CONNECTING THE LOADS

APPLYING THE LOADS

Allow the engine to warm up for two or three minutes before applying 

any load. This will allow the engine to reach normal operating 

temperature and oil to circulate throughout the engine. A short warm-

up time will permit the engine to work more efficiently when the load is 

applied and will reduce the wear in the engine, extending its life.

Receptacles have been provided to allow loads to be connected to the 

generator. The loads should be added one at a time. If a large motor 

is being started: or multiple motors are being started, they should be 

started individually and the largest should be started first.

CAUTION: EQUIPMENT OVERLOAD

Keep the generator load within in the generator and receptacle 

nameplate rating. Overloading may cause damage to the generator 

and/or the loads.

Most electric tools and appliances will have the voltage and amperage 

requirements on their individual nameplates. When in doubt, consult 

the manufacturer or a local electrician. The nameplate amperage rating 

for electric motors can be misleading. See “Starting Electric Motors” in 

the Unit Capabilities. 

These engine-generator sets are inherently self regulating based on 

engine speed. The engine governor will automatically adjust itself to 

the load. No harm to the generator will result if it is operated with no 

load connected. Proper utilization of the receptacles located on the 

control panel is necessary to prevent damage to either the receptacles 

or the generator. The generator is a limited source of electrical power, 

therefore, pay special attention to the receptacle and generator ratings. 

The nameplate rating can be obtained through a single receptacle as 

long as the receptacles amperage rating is not exceeded.

GROUNDING

All units must be grounded. Drive a 3/4 or 1” copper pipe or rod into 

the ground close to the engine-generator set. The pipe must penetrate 

moist earth. Connect an approved ground clamp to the pipe. Run a 

no. 10 Awg wire from the clamp to the generator ground lug on the 

receptacle panel. Do not connect to a water pipe or to a ground used 

by a radio system. The engine-generators covered in this manual were 

designed primarily for portable use. If you are connecting into a building 

wiring system that is already grounded using the 14-30 4 wire plug, you 

do not have to ground the unit.

WARNING: PERSONAL DANGER

DO NOT OPERATE THIS GENERATOR INDOORS,

 

The unit should 

be stored in a warm, dry location. During a power outage, move the 

unit outdoors to a flat, dry location such as a driveway or sidewalk. 

WIRING

Plug your tools such as drills, saws, blowers, sump pump, and 

other items to be powered directly into the generator receptacles. 

Before plugging in all the tools and cord sets, recheck the rating 

of the generator set. Be sure it can handle the intended load and 

is compatible with the voltage, phase, and current ratings. ‘Hard 

wiring’ this unit directly into a temporary construction site electrical 

system is 

NOT A SIMPLE DO-IT-YOURSELF JOB. 

For your safety, 

all wiring must be done by a qualified electrician and conform to the 

National Electric Code and comply with all state and local codes and 

regulations. Check with local authorities before proceeding.

WARNING: PERSONAL DANGER

A fully isolated, double pole double throw manual transfer switch must 

be installed any time a generator is being connected to an existing 

distribution system.

slight decrease in speed, together with the voltage drop within the 

generator itself, results in a slightly lower voltage when the generator 

is loaded to its full capacity than when running no load. The slight 

variation in speed also affects the frequency of the output current. 

This frequency variation has no appreciable effect in the operation of 

motors, lights, and most appliances. However, electronic equipment 

and clocks will be affected if correct RPM is not maintained. See Load 

vs. Output chart.

Although individual units and models vary slightly, the normal voltage 

and frequency of the engine-generator described in this manual are 

approximately as follows, under varying loads:

LOAD vs. OUTPUT

Generator 

Load

Speed 

(RPM)

Frequency 

(Hz)

Voltage

None

3690

61.5

125V

Half

3600

60.0

120V

Full

3510

58.5

115V

The speed of the engine was carefully adjusted at the factory so that 

the generator produces the proper voltage and frequency. For normal 

usage, the speed setting should not be charged. If the generator is 

being run continuously on a very light load, it is often advisable to lower 

the operating speed slightly. 

CAUTION: EQUIPMENT DAMAGE:

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED 

SERVICE TECH. 

Whenever making any speed adjustments, check the 

unit with a voltmeter and a frequency meter or a tachometer and be 

sure the voltage and speed are correct.

Lower voltage may damage both the generator and any load connected 

to it. Running the engine at excessively high speeds results in high 

voltage, which may significantly shorten the life of appliances being 

used.

Output voltage should be checked periodically to ensure continued 

proper operation of the generating plant and appliances. If the 

generator is not equipped with a voltmeter, it can be checked with a 

portable meter.

Содержание DP7500/A

Страница 1: ...WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 www wincogen com INSTALLATION AND OPERATORS DP7500 A GENERATOR MANUAL...

Страница 2: ...precision engineered generator designed and tested to give you years of satisfactory service To get the best performance from your new generator it is important that you carefully read and follow the...

Страница 3: ...ry It may also be used to alert against unsafe practices 1 ELECTRICAL SHOCK The output voltage present in this equipment can cause fatal electric shock This equipment must be operated by a responsible...

Страница 4: ...to 4 times as much starting current as running current Repulsion Induction motors are the easiest to start and require only 1 1 2 to 2 1 2 times as much starting as running current Most fractional ho...

Страница 5: ...res determine the proper oil viscosity for the engines Use the chart to select the best viscosity for the outdoor temperature range expected OIL ALERT SYSTEM This generator is equipped with a low oil...

Страница 6: ...id batteries contain sulfuric acid which causes severe burns If acid contacts eyes skin or clothing flush well with water For contact with the eyes get immediate medical attention BATTERY CHARGING Uni...

Страница 7: ...OLD WEATHER A Use the proper oil for the temperature expected B Use fresh winter grade fuel Winter grade gasoline is blended to improve starting Do not use summer grade gasoline 2 HOT WEATHER A Use th...

Страница 8: ...unit outdoors to a flat dry location such as a driveway or sidewalk WIRING Plug your tools such as drills saws blowers sump pump and other items to be powered directly into the generator receptacles B...

Страница 9: ...on your generator for the amperage capabilities of your unit CAUTION EQUIPMENT DAMAGE Failure to properly limit and balance the load a lied to the generator will cause the generator to produce low vol...

Страница 10: ...Proper care and maintenance of the generator is necessary to ensure a long trouble free life EXERCISING THE GENERATOR The generator should be operated every three to four weeks It should be operated f...

Страница 11: ...otor field Shorted capacitor Shorted diodes on rotor GFCI receptacle tripped 1 Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling At least y...

Страница 12: ...or This warranty does not cover travel time mileage or labor for removal or re installation of WINCO product from its application Normal wear and tear Costs of rental equipment WINCO does not warrant...

Отзывы: