Winco HPS9000VE-03/A Скачать руководство пользователя страница 8

8

60706-237/G

NG FUEL

The information in this manual is offered to assist you in 

providing the proper vapor fuel supply for your engine. This 

information is only provided to advise you of the engine’s 

requirements and the decisions you must make. In no case 

should this information be interpreted to conflict with any 

local, state, or national codes. If in doubt, always follow local 

codes.

DANGER: FIRE/PERSONAL INJURY

All fuel lines must be installed by a qualified fuel 

supplier.

The fuel source should be as close as possible to the 

outdoor operating location. This will reduce the installation 

cost of fuel runs. Connect the fuel supply line to the inlet 

of the fuel demand regulator on the unit using a locally 

approved flexible fuel line (see table for recommended line 

size). The pressure supplied to the demand regulator must 

be 4 to 6 ounces or 7 to 11 inches w.c. (water column). 

The primary regulator at the fuel supply must be capable of 

delivering the proper volume of fuel at this pressure.

Have your local fuel supplier install a protected fuel 

connection at the outside operating location. They should 

also install a lockable fuel shut off valve at the connection 

point. An approved flexible fuel line must be installed 

between the engine generator set and the supply line.

DANGER: FIRE/PERSONAL INJURY

The NG fuel supply line must always be shut off when 

the engine is not running. Failure to do so may allow 

fuel to leak at the unit.

INSTALLING THE FUEL LINE

DANGER: PERSONAL INJURY

Units that are intended to be run unattended MUST 

have an electric fuel solenoid installed. This solenoid 

MUST be wired to AUTOMATICALLY turn off the fuel 

whenever the engine stops.

Unit location will determine the size of fuel line the 

is required to supply the engine with a constant fuel 

pressure. Refer to the tables below for fuel line size and 

recommended tank size. For distances of 100 feet and over, 

a two regulator fuel system is recommended. This system 

consisting of a primary 10-15# regulator at the tank and a 6 

ounce secondary regulator installed about 10 feet from the 

generator. You need to run a 3/4 inch line or larger from 

the secondary regulator to the engine-generator set. When 

a two (2) regulator fuel system is used, a fuel line size of 3/8 

inch is generally adequate for distances up to 300 feet, The 

line size from the table below applies to the distance from 

the second regulator to the demand regulator. A positive 

fuel shut-off device must be installed in the fuel line close 

to the engine-generator set. This manual shut-off valve 

is required by code even if the 12 Volt fuel solenoid kit is 

installed. This optional 12 Volt DC valve is available through 

your local WINCO dealer and can be used to shut off during 

normal periods of operation without having to shut off the 

manual valve.

The fuel line used to connect the supply line to the demand 

regulator must be a locally approved flexible fuel line. 

Products used will vary in different regions depending on 

availability and local codes. Consult with your local fuel 

supplier to ensure complete compliance with ALL codes.

 

1. Remove the plastic cover plug from the demand 

   regulator.

 

2. Connect the flex fuel line to the demand regulator or 

 

  the optional solenoid.

DANGER: PERSONAL INJURY

Do NOT use galvanized pipe in the fuel line runs. The 

galvanized coating will become eroded and flake 

off, causing possible obstruction or damage to the 

regulator or fuel valve. The obstruction could cause an 

inoperative engine or an explosive fuel leak.

Size of pipe required for generators operating on NG gas.

  Length of fuel line*     Fuel line size

 

 

Less than 25 feet 

 

 

3/4/ in black pipe

  25-100 

Feet 

    1 

in 

black 

pipe

  Over 

100 

feet    Not 

recommended**

*Allow an additional 3 feet for each standard elbow. Do not 

use ‘street ells’ (restrictive).

**Consult factory for fuel run over 100 feet.

DANGER: FIRE/PERSONAL INJURY

Be careful when sealing gas joints. Excessive sealing 

compound can be drawn into the solenoid, regulator, 

or carburetor causing an engine malfunction or 

dangerous fuel leak.

FUEL CONSUMPTION

(Full Load)

Gasoline   1 

gal/hr

Natural Gas  

 

160 ft

3

/hr 

  163,200 

BTU/hr

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough. The most 

common cause for inoperative systems is an inadequate 

or incorrect fuel pressure. Power and performance of the 

engine is in direct relation to the correctness of the fuel 

system. The following diagram is of a typical NG installation. 

LP VAPOR

Reference numbers 1 and 3 in the previous diagram are 

system parts supplied by the customer. Reference number 4 

is the engine-generator set. The following table is of the fuel 

pressure reading at each reference in the system.

Single Regulator (LP only)

7

13240-11

60706-236

The fuel line used to connect the supply line to the 

GHPDQGUHJXODWRUPXVWEHDORFDOO\DSSURYHGÀH[LEOH

fuel line.  Products used will vary in different regions 

depending on availability and local codes.  Consult 

with your local fuel supplier to ensure complete com-

pliance with ALL codes. 

1.   Remove the plastic cover plug from the demand 

regulator.

&RQQHFWWKHÀH[IXHOOLQHWRWKHGHPDQGUHJXODWRU

or the optional fuel solenoid..

DANGER: PERSONAL INJURY 

    

Do not use galvanized pipe in the fuel line runs. 

The galvanized coating will become eroded and 

ÀDNHRIIFDXVLQJSRVVLEOHREVWUXFWLRQRUGDPDJH

to the regulator or fuel valve. The obstruction could 

cause  an inoperative engine or an explosive fuel 

leak.

Size of pipe required for generators operating on 

natural gas/LP gas.

 

Length of Fuel Line*    Fuel Line Size

 

  less than 25 feet 

 3/4 inch black pipe

 

  25 to 100 feet 

 1 inch black pipe

 

  over 100 feet 

 not  recommended**

*allow an additional 3 feet for each standard elbow.  

Do not use ‘street ells’ (restrictive)

** Consult factory for fuel runs over 100 feet.

DANGER! - FIRE - PERSONAL INJURY -

    Be careful when sealing gas joints. Excessive 

sealing compound can be drawn into the solenoid, 

regulator or carburetor causing an engine malfunc-

tion or dangerous fuel leak

.

 

FUEL CONSUMPTION (Full Load) 

 

  Gasoline 

1.67 Gal/HR 

  LP Vapor 

2.2 Gal/HR  

200,932 BTU/HR

  Natural Gas 

200 cu ft/hr 

200,000 BTU/HR

 

 

FUEL PRESSURE

Correct fuel pressure cannot be stressed enough.  

The most common cause for inoperative systems is 

an inadequate or incorrect fuel pressure.  Power and 

performance of the engine is in direct relation to the 

correctness of the fuel system.  Shown below is a 

diagram of a typical L.P. or N.G. installation.  

Reference numbers 1 through 3 in the diagrams 

above are system parts supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure reading at each 

reference in the system.

Fuel Pressure Table

Single Regulator (L.P. Vapor only) 

1

3

4

UNIT OFF

TANKPSI

7-11 in

7-11 in

4-6 oz

4-6 oz

STARTING

TANK PSI

7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI 

7-11 in

7-11 in

  

4-6 oz

4-6 oz

FULL LOAD

TANK PSI

7-11 in

7-11 in

 

4-6 oz

4-6 oz

Two (2) Regulator System (L.P. Vapor only) 

1

2

3

4

UNIT OFF

TANK PSI 10-15 lbs

7-11 in

7-11 in

4-6 oz

4-6 oz 

STARTING

TANK PSI 10-15 lbs  7-11 in

7-11 in

4-6 oz

4-6 oz

NO LOAD

TANK PSI 10-15 lbs  7-11 in 

7-11 in

4-6 oz  

4-6 oz

FULL LOAD

TANK PSI   10-15 lbs  7-11 in 

7-11 in

4-6 oz

4-6 oz

Содержание HPS9000VE-03/A

Страница 1: ...d to contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PUR...

Страница 2: ...ING THE OIL DUAL ELEMENT AIR FILTER SPARK PLUG CARBON CANISTER TROUBLESHOOTING 18 GENERATOR CARE 18 EXERCISING THE GENERATOR GENERATOR MAINTENANCE CLEANING RECEPTACLE WIRING DIAGRAM 19 CA EVAP EMISSIO...

Страница 3: ...ber S20W 110 Part Number 16346 009 Rotor Resistance 5 22 Ohms Stator Resistance 0 21 Ohms Cap Winding Resistance 0 87 Ohms Capacitors 35 mF Capacitor Part Number 300323 212 ENGINE Engine Manufacturer...

Страница 4: ...he earth 2 FIRE HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C D...

Страница 5: ...nce these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle assembly may c...

Страница 6: ...rs take about the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard starting load such as an...

Страница 7: ...per lubricant are considered abuse and not covered by the generator or engine manufacturer s warranty OIL RECOMMENDATIONS Outdoor temperatures determine the proper oil viscosity for the engines Winco...

Страница 8: ...on without having to shut off the manual valve The fuel line used to connect the supply line to the demand regulator must be a locally approved flexible fuel line Products used will vary in different...

Страница 9: ...one fuel to another FROM GASOLINE TO LP NG 1 With the engine running turn off the gasoline fuel valve 2 Run the engine until it runs out of fuel 3 Remove the plastic insert from the demand regulator...

Страница 10: ...ill automatically stop the engine before the oil level reaches a critical danger point This feature is designed to prevent costly repairs and downtime CAUTION EQUIPMENT DAMAGE Allowing the engine to s...

Страница 11: ...ging circuit For your safety always connect the positive battery cable to the bat terminal first Then connect the negative battery cable to the bat terminal Make sure all connections are clean and tig...

Страница 12: ...n pull briskly 6 When the engine starts open the choke gradually 7 The engine should promptly come up to operating speed NOTICE Do not allow the starter grip to snap against the engine Return it gentl...

Страница 13: ...the fuel system it is almost impossible to manual start the unit using NG 1 Check oil level refill as needed 2 Turn on the LP NG fuel supply 3 NEVER use the choke when operating on NG 4 Turn the engin...

Страница 14: ...do so could result in damage to equipment plugged into the unit and possible injury to the individual All engines have a tendency to slow down when a load is applied When the electrical load is connec...

Страница 15: ...d on the generator or the vehicle PERMANENTLY INSTALLED GENERATORS This WINCO portable generator ships with a bonded neutral and overcurrent protection NFPA 70 refers to this as a separately derived s...

Страница 16: ...load on the generator during the initial start up See the nameplate on your generator for the amperage capabilities of your unit CAUTION EQUIPMENT DAMAGE Failure to properly limit and balance the load...

Страница 17: ...dipstick when filling the engine with oil to prevent overfilling E Replace filler plug F Start engine up and warm it up G After warming up the engine recheck the oil level and refill as necessary to...

Страница 18: ...he high pressure spray could contaminate the fuel system and the generator components 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling A...

Страница 19: ...19 60706 237 G G1 G1 G3 G3 RECEPTACLE WIRING DIAGRAM...

Страница 20: ...quest THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILI...

Отзывы: