damage This type of damage is not cover...

Страница 8: ...EGATIVE battery terminal to GROUND For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the Bat terminal Make sure all connect...

Страница 9: ...e the starter Turn the engine switch to the START position and hold it there until the engine starts If the engine fails to start within 5 seconds release the engine switch and wait at least 10 second...

Страница 10: ...s and models vary slightly the normal voltage and frequency of the engine generator described in this manual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Fr...

Страница 11: ...sist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO portable generator ships with a bonded neutral You can safely use this generator without external gr...

Страница 12: ...ution panel must be installed by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in...

Страница 13: ...ual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 120V 240V Half 3600 60 0 120V 240V Full 3510 58 5...

Страница 14: ...from the receptacles attached to either A or B output legs This generator is capable of producing 45 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage t...

Страница 15: ...o length A Start the engine and warm it up stop the engine and remove the spark plug wire to prevent it from accidentally being started B This engine has an oil drain valve for your convenience Attach...

Страница 16: ...nt in clean engine oil and squeeze out all the excess before reinstalling it The engine will smoke when started if too much oil is left in the foam H Clean the dirt from the inside of the air cleaner...

Страница 17: ...igh pressure spray could contaminate the fuel system and the generator components 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling At le...

Страница 18: ...18 OPM 139 E WIRING DIAGRAM WL12000HE 03 A WL12000HE 03 C...

Страница 19: ...19 OPM 139 E WIRING DIAGRAM G1 G3 G3 G3 G3 G3 G3 G3 N G1 GND GND GND GND GND N N N N N G1 G1 G1 G1 G1 G1 G1 WL12000HE 03 B WL12000HE 03 D...

Страница 20: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Отзывы: