30
WILO SE 11/2013
Minimum inlet pressure (above atmospheric pressure) at the pump suction port
in order to avoid cavitation noises (at fluids temperature T
Med
):
The values apply up to 300 m above sea level; allowance for higher altitudes:
0.01 bar/100 m increase in height.
5.3 Scope of delivery
• Pump, complete
• Two gaskets for threaded connection
• Two-part thermal insulation shell (single pump only); not on TOP-RL
and TOP-I
• 8 x M12 washers
(for M12 flange screws on combination flange version DN 32-DN 65)
• 8 x M16 washers
(for M16 flange screws on combination flange version DN 32-DN 65)
• Installation and operating instructions
5.4 Accessories
Accessories must be ordered separately:
• Wilo-Protect Module C
• Switching plug for 3~230 V
See catalogue for detailed list.
6 Description and function
6.1 Description of the pump
The pump is fitted with a glandless motor (single-phase (1~) or three-phase
(3~),
for mains connection voltage and mains frequency see the rating plate
,
in which all the rotating parts are in contact with the fluid. The design relies on
the fluid to provide lubrication for the plain bearings of the rotor shaft.
The motor is multi-speed. Speed switching is executed in different ways
depending on the terminal box. This is performed either by a speed selection
switch, by plugging in the switching plug differently or by internally or exter-
nally jumpering the contacts (See Commissioning/Switching Over the Speed).
A suitable switching plug is available as an accessory for 3 ~230 V.
TOP-S/-SD/-RL
TOP-I
T
Med
Rp 1, Rp 1¼,
DN 32/40
DN 50, DN 65,
DN 80, DN 100
Rp ¾, Rp 1
+50 °C
0.05 bar
0.3 bar
0.5 bar
+80 °C
-
-
0.8 bar
+95 °C
0.5 bar
1.0 bar
-
+110 °C
1.1 bar
1.6 bar
2.0 bar
+130 °C
2.4 bar(*)
2.9 bar(*)
-
(*) not applicable to TOP-S 25/13, TOP-S/-SD 80/15, TOP-S/-SD 80/20