41
WILO SE 03/2013
English
100%
Set value 4-20mA
0
2
4
20
Input current (mA)
Set value
in % of the range
of measurement of
the sensor
Area where converter stops
Safety
area
100%
Set value 0-10V
0
1
2
10
Input voltage (V)
Set value
in % of the range
of measurement of
the sensor
Area where converter stops
Safety
area
IN2 : Input of the external set value control in « Constant pressure » and « P.I.D. control » mode
IN2 : Input of external frequency control in « Speed control » mode
100%
~30%
~30%
External Signal 0-20mA
0
2
4
6
10
20
Input current (mA)
Frequency
of the converter
Area where converter stops
Safety
area
100%
External Signal 4-20mA
0
20
Input current (mA)
Frequency
of the converter
Area where converter stops
Safety
area
~30%
3
5
100%
External Signal 2-10V
0
10
Input voltage (V)
Frequency
of the converter
Area where converter stops
Safety
area
100%
~30%
External Signal 0-10V
0
1
2
10
Input voltage (V)
Frequency
of the converter
Area where converter stops
Safety
area