42
• Les câbles du capteur, de la consigne externe,
des entrées [Ext.off] et [Aux] doivent impérati-
vement être blindés.
- The electric characteristics (frequency, voltage,
nominal current) of the frequency converter are
specified on the pump identification label.
Ensure that the frequency converter complies
with the power supply it will be used with.
- The electric protection of the motor is inte-
grated into the converter. It is set up to take into
account the pump characteristics and ensure the
protection of pump and motor.
- In all cases, install a fused isolator (type gF) to
protect the unit.
NOTICE: If a residual-current device needs to be
installed for the user’s protection, it must have
a delay effect. Adjust the circuit breaker rating
according to the current provided on the pump
identification sticker.
NOTICE: This pump is equipped with a frequency
converter and does not require protection from
a residual-current device. Frequency convert-
ers can impair the function of residual-current
devices.
Exception: Residual-current devices that have a
selective universal-current-sensitive design are
permitted.
Power (kW)
0.75
1.1
1.5
2.2
M25
Power (kW)
0.75
1.1
1.5
2.2
Cable
shield-
ing
M20
M12
M25
M12
M16
• Labelling:
FI
•
Trigger current: > 30 mA.
- Use only power cables complying with applicable
regulations.
-
Protection on mains side: max. admissible 25 A.
Trigger characteristic of the fuses: B.
As soon as the power supply to the converter is
activated, a 2-second display test is carried out
during which all characters on the display are
shown.
NOTICE: Requirements and limit values for
harmonic currents.
Pumps with the engine-power classes of 11 kW,
15 kW, 18.5 kW and 22 kW are equipment
for professional usage. These devices are sub-
ject to special connectivity conditions since
a short-circuit ratio Rsce of 33 at the connecting
point is not sufficient for your type of operation.
The connection to the public low-voltage mains
is regulated by the standard IEC 61000-3-12 –
the basis for these pumps’ rating is table 4 for
three-phase devices under specified conditions.
For all public connection points, the short-circuit
power Ssc at the interface between the user’s
electrical installation and the public power supply
must be greater than or equal to the values in the
table below. It is the responsibility of the installer
or of the user, and if applicable the distribution
system operator too, to ensure that these pumps
are operated properly. If the pump is used within
an industrial middle-voltage system, the connec-
tivity conditions are the sole responsibility of the
operator.
By installing an appropriate harmonic filter
between the pump and the power supply, the
harmonic current content will be reduced.
Motor power
[kW]
Shortcircuit Ssc power
[kVA]
11
1800
15
2400
18.5
3000
22
3500
English
WILO SE 11/2019
Содержание Economy MHIE
Страница 3: ...ou or 16 15 14 10 Fig 5 16 15 14 Fig 7 ou or 16 15 14 10 Fig 6...
Страница 4: ...Fig 8 Fig 9 18 19...
Страница 5: ...Fig 1D 1...
Страница 6: ......
Страница 120: ...120 WILO SE 11 2019 1 1 1 2 2 1 2 2 2 3 2 4 2 5...
Страница 121: ...121 Wilo Economy MHIE 2 6 2 7 2 8 4 3 4...
Страница 130: ...130 WILO SE 11 2019 100 100 4 20 0 0 2 2 4 4 20 10 0 2 0 1 100 100 0 20 0 0 20 10 2 10 0 10 S1 S2...
Страница 135: ...135 Wilo Economy MHIE Fig A1 1 OFF OPERATION 1 OFF OPERATION PID 1 OFF OPERATION Information Service...
Страница 137: ...137 Wilo Economy MHIE Fig A2 EASY EXPERT EXPERT Fig A4 Information EASY Fig A3...
Страница 141: ...141 Wilo Economy MHIE Fig A5 Information SSM SBM Ext Off INFORMATION 4000...
Страница 142: ...142 WILO SE 11 2019 2 ON 7 0 0 0 2 OFF A1 1 9 15 000...
Страница 143: ...143 Wilo Economy MHIE 10 Wilo NPSH Ha 4 4 4 4...
Страница 144: ...144 WILO SE 11 2019 9 2 SBM 5 7 6 0 3 1 2 3 SSM 1 6 6 24 SBM 24 SBM SSM 1 2 3 4 5 6...
Страница 146: ...146 WILO SE 11 2019 10 2 6 0 0 0 24 1 6 300...
Страница 147: ...147 Wilo Economy MHIE 11 Wilo www wilo com 12 www wilo recycling com...
Страница 152: ......