Wilo Yonos PICO1.0 Скачать руководство пользователя страница 14

en

Shutdown

14

WILO SE 2021-08

7.2.3

Completing the settings

ƒ

Do not rotate the operating button for 2 seconds.

The LED display flashes 5 times and changes to the current power consumption
in W.

NOTICE

All settings and displays are retained if the power supply is interrupted.

8

Shutdown

8.1

Shutting down the pump

Shut down the pump immediately if the connecting cable or other electrical compon-
ents are damaged.

ƒ

Disconnect the pump from the power supply.

ƒ

Contact Wilo customer service or a specialist technician.

9

Maintenance

9.1

Cleaning

ƒ

Carefully remove dirt from the pump on a regular basis using a dry duster.

ƒ

Never use liquids or aggressive cleaning agents.

10

Faults, causes and remedies

DANGER
Risk of fatal electrical shock!

Ensure there are no risks arising from electrical current!

• The pump must be voltage-free and secured against unauthorised reactivation

prior to any repair work.

• Damage to the mains connecting cables should always be repaired by a qualified

electrician only.

WARNING
Risk of scalding!

At high fluid temperatures and system pressures, allow the pump to cool down first
and then depressurise the system.

Faults

Causes

Remedies

Pump is not running with
switched-on power supply.

Fuse protection defect.

Check the fuse protection.

Pump is not running with
switched-on power supply.

Pump has no voltage.

Reconnect the voltage.

Pump makes noises.

Cavitation due to insuffi-
cient suction pressure.

Increase the system pres-
sure within the permissible
range.

Pump makes noises.

Cavitation due to insuffi-
cient suction pressure.

Check the delivery head
setting and set it to a lower
head if necessary.

Building does not get
warm.

Heat output of the heating
surfaces too low.

Increase setpoint.

Building does not get
warm.

Heat output of the heating
surfaces too low.

Set the control mode to
Δp-c.

10.1

Warning messages

ƒ

The warning signal is indicated by the LED display.

ƒ

The pump continues to run with limited output.

ƒ

The indicated faulty operating status must not occur for a prolonged period. The
cause must be eliminated.

Содержание Yonos PICO1.0

Страница 1: ...Pioneering for You Wilo Yonos PICO1 0 4248347 Ed 01 2021 08 en Installation and operating instructions...

Страница 2: ......

Страница 3: ...cations control mode and functions 7 4 Application use 7 4 1 Intended use 8 4 2 Misuse 8 5 Transportation and storage 8 5 1 Scope of delivery 8 5 2 Transport inspection 8 5 3 Transport and storage con...

Страница 4: ...on carries the following risks Danger to persons from electrical mechanical and bacteriological effects as well as electromagnetic fields Environmental damage from discharge of hazardous substances Da...

Страница 5: ...t be observed Before commencing work disconnect the product from the mains and secure it against being switched on again The connection must be secured by means of a residual current device RCD The pr...

Страница 6: ...with LED display 7 LED display Display of operating statuses 8 Operating button Settings of all parameters 9 Wilo Connector Electrical mains connection 3 2 Operating and display elements Operating but...

Страница 7: ...Radiator heating system H max H H min Hs Q Hs 1 2 Recommended for two pipe heating systems with radiators to reduce the flow noise at thermostatic valves Variable differential pressure p v The pump re...

Страница 8: ...distance from the product Never allow unauthorised persons to carry out work Never operate the pump beyond the specified limits of use Never carry out unauthorised conversions Never operate with phase...

Страница 9: ...ation posi tion Fig 2 The motor must always be installed horizontally The electrical connection must never face upwards Fig 2 Installation positions Choose an installation point that is easily accessi...

Страница 10: ...hen installing the pump Note the direction of flow arrow on the pump housing 1 Install with horizontal glandless motor 2 without mechanical tension Place gaskets in the screwed connections Screw on th...

Страница 11: ...ary adjust the RCD accordingly Only operate the pump with sinusoidal AC voltage Observe the switching frequency Switch on off procedures via mains voltage 100 24 h 20 h for a switching frequency of 1...

Страница 12: ...oving the Wilo Connector Connecting the pump Earth the pump Connect the Wilo Connector to the control module until it snaps into place Fig 5f Activate the power supply Removing the Wilo Connector Disc...

Страница 13: ...delivery head are provided as a guide only A more detailed calculation for the setting is recommended The values of the delivery head are displayed in increments of 0 1 m with the setting 7 2 1 Radiat...

Страница 14: ...onnecting cables should always be repaired by a qualified electrician only WARNING Risk of scalding At high fluid temperatures and system pressures allow the pump to cool down first and then depressur...

Страница 15: ...temperature Module interior too warm Check conditions of use E36 Module defective Electronics defective Request customer service If the fault cannot be remedied contact a specialist technician or the...

Страница 16: ...elated Products and Energy Information Amendment EU Exit Regulations SI 2019 No 539 _ Restriction of the Use of Certain Hazardous Substances RoHS in Electrical and Electronic Equipment Regulations SI...

Страница 17: ...turer declare under our sole responsability that these glandless circulating pump types of the series Als Hersteller erkl ren wir unter unserer alleinigen Verantwortung da die Nassl ufer Umw lzpumpen...

Страница 18: ...ge side HR Hrvatski HU Magyar FI Suomen kieli GA Gaeilge EU EY VAATIMUSTENMUKAISUUSVAKUUTUS AE EC DEARBH COMHL ONTA Matala J nnite 2014 35 EU S hk magneettinen Yhteensopivuus 2014 30 EU Energiaan liit...

Страница 19: ...patybilno ci Elektromagnetycznej 2014 30 UE Produkt w zwi zanych z energi 2009 125 WE sprawie ograniczenia stosowania niekt rych niebezpiecznych substancji 2011 65 UE 2015 863 De producten voldoen eve...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...Pioneering for You Local contact at www wilo com contact WILO SE Wilopark 1 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: