AUTOMATIC GENERATOR EXERCISER  

This light indicates the status of the generator exer-

ciser:

    

-  Blinks during the exercise period (including cool        

down).

    -  stays on when the exerciser has been set.

    

-  is off when the exerciser has not been set.

GENERATOR STARTING CONTACTS

Disconnect the generator battery.  Connect the 

generator starting wires #  (battery -) to terminal 4 

and wire # 23 (start) to terminal 5 of the TB7 terminal 

block.  This is removable for convenient connections.

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to 

automatically exercise the generator for 20 minutes 

once every week.

In order to set and test the exercise circuit the 

AUTO button on the generator control panel 

must be on.

EXERCISE WITH OR WITHOUT LOAD

The transfer switch can be set up to exercise the 

generator with or without a load transfer.  Normally 

Winco generators exercise without a load transfer.  

This is because you may not wish to have a mo-

mentary interruption of power.  Turn the exerciser 

dipswitch on.  Then set the “with load” or “without 

load” dipswitch

.  

See table below.

Function

Factory

Setting

DIP 

Switch

DIP

 Actuator

Actuator 

Position

clock battery

off

S2

0

on (up)

off (down)

exerciser

off

S

7

on (up)

off (down)

with load or 

without load

without 

load

S

8

with (up)

without 

(down)

SETTING THE EXERCISER CIRCUIT

Press and hold (5 seconds) the 

Set Engine Exer-

ciser 

button.  The exercise period occurs immedi-

ately and at the same time weekly thereafter.  The 

status light below the button blinks during the exer-

cise period (including the cooldown).  The light stays 

on to indicate that the exerciser has been set.  If the 

light is off, the exerciser has not been set.

CANCELLING AN ACTIVE EXERCISE PERIOD

Press the 

Bypass Time Delay

 button to stop an 

exercising generator.  If exercise with load is set, the 

ATS retransfers the load to the utility, then stops the 

generator after cooldown.

     ******************

*****  WARNING  *****

     ******************

WITH A TOTAL POWER FAILURE (UTILITY 

POWER FAILS AND THE GENERATOR FAILS TO 

START AND RUN) THE EXERCISER MUST BE 

RESET AFTER THE POWER IS RESTORED.

SETTINGS

The ASCO 85 has settings that can be changed 

for various applications.  The dipswitch options are 

explained in the ASCO 85 Operator’s Manual.

SEE THE FOLLOWING PAGE FOR SEQUENCE 

OF OPERATION.

This completes your installation and unit testing.  

ALWAYS leave the system in automatic mode unless 

servicing the unit.  For automatic operation, the auto 

mode icon must be displayed on the engine control 

module display.

Содержание ULPSS20B2W/A

Страница 1: ...12270 00 60706 229 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS20B2W A...

Страница 2: ...el Pressure Tables 8 Fuel Conversions 8 Battery Installation 9 Connecting Battery Charger 11 TRANSFER SWITCH INSTALLATION AC Electrical Connections 11 12 DC Electrical Connections 13 INITIAL START UP...

Страница 3: ...ground rod driven into the earth 2 FIRE HAZARD Natural gas and L P present a hazard of possible explosion and or fire a Keep fuel containers out of reach of children b Do not smoke or use open flame...

Страница 4: ...outside instal lation The transfer switch is UL1008 approved A seven day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing cir...

Страница 5: ...ansfer switch The installation must comply with all national state and local codes Before beginning the installation process check the rating of the generator set and its transfer switch rating Be cer...

Страница 6: ...to the fuel solenoid on the unit must be four to six ounces psi per square inch or 7 to 11 inches W C water column These fuel pressures are critical failure to provide the proper pressure can cause ma...

Страница 7: ...s to the generator set and all other appliances in the building If the primary regulator fuel meter is a high pressure regu lator then a low pressure regulator must be installed to bring the pressure...

Страница 8: ...4 6 OZ 7 11 IN 4 6 OZ STARTING 2 PSI 7 11 IN 4 6 OZ 7 11 IN 4 6 OZ NO LOAD 2 PSI 7 11 IN 4 6 OZ 7 11 IN 4 6 OZ FULL LOAD 2 PSI 7 11 IN 4 6 OZ 7 11 IN 4 6 OZ LP TANK SIZING Required LP tank size for L...

Страница 9: ...d disconnect the negative cable first and then the positive cable 5 Be sure all connections are tight and coat the terminals and cable ends with dielectric grease WARNING The electrolyte is a diluted...

Страница 10: ...12270 00 10 60706 229...

Страница 11: ...the generator It is suggested that this circuit be fused for 15 amps Terminal block connections have been provided in the customer connection area of the engine generator set See Page 10 for diagram N...

Страница 12: ...l must be installed All selected emergency circuits are removed from main distribution panels and reinstalled in the emer gency distribution panel Suggested circuits freez er refrigerator furnace emer...

Страница 13: ...ative White INITIAL START UP WARNING DO NOT jump start these engine generator sets Starting these units on a low battery of jump start ing them will cause damage to the engine control module Use the f...

Страница 14: ...mote start WILL NOT occur AUTO White Button This button places the module into its Automatic mode This mode allows the module to control the function of the generator automatically The module will mon...

Страница 15: ...l block in the ATS The voltage should be 240 volts plus or minus nominal The frequency should be between 61 5 to 62 hertz Hz The voltage should also be checked between the hot terminals L2 and L6 and...

Страница 16: ...s for control of the ATS and the generator PUSH BUTTONS On the front control display are three push buttons that control the operation of the generator and the ATS CAUTION Before using the transfer te...

Страница 17: ...ctuator Actuator Position clock battery off S2 10 on up off down exerciser off S1 7 on up off down with load or without load without load S1 8 with up without down SETTING THE EXERCISER CIRCUIT Press...

Страница 18: ...12270 00 18 60706 229...

Страница 19: ...ss 4 to select the next parameter or 3 to select the previous parameter within the current page When viewing the parameter to be changed press the button The value begins to flash Press 4 or 3 to adju...

Страница 20: ...ule detects that the engine oil temperature has exceeded the high engine temperature pre alarm setting level after the Safety On timer has expired UNDERSPEED The engine speed has fallen below the unde...

Страница 21: ...E MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and Automatic Transfer Switch WARNING When performing any type of main...

Страница 22: ...12270 00 22 60706 229 ENGINE GENERATOR SET LAYOUT ULPSS20B2W A...

Страница 23: ...23 12270 00 60706 229 ENGINE GENERATOR SET PAD LAYOUT...

Страница 24: ...Locked up engine generator set 9 Defective starter fuel solenoid relay s ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel supply empty 4...

Страница 25: ...25 12270 00 60706 229 AC AND DC GENERATOR SCHEMATIC...

Страница 26: ...12270 00 26 60706 229 AC WIRING SCHEMATICS ULPSS20 17 A ULPSS20 3 A...

Страница 27: ...27 12270 00 60706 229 AC WIRING SCHEMATICS ULPSS20 18 A ULPSS20 4 A...

Страница 28: ...nd fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or conse quential damages Note Some...

Отзывы: