14

OPM-129/F

120 Volt and 240 Volt receptacles are provided for 

connection to various loads. 

The following diagram represents this 5,160 watt (rated 

output) generator. A & B represent the 120 volt output legs 

of this generator. Up to 2,580 watts at 120 volts (43 Amps) 

can be drawn from the receptacles attached to either A 

or B output legs. This generator is capable of producing 

21.5 Amps of 240 volt current at C. Check the appliance 

or tool nameplates for the current and voltage to insure 

compatibility. Remember that power taken from C reduces 

the power available equally at both A and B and vice versa.

Change Oil Warning -

After the first 50 hours, the engine oil should be changed. 

The YourGen meter will light up the oil icon (         ) and the 

word ‘change’ will flash. Once the oil has been changed, 

press and hold the cycle button for approximately 5 

seconds until the warning has been removed from the 

display to reset the warning. The meter will then remind 

you of oil changes on the appropriate schedule for your 

generator. It is important to remember that the engine 

manufacturer recommends changing the oil on a calendar 

schedule even if the total number of operational hours have 

not been reached. Certain operating environments may 

also require more frequent oil changes.

Alarms  - 

The display will start blinking and toggle to the first 

parameter that is out of specification. The panel will remain 

flashing until the fault condition returns to within the 

acceptable range, see following table.

Acceptable Range

Frequency

57-63 Hz

Voltage

110VAC-130VAC

VAC1-VAC2

220VAC-260VAC

Battery - 

When the unit is off, the YourGen meter will display the 

hours continuously using a coin cell back-up battery inside 

the meter. Once the unit is running, the meter will get 

power from the main unit battery. 

Voltage  

 

 

3.0V DC

Battery Type 

 

CR2032 

Lifetime 

   10 

Years

The battery has a 10 year lifetime, in the event you need to 

change the battery, follow these instructions: 

The battery is located in the control box near potentially live 

AC terminals. To prevent electrocution while changing the 

battery disable the unit by disconnecting the main battery, 

remove the spark plug, and then open the receptacle panel. 

Locate the backside of the YourGen meter. Gently pry the 

back plate off using the slot located on top. 

 

Once open, the battery will be located at the top. Using a 

needle nose plier, carefully pull out the battery. 

Replace the battery having the POSITIVE (+) side down. 

Ensure the battery is secured between the battery 

connections. 

Replace the back plate of the meter and close the receptacle 

panel using the screws to secure it. Reconnect the unit’s 

main battery. 

Battery

Install Battery Between These Two Points

Содержание DP7500-03/A

Страница 1: ...eed to contact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE...

Страница 2: ...CHANGING THE OIL AIR FILTER SEDIMENT CUP SPARK PLUG CARBON CANISTER GENERATOR CARE 17 EXERCISING THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING 18 RECEPTACLE WIRING DIAGRAM 19 CA EVAP EM...

Страница 3: ...er S20W 95 A Part Number 16346 005 Rotor Resistance 4 8 Ohms Stator Resistance 0 28 Ohms Excitation Resistance 0 76 Ohms Capacitor 40 F Capacitor Part Number 16346 312 ENGINE Engine Manufacturer Honda...

Страница 4: ...cause severe burns instantly F The use of the engine generator set must comply with all national state and local codes SAFETY INFORMATION This engine generator set has been designed and manufactured...

Страница 5: ...e performance these units should never be run in small compartments without positive fresh air flow RESTRICTED USES DO NOT remove from the cradle assembly Removal of the generator from the cradle asse...

Страница 6: ...the same amount of current to run them whether they are Repulsion Induction RI Capacitor Cap or Split Phase SP type If the electric motor is connected to a hard starting load such as an air compresso...

Страница 7: ...struction for operating this unit at over 5 000 feet PREPARING THE UNIT UNPACKING CAUTION EQUIPMENT DAMAGE THIS UNIT HAS BEEN SHIPPED WITH OIL Failure to maintain the engine oil at the proper level wi...

Страница 8: ...ent to keep the battery charged under normal operating conditions but were not intended to be used as a battery charger WARNING PERSONAL INJURY Lead acid batteries produce explosive hydrogen gas when...

Страница 9: ...g speed CAUTION EQUIPMENT DAMAGE Never permit the choke to remain on after the engine has run for a short time It is not necessary to choke the engine when it is warm Avoid over choking ELECTRIC START...

Страница 10: ...emaining fuel from the fuel tank it must be drained into an approved container C Start the engine and allow it to run until all the fuel in the carburetor and the fuel lines has been used up and the e...

Страница 11: ...eptacle two hot one ground and one neutral has been provided on the control panel for use in temporary power applications requiring 120 240 Volt power Consult a licensed electrician for wiring the Tem...

Страница 12: ...mergency distribution panel must be installed by a licensed electrician according to all applicable codes The electrician will move the critical circuits to be powered during the outage to the emergen...

Страница 13: ...T Generator Load Speed RPM Frequency Hz Voltage 120V Recpt 240V Recpt None 3690 61 5 125V 258V Half 3600 60 0 120V 240V Full 3510 58 5 115V 230V The speed of the engine was carefully adjusted at the f...

Страница 14: ...ore frequent oil changes Alarms The display will start blinking and toggle to the first parameter that is out of specification The panel will remain flashing until the fault condition returns to withi...

Страница 15: ...etely then reinstall the oil drain plug and a new washer and tighten the oil drain plug securely Dispose of used motor oil in a manner that is compatible with the environment Do not throw it in the tr...

Страница 16: ...the fuel sediment cup and O Ring 2 Wash the sediment cup in non flammable solvent and dry thoroughly 3 Place the O Ring in the fuel valve and install the sediment cup Tighten the sediment cup securely...

Страница 17: ...ubrication B Receptacles Quality receptacles have been utilized If a receptacle should become cracked or otherwise damaged replace it Using damaged or cracked receptacles can be both dangerous to the...

Страница 18: ...r field Defective capacitor Circuit breaker trips Defective load Defective receptacle Excessive load Voltage too high Engine speed is too high Generator overheating Overloaded Insufficient ventilation...

Страница 19: ...19 OPM 129 F RECEPTACLE WIRING DIAGRAM G2 G2 G2 G2 G2 G1...

Страница 20: ...e furnished upon request THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED INCLUDING BUT NOT LIMITED TO WARRANTI...

Отзывы: