background image

7

OPM-122

REV C

The drive belt system must be of adequate size and must be tight 

enough to power the generator without slippage. Be careful not to 

over-tighten to the extent that it puts excessive strain on the bearings. 

Doing so can cause bearing failure and other possible damage to the 

generator.

Alignment of the generator to the prime mover is important. 

Misalignment of the pulleys will cause excessive belt and pulley wear 

and unnecessary stress on the prime mover.

The following table shows the effect if carious operating speeds and 

electrical loads on a typical generator when matched and mounted to 

an adequate prime mover.

LOAD VS. OUTPUT

Generator 

Load

Speed 

(RPM)

FREQUENCY 

(Hz)

Voltage

None

3690

61.5

129V

Half

3600

60.0

120V

Full

3510

58.5

115V

*Note: Required generator speed must be at 3600 +/- 90 RPM under all 

load conditions.

Although individual units and models may vary slightly, the normal 

voltage and frequency of typical 60 cycle engine-driven generators 

described in this manual are approximately as follows when powered 

by a typical prime mover (engine) run first with no load applied, then at 

half capacity as rated on the nameplate.

All engines have a tendency to slow down when a load is applied. 

The governor on the engine is designed to hold engine speed nearly 

constant. When the electrical load connected to the generator is 

increased, the engine is more heavily loaded and as a result, the 

speed drops slightly. This slight decrease in speed together with the 

natural “voltage drop” within the generator itself due to load current and 

heating of the windings, results in a slightly lower voltage than when 

the generator is running idle. 

The normal slight variations on speed also directly affect the frequency 

of the output current. This frequency variation has no appreciable effect 

in the operation of most loads (such as motors, lights, and most small 

appliances). However, timing devices and clocks will not keep perfect 

time unless the engine can keep the generator at exactly 3600 RPM at 

all times. Since this is not usually possible, minor time errors in clock 

occur.

The speed of the engine is usually adjusted so that the generator 

produces proper voltage. If the adjustment is made “cold”, set the 

voltage a little higher than normal since it will drop a few Volts as the 

generator warms up.

NOTE: When operating continuously at full load, the generator shell 

becomes very warm. It will be uncomfortable to the touch. This is 

normal for any high performance inherently regulated generator. Output 

voltage should be checked periodically to ensure proper operation of 

the generator and appliances.

UNIT INSTALLATION

Plans for installation should be prepared with proper attention to 

mechanical and electrical engineering detail to assure a satisfactory 

system installation. The information in this manual is offered as a 

guide to finalizing your installation plans. The installation sequence is 

summarized below.

PLAN THE INSTALLATION

Generally, two-bearing generators are used on portable equipment. For 

best service consider the following:

1. All electrical equipment should be protected from excessive 

moisture. Failure to do so will result in deterioration of the insulation 

and short circuits and grounds.

2. The generator should be installed in a sheltered area. If the unit must 

be left in the open, it should always be protected with a weather cover 

such as a tarp or large piece of canvas after each use to keep out 

water and dust.

CAUTION: EQUIPMENT DAMAGE

Always allow the generator and prime mover to cool before covering 

with a flammable weather covering.

MOUNTING

CAUTION: EQUIPMENT DAMAGE

The generator must be mounted with the engine to a common rigid 

base to prevent stress on the engine and generator shafts and 

bearings do to vibration displacement. For permanent installations, 

the engine-generator is usually mounted on a sub-frame which can be 

shock mounted with neoprene pads on the main frame.

Before proceeding with installation, be sure that you have completely 

read and understood the assembly and installation instructions.

An engine with adequate horsepower and a close regulated (fixed 

speed) governor is required for satisfactory operation of this generator.

About 1.4 horsepower is required to produce 1,000 Watts of generator 

output power assuming 100% efficiency of both the engine and the 

generator. However, due to engine and generator efficiencies of 80 

to 90%, the loss of power due to engine driving accessories such as 

cooling fans, battery charging alternators, etc., friction losses and 

slippage in the drive pulleys and belts, the general conservative rule 

of thumb allowing approximately two (2) horsepower for every 1,000 

Watts of generator output is much more realistic. For example, the 

7,200 Watt generator output will require a 14.4 horsepower engine 

for full output, good speed/voltage regulation, and satisfactory load 

performance. When determining the prime mover/generator pulley 

ratio to drive the generator at the correct operating speed, bear in mind 

the power rating of most prime movers (usually an engine) varies with 

speed. It produces more power at higher speeds, less when slowed. 

The prime mover must be fast enough to reach desired horsepower for 

good generator operation.

Содержание TB2400/E

Страница 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 wincogen com INSTALLATION AND OPERATORS TB2400 E TB4800 A TB7200 C TWO BEARING GENERATORS MANUAL TB7200...

Страница 2: ...ting instructions in this manual Should you experience a problem please follow the Troubleshooting Tables near the end of this manual The warranty listed in the manual describes what you can expect fr...

Страница 3: ...Amps 60 30 Receptacles 1 NEMA L14 30R Moisture Protection IP 23 Generator End Manufacturer Mecc Alte Model S20W 110 2 Capacitor 35 F Capacitor Part Number 16346 312 INTRODUCTION These generators are...

Страница 4: ...tructions in this manual could result in serious injury or death Keep this manual available for future reference ANSI SAFETY DEFINITIONS DANGER DANGER indicates an imminently hazardous situation which...

Страница 5: ...ctric motor up to operating speed The generator responds with high initial starting current but the engine speed drops sharply The overload may stall the engine If allowed to operate at very low speed...

Страница 6: ...E DO IT YOURSELF JOB For your safety all wiring must be done by a qualified electrician and conform to the National Electric Code and all state and local codes and regulations Check with local authori...

Страница 7: ...voltage should be checked periodically to ensure proper operation of the generator and appliances UNIT INSTALLATION Plans for installation should be prepared with proper attention to mechanical and e...

Страница 8: ...ective stator 4 Defective rotor Output voltage too high Engine speed too high Generator overheating 1 Generator overloaded 2 Poor ventilation No output voltage 1 Short in load 2 Broken or loose wire 3...

Страница 9: ...9 OPM 122 REV C WIRING SCHEMATICS TB2400 GND GND G1 G1 G1 N N...

Страница 10: ...10 OPM 122 REV C TB4800 2 N N N G1 G1 G1 G2 G2 G2 GND GND GND GND...

Страница 11: ...11 OPM 122 REV C 2 G1 G1 G2 G2 N N GND GND GND TB7200...

Страница 12: ...ranty does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment WINCO does not warrant engines Eng...

Отзывы: