Installation
70
WILO SE 2018-12
0-10 V
Fig. 18:
Overview of connection symbol
The actual level value is exported via a separate output. A voltage of 0 – 10 V is
provided for this at the output:
▪ 0 V = level sensor value “0”
▪ 10 V = level sensor upper limit
Example:
– Level sensor measurement range: 0 – 2.5 m
– Display range: 0 – 2.5 m
– Setting: 1 V = 0.25 m
Insert the connection cable laid by the customer through the threaded cable connec-
tions and secure. Connect the wires to the terminal strip according to the connection
diagram.
For details on the terminal number, see the overview of connections in the
cover.
Activate the function in menu 5.07 to output the actual level value.
6.5.12
Collective run signal (SBM) con-
nection
DANGER
Risk of fatal injury due to an external electrical current source!
The power supply comes from an external source. This voltage is also present at the
terminals when the main switch is switched off! There is a risk of fatal injury! The
power supply must be disconnected from its source before commencing any work!
Electrical work must be carried out by a qualified electrician in accordance with the
locally applicable regulations.
Fig. 19:
Overview of connection symbol
A run signal is exported for all pumps (SBM) via a separate output:
▪ Contact: potential-free changeover contact
▪ Switching capacity: 250 V, 1 A
Insert the connection cable laid by the customer through the threaded cable connec-
tions and secure. Connect the wires to the terminal strip according to the connection
diagram.
For details on the terminal number, see the overview of connections in the
cover.
6.5.13
Collective fault signal connection
(SSM)
DANGER
Risk of fatal injury due to an external electrical current source!
The power supply comes from an external source. This voltage is also present at the
terminals when the main switch is switched off! There is a risk of fatal injury! The
power supply must be disconnected from its source before commencing any work!
Electrical work must be carried out by a qualified electrician in accordance with the
locally applicable regulations.
Fig. 20:
Overview of connection symbol
A fault message is output for all pumps (SSM) via a separate output:
▪ Contact: potential-free changeover contact
▪ Switching capacity: 250 V, 1 A
Insert the connection cable laid by the customer through the threaded cable connec-
tions and secure. Connect the wires to the terminal strip according to the connection
diagram.
For details on the terminal number, see the overview of connections in the
cover.
Содержание Wilo-Control EC-L
Страница 2: ......
Страница 3: ...3 Deutsch 4 English 54 Fran ais 104 Polski 156 P 207 WILO187690...
Страница 209: ...ru Wilo Control EC L 209 1 1 1 1 2 1 3 1 4 www wilo com legal 2...
Страница 210: ...ru 210 WILO SE 2018 12 2 1 1 2 2...
Страница 211: ...ru Wilo Control EC L 211 2 3 2 4 2 5 IP 2 6 IP54 30 C 50 C 90 2 7 2 8 16 18 3...
Страница 216: ...ru 216 WILO SE 2018 12 1 2 3 4 5 6 6 4 3 IPS 6 4 4 Extern OFF 6 4 5 6 4 6 3 01 Extern OFF...
Страница 221: ...ru Wilo Control EC L 221 6 5 5 x Fig 9 30 1 1 2 2 3 3 6 5 6 off 1 2 on 1 on 2 Fig 10 off 1 2 on 1 1 on 2 2...
Страница 223: ...ru Wilo Control EC L 223 6 5 8 Fig 14 Fig 15 6 5 9 Fig 16...
Страница 225: ...ru Wilo Control EC L 225 Fig 19 SBM 250 1 A 6 5 13 SSM Fig 20 SSM 250 1 A 6 5 14 EBM...
Страница 228: ...ru 228 WILO SE 2018 12 7 7 1 1 2 SSM ESM SSM 7 1 1 1 2 1 Extern OFF 2 3 7 1 2 7 1 3 Extern OFF 3 01 3 04...
Страница 229: ...ru Wilo Control EC L 229 Extern OFF 7 1 4 7 2 3 01 OFF drain fill 7 2 1 4 3 1 2 5 Fig 24 1 1 2 2 3 1 2 4 5 1 2 1 2...
Страница 233: ...ru Wilo Control EC L 233 8 3 8 4 E006 5 68 off E080 x 5 69 off 6 01...
Страница 247: ...ru Wilo Control EC L 247 7 OFF 8 9 4 1 2 3 4 5 6 10 10 1 10...
Страница 248: ...ru 248 WILO SE 2018 12 10 2 1 10 3 Fig 72 SER Fig 73 7 01 on 1 3 1 00 2 7 3 7 01 4 7 07 5 6 0 0 25 0 5 1 2 7...
Страница 249: ...ru Wilo Control EC L 249 Fig 74 SER 7 01 on 1 3 1 00 2 7 3 7 01 4 7 08 5 6 on 7 11 11 1 11 2 11 3 Easy Actions...
Страница 252: ...ru 252 WILO SE 2018 12 www wilo recycling com 13 13 1 13 1 1 1 2 0 13 1 2 Ex i 13 1 3...
Страница 253: ...ru Wilo Control EC L 253 13 1 4 x Fig 76 217 4b 13 1 5 Fig 77 217 4b 13 1 6 1 3 1 00 2 5 3 5 01 4 5 64 5 6 on 7...
Страница 260: ......
Страница 261: ......
Страница 262: ......