TESTING POLICY 

Before any generator is shipped from the factory, it 
is fully checked for performance.  The generator is 
loaded to its full capacity, and the voltage, current 
and frequency are carefully checked.

Rated output of generator is based on engineering 
tests of typical units, and is subject to and limited 
by, the temperature, altitude, fuel, and other condi-
tions specifi ed by the manufacturer of the applicable 
engines.

INTENDED USES 

This engine generator set has been designed pri-
marily for portable heavy duty commercial use.  Both 
120 volt and 240 volt receptacles are provided in the 
control panel to plug in your loads (lights, portable 
tools, and small appliances).  

This portable unit requires large quantities of fresh 
air for cooling the engine and generator.  For safety, 
long life and adequate performance, these units 
should never be run in small compartments without 
positive fresh air fl ow.

RESTRICTED USES

DO NOT 

remove from the cradle assembly.  Re-

moval of the generator from the cradle assembly 
may cause excessive vibration and damage to the 
engine-generator set.

DO NOT 

install and operate this generator in a small 

compartment., i.e. generator compartments of ve-
hicles, motor homes or travel trailers.  These com-
partments will not allow enough free fl ow of fresh 
air to reach the engine generator set for cooling and 
will cause the unit to overheat, damaging both the 
engine and generator.  Small compartments will also 
develop hot spots where there is very little air fl ow 
and may cause a fi re.

PLEASE NOTE

  There are 3rd party companies 

making enclosures for generators that have been 
properly engineered.  The use of these 3rd party 
enclosures is acceptable as long as they have been 
certifi ed and meet current code.

DO NOT 

attempt to operate at 50 cycles.  These 

units are designed and governed to operate at 60 
cycles only.

UNIT CAPABILITIES

GENERATOR CONNECTIONS

DL6000H - 120 volt and 240 volt receptacles are 
provided for connection to various loads.  The dia-
gram below represents this 5500 watt (rated output) 
generator.  A & B represent the 120 volt output legs 
of this generator.  Up to 2250 watts at 120 volts 
(22.9 Amps) can be drawn from each of the recepta-
cles attached to either of the A or B output legs. This 
generator is capable of producing 22.9 Amps of 240 
volt current at C. Check the appliance or tool name-
plates for the current and voltage to insure compat-
ibility.  Remember that power taken from C reduces 
the power available at both A and B and vice versa.

Reference A & B = 120 Volt Receptacle
 

   

NEMA 5-20 (120V-20A)

Reference C = 120/240 Volt Twistlock Receptacle
 

   

NEMA L14-30 (120/240V-30A)

DL5000H - the same principles apply to this unit as 
the one described above, only you are limited to 
4500 watts or 18.75 amps at each 120 volt recep-
tacle and 18.75 amps at 240 volt.

STARTING ELECTRIC MOTORS

Electric motors require much more current (amps) to 
start them than to run them.  Some motors, par-
ticularly low cost split-phase motors, are very hard 
to start and require 5 to 7 times as much starting 
current as running current.  Capacitor motors are 
easier to start and usually require 2 to 4 times as 
much starting current as running current.  Repulsion 
Induction motors are the easiest to start and require 
only 1 1/2 to 2 1/2 times as much starting as running 
current.

Содержание 15041-006

Страница 1: ...INSTALLATION AND OPERATORS MANUAL PORTABLE GENERATORS DL5000H D DL6000H F WINCO INC 225 S CORDOVA AVE LE CENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 wincogen com...

Страница 2: ...ing 8 Electric Starting 8 Stopping Storage 9 Operating Speed 9 CONNECTING THE LOADS 10 Wiring 10 ENGINE CARE 11 GENERATOR CARE 12 TROUBLESHOOTING 13 CONTROL PANEL WIRING DIAGRAM 14 WARRANTY INFORMATIO...

Страница 3: ...dren c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel on...

Страница 4: ...3rd party companies making enclosures for generators that have been properly engineered The use of these 3rd party enclosures is acceptable as long as they have been certified and meet current code DO...

Страница 5: ...s in good order when shipped Inspect the generator set promptly after receiving it If any damage is noted notify the trans portation company immediately request proper pro cedures for filing a conceal...

Страница 6: ...perate it Units equipped with a recoil or rope start will operate satisfactorily without a battery WARNING EQUIPMENT DAMAGE The battery positive cable is shipped with a plastic protective cap When sta...

Страница 7: ...ed inside the engine If the oil level drops below a certain point the low oil module on the engine will shut it down This low oil warning system will automatically stop the engine before the oil level...

Страница 8: ...ith time to cool off between cranking cycles Do not operate the starter more than 5 seconds and wait at least 10 seconds before operating the starter again Repeat cycle if necessary 6 When the engine...

Страница 9: ...chart Although individual units and models vary slightly the normal voltage and frequency of the engine gen erator described in this manual are approximately as follows under varying loads LOAD VS OUT...

Страница 10: ...ll state and local codes and regulations Check with local authorities before proceeding WARNING PERSONAL DANGER A fully isolated double pole double throw manual transfer switch must be installed any t...

Страница 11: ...The oil level must al ways be checked before the engine is started Take care to remove any dirt or debris from around the oil fill plug before removing Be sure the oil level is maintained Fill to the...

Страница 12: ...tion or replacement of parts should be performed only by a qualified electrical service technician USE ONLY FACTORY APPROVED REPAIR PARTS a Bearing The bearing used in these generators is a heavy duty...

Страница 13: ...Shorted capacitor Shorted diodes on rotor GFCI Receptacle tripped SPECIFICATIONS DL5000H D Generator manufacturer WINCO Inc Part number 15359 039 Rotor resistance 0 83 Ohms Stator resistance G1 N 0 6...

Страница 14: ...3310 00 14 60707 126 WIRING DIAGRAMS...

Страница 15: ...e repaired or replaced For warranty service return the product within 24 months from the date of purchase transportation charges prepaid to your nearest WINCO Authorized Service Center or to WINCO Inc...

Страница 16: ...RER S WARRANTY COVERAGE The evaporative emission control system is warranted for two years If any evaporative emission related parts on your equipment are defective the parts will be repaired or repla...