Installation and operating instructions Wilo-VeroLine-IP-Z
21
• The pump must be protected from the weather and installed in a
frost/dust-free, well-ventilated environment which is not potentially
explosive.
• Install the pump in a place that is easy to access so that subsequent
inspections, maintenance (e.g. mechanical seal) or replacement is
easily possible.
Installation
The standard IP-Z pump was designed for use in return flow systems.
It features a suction port on top (indicated by an arrow on the pump
housing, see Fig. 2).
If it is installed in a heating system or air-conditioning system (suction
port faces downward), the pump housing must be rotated by 180°
(or 90°) on the lantern (see Fig. 2).
CAUTION! Risk of property damage!
Risk of damage due to incorrect installation.
• Always install with the pump motor in the horizontal position.
Hydraulic connections
• Connect the pump directly to the pipes using threaded screws (avail-
able as accessories, see section 5.4 "Accessories" on page 20).
• Shut-off devices must be installed without fail in front of and behind
the pump in order to avoid the entire system being drained when the
pump is inspected or exchanged.
• In process water systems, a non-return valve must be installed on the
pressure port side.
• The pipes and pump must be free of mechanical stress when installed.
7.2
Electrical connection
Safety
DANGER! Risk of fatal injury!
An improper electrical connection can result in a fatal electrical
shock.
• Have the electrical connection established by an electrician
approved by the local electricity supplier only and in accordance
with local regulations.
• Observe the installation and operating instructions for the acces-
sories!
Preparation/notes
CAUTION! Risk of property damage!
Risk of damage due to incorrect electrical connection.
• The mains connection cable must be protected against moisture.
• The mains connection cable must be installed in such a way that it
cannot under any circumstances come into contact with the pipe
and/or the pump and motor housing.
• Check whether the terminal box is accessible and water-proof (pro-
tected against leakage, water spray or condensate, etc.).
• Check the current type and voltage of the mains connection.
• Observe the rating plate information for the pump. The current type
and voltage of the mains connection must correspond to the details
on the rating plate.
• Only use connection cables that comply with VDE or local regulations.
• The electrical connection must be established via a fixed power cable,
which is provided with a plug device or an all-pole switch with a con-
tact opening width of at least 3 mm (in accordance with VDE 0730
Part 1 in Germany).
• In order to ensure drip protection and strain relief on the threaded
cable connection, cables are to be used which have a sufficient outer
diameter and are to be screwed sufficiently tightly. To get rid of any
drips that accumulate, the cables are to be bent into a drain loop near
the threaded cable connection.
Содержание VeroLine-IP-Z
Страница 2: ......
Страница 3: ...Fig 1 Fig 2...
Страница 4: ...Fig 3 3 1 1 13 1 14 1 12 3 1 13 1 11 1 12 1 15 1 14 1 1 1 14 1 21 1 22 1 15 1 13 1 2 1 31 1 14 1 3 5 2...
Страница 72: ...68 WILO SE 11 2017 1 2 2 1...
Страница 73: ...Wilo VeroLine IP Z 69 2 2 2 3 2 4 2 5 IEC VDE...
Страница 74: ...70 WILO SE 11 2017 2 6 2 7 2 8 4 3 3 1 4 IP Z VDI 2035...
Страница 77: ...Wilo VeroLine IP Z 73 6 6 1 Noryl 7 7 1 1 1 2 3 4 5 6 7 8 9 10 11 12 IP Z IP Z 2 180 90 2...
Страница 78: ...74 WILO SE 11 2017 5 4 72 7 2 VDE 3 1 VDE 0730...
Страница 79: ...Wilo VeroLine IP Z 75 90 C 3 1 230 3 x 0 75 2 3 x 2 5 2 2 3 230 400 4 x 0 75 2 4 x 2 5 2 3 8 3...
Страница 80: ...76 WILO SE 11 2017 8 1 3 230 400 2 L1 L2 9 Wilo 5...
Страница 81: ...Wilo VeroLine IP Z 77 5 9 1 5...
Страница 82: ...78 WILO SE 11 2017 5 1 230 8 75 9 2 Wilo 9 1 77 1 15 1 11 1 21 1 31 1 21 1 11 1 15 1 14 9 1 77 8 75 10 M5 5...
Страница 83: ...Wilo VeroLine IP Z 79 10 9 76 Wilo 11 Wilo Wilo 3 L1 L2 Wilo...
Страница 84: ...80 WILO SE 11 2017 Wilo www wilo ru 12 1 2 www wilo recycling com...
Страница 88: ......
Страница 89: ......
Страница 90: ......