1 General Information
Installation and commissioning only by qualified personnel
1.1 Uses
The pump is suitable for hot and cold water and other fluids free from
mineral oil and without abrasives or long-fibred substances. The main
areas of use are in water supply installations, as a booster pump, as a
boiler feeder pump, in industrial circulation systems, in process tech-
nology, in cooling water systems, in fire extinguishers and in washing
and sprinkler installations.
1.2 Product data
1.2.1 Connection and electrical data
(Table 1)
Pumping medium allowed
Permissible media temperature
Maximum ambient temperature
Maximum permissible working pressure:
at the inlet (inlet pressure see paragraph 5.3)
at the outlet, for a 2 pole motor
at the outlet, for a 2 pole motor
Mains voltages
DM: for P
2
≤
4 kW:
for P
2
≥
5.5 kW:
Standard motor
for P
2
≤
5.5 kW:
for P
2
≥
7.5 kW:
Speed
2 pole version
4 pole version
Mains fuse protection
Insulation class
System of protection
Drinking water in acc. with Drinking Water Order
Heating water / service water
Condensate
Water/glycol mixture
1
)
Other liquid media
2
)
-15 °C to +120 °C
(Follow catalogue instructions)
+40 °C
16/
10 bar
16/25 bar
16/
16 bar
3 ~ 230/400 V ± 10 %, 50 Hz
3 ~ 400 V ± 10 %, 50 Hz
V 18 standard motor
V 1 standard motor
2900 RPM
1450 RPM
see motor rating plate
F
IP 55
better protective systems available
1
) When using a water-glycol mixture containing up to 40 % glycol (or media with a viscosity different to that of pure water, the flow data for the pump must be adjusted accord-
ing to the higher viscosity of the flow media, regardless of the percentage of the viscous matter. Only use branded goods with corrosion protection-inhibitors, follow manufac-
turer’s instructions.
2
) If other and also aggressive chemical fluids are to be pumped, be sure to follow catalogue instructions and first obtain the approval of WILO.
Principal dimensions and connection dimensions
(Table 2, see also Fig. 3):
When ordering spare parts, please give all the information on the pump/motor rating plate.
Types
PN16 version
PN25 version
A
B
Y
W
Z
E
F
J
K
A
B
Y
W
Z
E
F
J
K
MV
I
mm
mm
1602
è
1614
DN50
194
252
20
215
130
300
90
125
4x18
194
252
20
215
130
300
90
125
4x18
3202
è
3216
DN65
235
235
35
195
195
320
105
145
4x18
260
260
35
220
220
320
120
145
8x18
5202
è
5212
DN80
260
260
30
220
220
320
105
160
8x18
260
260
30
220
220
320
105
160
8x18
7001
è
7007
DN100
261
350
45
280
199
380
140
180
8x19
261
350
45
280
199
380
140
190
8x23
9501
è
9506
DN100
261
350
45
280
199
380
140
180
8x19
261
350
45
280
199
380
140
190
8x23