“Concealed Damage” is understood to mean dam-

age to the contents of a package which is not 

evident at the time of delivery by the carrier, but 

which is discovered later.  The carrier or carriers are 

responsible for merchandise lost or damaged in tran-

sit.  The title to goods rests with the consignee when 

generators are shipped F.O.B. factory, and only the 

consignee can legally file a claim.  Please note, most 

carriers have a time limit for filing concealed damage 

claims.

****  CAUTION  ****

These units are shipped with oil.  Be sure to check 

oil levels before operating.  See engine manufactur-

er’s instruction manual for recommended oil require-

ments before initial starting.

UNPACKING

  .  Carefully remove the carton.

  2.  After inspecting the engine-generator and trans-

 

fer switch for external physical damage, check 

 

for the following items packed inside the carton.

 

a.  Owner’s manual.

 

b.  Engine manufacturer’s instruction manual.

  3.  Remove main frame hold down bolts.  (4)

  4.  Unit can now be lifted from shipping pallet.

INSTALLATION

General Information

    ******************

*****  WARNING  *****

    ******************

Before proceeding with the installation be sure the 

operation selector switch is in the stop position.

These engine generator sets are designed to be 

mounted on a concrete pad outdoors only.  

As an 

option, a prefab pad may be used as long as proper 

attention is paid to site preparation to ensure the unit 

will not move after installation.  The transfer switch is 

mounted next to your electrical entrance or distribu-

tion panel inside or outside the building.  Consult a 

qualified, licensed electrician or contractor to install 

and wire the transfer switch.  

The installation must 

comply with all national, state and local codes.

Before beginning the installation process check the 

rating of the generator set and its transfer switch 

rating.  Be certain they can handle the intended load 

and are compatible with the entrance voltage, phase 

and current ratings.  Plans for installation should be 

prepared with proper attention to mechanical and 

electrical engineering detail to assure a satisfactory 

system installation.  The information in this manual is 

offered only as a guide to finalizing your installation 

plans.

SPECIFICATIONS

GENERATOR

FUEL

WATTS*

VOLTS AMPS HZ PH RPM

LP

7000

20/240

70.8

60

3600

NG

5000

20/240

62.5

60

3600

*  

Continuous Rating.

* Derate 3.5% per 000 feet elevation above sea 

level.

FUEL CONSUMPTION

NATURAL GAS

1000 BTU/CU FT

LP VAPOR

2520 BTU/CU FT

CF/HR*

328

130.5

BTU/HR*

328,000

329,000

GAL/HR*

N/A

3.61

  *  

Based on full load operation.

LP TANK SIZING

Required LP tank size for LP Vapor withdrawal 

operating at various outside temperatures given in 

degrees Fahrenheit (Celsius).

TANK TEMPERATURE

TANK SIZE

60° F (16° C)

150 GALLON

32° F (0° C)

250 GALLON

0° F (18° C)

500 GALLON

-20° F (-29° C)

1000 GALLON

ENGINE SPECIFICATIONS

Refer to engine operating and maintenance instruc- 

tions.

**  NOTICE  **

When unpacking the generator set, be sure to in-

spect it carefully for freight loss or damage.  If loss or 

damage is noted at the time of delivery, require that 

the person making the delivery make note of the loss 

or damage on the freight bill, or affix his signature 

under the consignor’s memo of the loss or damage.  

Contact the carrier for claim procedures.

When loss or damage is noted after delivery, segre-

gate the damaged material, and contact the carrier 

for claim procedures.  Be sure to retain the packag-

ing material for carrier inspection.

Содержание ULPSS20B2W/A

Страница 1: ...12270 00 60706 229 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS20B2W A...

Страница 2: ...el Pressure Tables 8 Fuel Conversions 8 Battery Installation 9 Connecting Battery Charger 11 TRANSFER SWITCH INSTALLATION AC Electrical Connections 11 12 DC Electrical Connections 13 INITIAL START UP...

Страница 3: ...ground rod driven into the earth 2 FIRE HAZARD Natural gas and L P present a hazard of possible explosion and or fire a Keep fuel containers out of reach of children b Do not smoke or use open flame...

Страница 4: ...outside instal lation The transfer switch is UL1008 approved A seven day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing cir...

Страница 5: ...ansfer switch The installation must comply with all national state and local codes Before beginning the installation process check the rating of the generator set and its transfer switch rating Be cer...

Страница 6: ...to the fuel solenoid on the unit must be four to six ounces psi per square inch or 7 to 11 inches W C water column These fuel pressures are critical failure to provide the proper pressure can cause ma...

Страница 7: ...s to the generator set and all other appliances in the building If the primary regulator fuel meter is a high pressure regu lator then a low pressure regulator must be installed to bring the pressure...

Страница 8: ...4 6 OZ 7 11 IN 4 6 OZ STARTING 2 PSI 7 11 IN 4 6 OZ 7 11 IN 4 6 OZ NO LOAD 2 PSI 7 11 IN 4 6 OZ 7 11 IN 4 6 OZ FULL LOAD 2 PSI 7 11 IN 4 6 OZ 7 11 IN 4 6 OZ LP TANK SIZING Required LP tank size for L...

Страница 9: ...d disconnect the negative cable first and then the positive cable 5 Be sure all connections are tight and coat the terminals and cable ends with dielectric grease WARNING The electrolyte is a diluted...

Страница 10: ...12270 00 10 60706 229...

Страница 11: ...the generator It is suggested that this circuit be fused for 15 amps Terminal block connections have been provided in the customer connection area of the engine generator set See Page 10 for diagram N...

Страница 12: ...l must be installed All selected emergency circuits are removed from main distribution panels and reinstalled in the emer gency distribution panel Suggested circuits freez er refrigerator furnace emer...

Страница 13: ...ative White INITIAL START UP WARNING DO NOT jump start these engine generator sets Starting these units on a low battery of jump start ing them will cause damage to the engine control module Use the f...

Страница 14: ...mote start WILL NOT occur AUTO White Button This button places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will mon...

Страница 15: ...l block in the ATS The voltage should be 240 volts plus or minus nominal The frequency should be between 61 5 to 62 hertz Hz The voltage should also be checked between the hot terminals L2 and L6 and...

Страница 16: ...s for control of the ATS and the generator PUSH BUTTONS On the front control display are three push buttons that control the operation of the generator and the ATS CAUTION Before using the transfer te...

Страница 17: ...ctuator Actuator Position clock battery off S2 10 on up off down exerciser off S1 7 on up off down with load or without load without load S1 8 with up without down SETTING THE EXERCISER CIRCUIT Press...

Страница 18: ...12270 00 18 60706 229...

Страница 19: ...ss 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the button The value begins to flash Press 4 or 3 to adju...

Страница 20: ...ule detects that the engine oil temperature has exceeded the high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the unde...

Страница 21: ...E MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any type of main...

Страница 22: ...12270 00 22 60706 229 ENGINE GENERATOR SET LAYOUT ULPSS20B2W A...

Страница 23: ...23 12270 00 60706 229 ENGINE GENERATOR SET PAD LAYOUT...

Страница 24: ...Locked up engine generator set 9 Defective starter fuel solenoid relay s ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4...

Страница 25: ...25 12270 00 60706 229 AC AND DC GENERATOR SCHEMATIC...

Страница 26: ...12270 00 26 60706 229 AC WIRING SCHEMATICS ULPSS20 17 A ULPSS20 3 A...

Страница 27: ...27 12270 00 60706 229 AC WIRING SCHEMATICS ULPSS20 18 A ULPSS20 4 A...

Страница 28: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or conse quential damages Note Some...