Commissioning
en
Installation and operating instructions Wilo-Control EC-L
77
Reset the current error message
NOTICE! Menu point is only shown when an error is present!
Manual operation pump 1
If the operating button is pressed, pump 1 runs.
If the operating button is released, the pump switches off. The last
set operating mode is active again.
Manual operation pump 2
If the operating button is pressed, pump 2 runs.
If the operating button is released, the pump switches off. The last
set operating mode is active again.
Manual operation pump 3
If the operating button is pressed, pump 3 runs.
If the operating button is released, the pump switches off. The last
set operating mode is active again.
Pump 1 switch off.
Corresponds to the “off” value in menu 3.02.
Pump 2 switch off.
Corresponds to the “off” value in menu 3.03.
Pump 3 switch off.
Corresponds to the “off” value in menu 3.04.
Automatic mode, pump 1
Corresponds to the “Auto” value in menu 3.02.
Automatic mode, pump 2
Corresponds to the “Auto” value in menu 3.03.
Automatic mode, pump 3
Corresponds to the “Auto” value in menu 3.04.
7.7
Factory settings
To reset the switchgear to the factory settings, contact customer service.
8
Commissioning
8.1
Operator responsibilities
▪ Provide installation and operating instructions at the switchgear or at a place specially
reserved for it.
▪ Make the installation and operating instructions available in a language the personnel
can understand.
▪ Make sure that the installation and operating instructions are read and understood by
all personnel.
▪ The installation site of the switchgear is overflow-proof.
▪ The switchgear must be properly fused and earthed.
▪ The signal transmitter must be installed and set in accordance with the system docu-
mentation.
▪ Observe the minimum water submersion of the connected pumps.
▪ Safety devices (incl. emergency off) of the entire system are switched on and checked
for trouble-free operation.
▪ The switchgear is suitable for use under the specified operating conditions.
8.2
Commissioning in explosive atmo-
spheres
The switchgear may
not
be put into operation in potentially explosive atmospheres!
Содержание Wilo-Control EC-L
Страница 2: ......
Страница 3: ...3 Deutsch 4 English 54 Fran ais 104 Polski 156 P 207 WILO187690...
Страница 209: ...ru Wilo Control EC L 209 1 1 1 1 2 1 3 1 4 www wilo com legal 2...
Страница 210: ...ru 210 WILO SE 2018 12 2 1 1 2 2...
Страница 211: ...ru Wilo Control EC L 211 2 3 2 4 2 5 IP 2 6 IP54 30 C 50 C 90 2 7 2 8 16 18 3...
Страница 216: ...ru 216 WILO SE 2018 12 1 2 3 4 5 6 6 4 3 IPS 6 4 4 Extern OFF 6 4 5 6 4 6 3 01 Extern OFF...
Страница 221: ...ru Wilo Control EC L 221 6 5 5 x Fig 9 30 1 1 2 2 3 3 6 5 6 off 1 2 on 1 on 2 Fig 10 off 1 2 on 1 1 on 2 2...
Страница 223: ...ru Wilo Control EC L 223 6 5 8 Fig 14 Fig 15 6 5 9 Fig 16...
Страница 225: ...ru Wilo Control EC L 225 Fig 19 SBM 250 1 A 6 5 13 SSM Fig 20 SSM 250 1 A 6 5 14 EBM...
Страница 228: ...ru 228 WILO SE 2018 12 7 7 1 1 2 SSM ESM SSM 7 1 1 1 2 1 Extern OFF 2 3 7 1 2 7 1 3 Extern OFF 3 01 3 04...
Страница 229: ...ru Wilo Control EC L 229 Extern OFF 7 1 4 7 2 3 01 OFF drain fill 7 2 1 4 3 1 2 5 Fig 24 1 1 2 2 3 1 2 4 5 1 2 1 2...
Страница 233: ...ru Wilo Control EC L 233 8 3 8 4 E006 5 68 off E080 x 5 69 off 6 01...
Страница 247: ...ru Wilo Control EC L 247 7 OFF 8 9 4 1 2 3 4 5 6 10 10 1 10...
Страница 248: ...ru 248 WILO SE 2018 12 10 2 1 10 3 Fig 72 SER Fig 73 7 01 on 1 3 1 00 2 7 3 7 01 4 7 07 5 6 0 0 25 0 5 1 2 7...
Страница 249: ...ru Wilo Control EC L 249 Fig 74 SER 7 01 on 1 3 1 00 2 7 3 7 01 4 7 08 5 6 on 7 11 11 1 11 2 11 3 Easy Actions...
Страница 252: ...ru 252 WILO SE 2018 12 www wilo recycling com 13 13 1 13 1 1 1 2 0 13 1 2 Ex i 13 1 3...
Страница 253: ...ru Wilo Control EC L 253 13 1 4 x Fig 76 217 4b 13 1 5 Fig 77 217 4b 13 1 6 1 3 1 00 2 5 3 5 01 4 5 64 5 6 on 7...
Страница 260: ......
Страница 261: ......
Страница 262: ......