13

OPM-139/E

YOURGEN 

The WINCO YourGen meter allows you to see useful 

information about your generator from the front panel 

by displaying RPMs, Voltage, frequency, load, hours, and 

maintenance reminders. It also has the ability to display 

warnings if any parameter gets outside of normal operation 

range. 

Cycle Button (      ) -

During normal operation, the display will toggle through 

on fixed delay. If you want to see any specific item, you 

can press the cycle button to move it to that setting. Once 

the display is selected, the delay before it starts toggling is 

approximately 5 seconds. This button is also used to reset 

maintenance reminders.

RPM - 

The meter will display the RPMs of the engine. This number 

is calculated based upon frequency and is not directly 

measured from the engine. The engine-generator must be 

run at the correct speed in order to produce the proper 

electrical voltage and frequency.

CAUTION: EQUIPMENT DAMAGE

The output voltage should be checked to ensure the 
generator is working properly prior to connecting a load 
to the generator. Failure to do so could result in damage 
to equipment plugged into the unit and possible injury to 
the individual.

Operating Speed: All engines have a tendency to slow 

down when a load is applied. When the electrical load is 

connected to the generator, the engine is more heavily 

loaded, and as a result, the speed drops slightly. This slight 

decrease in speed, together with the voltage drop  within 

the generator itself, results in a slightly lower voltage 

when the generator is loaded to its full capacity than 

when running no load. The slight variation in speed also 

affects the frequency of the output current. This frequency 

variation has no appreciable effect in the operation of 

motors, lights, and most appliances. However, electronic 

equipment and clocks will be affected if correct RPM is not 

maintained. See Load vs. Output chart.

Although individual units and models vary slightly, the 

normal voltage and frequency of the engine-generator 

described in this manual are approximately as follows, 

under varying loads:

LOAD vs. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

120V 

Recpt

240V 

Recpt

None

3690

61.5

120V

240V

Half

3600

60.0

120V

240V

Full

3510

58.5

120V

240V

The speed of the engine was carefully adjusted at the 

factory so that the generator produces the proper voltage 

and frequency. For normal usage, the speed setting should 

not be changed. If the generator is being run continuously 

on a very light load, it is often advisable to lower the 

operating speed slightly. 

The engine will govern itself at full speed. Intentionally 

overriding the governor and operating the generator at 

low voltage may damage both the generator and any load 

connected to it. Running the engine at excessively high 

speeds results in high voltage, which may significantly 

shorten the life of light bulbs and appliances being used, as 

well as possibly damaging the engine.

CAUTION: EQUIPMENT DAMAGE

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A 
QUALIFIED SERVICE TECH. 

Whenever making any speed 

adjustments, check the YourGen meter and be sure the 
voltage and speed are correct.

Output voltage should be checked periodically to ensure 

continued proper operation of the generating plant and 

appliances. 

Hz -

This is the measured frequency of the generator set. See 

the table in the RPM section above for an explanation of 

voltage and frequency ranges under load.

V1 - 

Output voltage of Line 1 (L1 on panel) to neutral. See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

V2 - 

Output voltage of Line 2 (L2 on panel) to neutral. See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

V1-V2 -

Output voltage of Line 1 (L1) and Line 2 (L2). See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

Hours -

This displays the total running hours of the generator set. 

When the generator is turned off, the hours will remain 

displayed. The display is run on a CR2032, ten-year battery. 

Once the unit is running, the battery connected to the unit 

will then supply the power to the YourGen meter.

Load Bars - 

These bars indicate how much load is being used on Line 1 

(L1) and Line 2 (L2).

   

= 1-25%             = 25-50%             = 50-75%              = 75-100%

Содержание WL12000HE-03/A

Страница 1: ...ld ever need to contact us concerning this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________...

Страница 2: ...E 17 WIRING DIAGRAM 18 WIRING DIAGRAM 19 CA EVAP EMISSION CONTROL 20 LIMITED WARRANTY 20 SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation...

Страница 3: ...set or fuel tank D Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in an approved container and only in a well ventilated...

Страница 4: ...Generator Model Number S20FS 160 A Part Number 351836 1 Rotor Resistance 6 57 Ohms Stator Resistance 0 124 Ohms Cap Winding Resistance 0 60 Ohms Capacitors 31 5 mF Capacitor Part Number 300323 112 ENG...

Страница 5: ...e performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle asse...

Страница 6: ...out the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard starting load such as an air compre...

Страница 7: ...ine in a level position fill with the recommended oil to the upper limit mark on the oil level dipstick Running the engine with a low oil level can cause engine damage This type of damage is not cover...

Страница 8: ...EGATIVE battery terminal to GROUND For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the Bat terminal Make sure all connect...

Страница 9: ...e the starter Turn the engine switch to the START position and hold it there until the engine starts If the engine fails to start within 5 seconds release the engine switch and wait at least 10 second...

Страница 10: ...s and models vary slightly the normal voltage and frequency of the engine generator described in this manual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Fr...

Страница 11: ...sist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO portable generator ships with a bonded neutral You can safely use this generator without external gr...

Страница 12: ...ution panel must be installed by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergency panel Keep in...

Страница 13: ...ual are approximately as follows under varying loads LOAD vs OUTPUT Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 120V 240V Half 3600 60 0 120V 240V Full 3510 58 5...

Страница 14: ...from the receptacles attached to either A or B output legs This generator is capable of producing 45 Amps of 240 volt current at C Check the appliance or tool nameplates for the current and voltage t...

Страница 15: ...o length A Start the engine and warm it up stop the engine and remove the spark plug wire to prevent it from accidentally being started B This engine has an oil drain valve for your convenience Attach...

Страница 16: ...nt in clean engine oil and squeeze out all the excess before reinstalling it The engine will smoke when started if too much oil is left in the foam H Clean the dirt from the inside of the air cleaner...

Страница 17: ...igh pressure spray could contaminate the fuel system and the generator components 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling At le...