Most fractional horsepower motors take about the 
same amount of current to run them whether they 
are Repulsion Induction (RI), Capacitor (Cap), or 
Split-Phase (SP) type.  

If the electric motor is connected to a hard starting 
load, such as an air compressor, it will require more 
starting current.  If it is connected to a light load, 
or no load such as a power saw, it will require less 
starting current.  The exact requirement will also 
vary with the brand or design of the motor.

Self-exciting generators respond to severe overload-
ing differently than utility power.  When overloaded, 
the engine is not able to supply enough power to 
bring the electric motor up to operating speed.  The 
generator responds with high initial starting current, 
but the engine speed drops sharply.  The overload 
may stall the engine.  If allowed to operate at very 
low speeds, the electric motor starting winding will 
burn out in a short time.  The generator winding 
might also be damaged.

CAUTION:  EQUIPMENT DAMAGE

 

RUNNING THE GENERATOR SET UNDER 

THESE CONDITIONS MAY RESULT IN DAMAGE 
TO THE GENERATOR STATOR AS WELL AS THE 
MOTOR WINDING.

The heavy surge of current required for starting 
motors is required for only an instant.  The genera-
tor will not be damaged if it can bring the motor up 
to speed in a few seconds of time.  If diffi culty is 
experienced in starting motors, turn all other electri-
cal loads off and if possible reduce the load on the 
electric motor.

PREPARING THE UNIT

UNPACKING

CAUTION:  EQUIPMENT DAMAGE

    THIS UNIT HAS BEEN SHIPPED WITHOUT OIL.  
Failure to maintain the engine oil at the proper level 
will result in serious engine damage.

When you unpack your new engine-generator set be  
sure to remove all the information sheets and manu-
als from the carton.

1.  This generator-set was in good order when 
shipped.  Inspect the generator-set promptly after 
receiving it.  If any damage is noted, notify the trans-
portation company immediately; request proper pro-
cedures for fi ling a “concealed damage” claim.  Title 
to the equipment and responsibility for fi ling a claim 
rests with you when a generator set is sent F.O.B. 
shipping point.  Only you can legally fi le a claim.

2.  Before proceeding with the preparations of your 
new generator set for operation, take a couple of 
minutes to ensure the unit you have received is the 
correct model and review the specifi cation pages in 
this manual to insure that this unit meets your job 
requirements.

LUBRICATION

Before starting the engine, fi ll the crankcase to the 
proper level with a good quality oil.  The recom-
mended grade of oil and quantity of oil required is 
listed in the engine operator’s manual and below in 
this manual.  This unit was shipped with most of the 
oil removed.  The engine normally holds 36 to 39 
ounces of oil.  Since there is some trapped oil in the 
engine, when fi lling the crankcase the fi rst time use 
the dipstick to ensure that you do not over fi ll the 
crankcase. The blow-up shows the full oil level mark 
on the dipstick.  

Oil is added to the engine by removing the oil fi ll cap 
and adding oil at this point.  After fi lling the crank-
case to the proper level, be sure you properly tighten 
the oil fi ll cap.  NOTE:  This engine generator must 
be on a level surface before you check or add oil to 
the system.

The necessity of using the correct oil, and keeping 
the crankcase full cannot be overemphasized.  En-
gine failures resulting from inadequate or improper 
lubricant are considered abuse and not covered by 
the generator or engine manufacturer’s warranty.

Oil Recommendations

Outdoor temperatures determine the proper oil 
viscosity for the engines. Use the chart to select the 
best viscosity for the outdoor temperature range 
expected.

UPPER LIMIT

OIL FILLER CAP/DIPSTICK

LOWER LIMIT

OIL FILL HOLE
(bottom edge)

Содержание 15041-006

Страница 1: ...INSTALLATION AND OPERATORS MANUAL PORTABLE GENERATORS DL5000H D DL6000H F WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 wincogen com...

Страница 2: ...ing 8 Electric Starting 8 Stopping Storage 9 Operating Speed 9 CONNECTING THE LOADS 10 Wiring 10 ENGINE CARE 11 GENERATOR CARE 12 TROUBLESHOOTING 13 CONTROL PANEL WIRING DIAGRAM 14 WARRANTY INFORMATIO...

Страница 3: ...dren c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel on...

Страница 4: ...3rd party companies making enclosures for generators that have been properly engineered The use of these 3rd party enclosures is acceptable as long as they have been certified and meet current code DO...

Страница 5: ...s in good order when shipped Inspect the generator set promptly after receiving it If any damage is noted notify the trans portation company immediately request proper pro cedures for filing a conceal...

Страница 6: ...perate it Units equipped with a recoil or rope start will operate satisfactorily without a battery WARNING EQUIPMENT DAMAGE The battery positive cable is shipped with a plastic protective cap When sta...

Страница 7: ...ed inside the engine If the oil level drops below a certain point the low oil module on the engine will shut it down This low oil warning system will automatically stop the engine before the oil level...

Страница 8: ...ith time to cool off between cranking cycles Do not operate the starter more than 5 seconds and wait at least 10 seconds before operating the starter again Repeat cycle if necessary 6 When the engine...

Страница 9: ...chart Although individual units and models vary slightly the normal voltage and frequency of the engine gen erator described in this manual are approximately as follows under varying loads LOAD VS OUT...

Страница 10: ...ll state and local codes and regulations Check with local authorities before proceeding WARNING PERSONAL DANGER A fully isolated double pole double throw manual transfer switch must be installed any t...

Страница 11: ...The oil level must al ways be checked before the engine is started Take care to remove any dirt or debris from around the oil fill plug before removing Be sure the oil level is maintained Fill to the...

Страница 12: ...tion or replacement of parts should be performed only by a qualified electrical service technician USE ONLY FACTORY APPROVED REPAIR PARTS a Bearing The bearing used in these generators is a heavy duty...

Страница 13: ...Shorted capacitor Shorted diodes on rotor GFCI Receptacle tripped SPECIFICATIONS DL5000H D Generator manufacturer WINCO Inc Part number 15359 039 Rotor resistance 0 83 Ohms Stator resistance G1 N 0 6...

Страница 14: ...3310 00 14 60707 126 WIRING DIAGRAMS...

Страница 15: ...e repaired or replaced For warranty service return the product within 24 months from the date of purchase transportation charges prepaid to your nearest WINCO Authorized Service Center or to WINCO Inc...

Страница 16: ...RER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or repla...

Отзывы: