background image

English

27

  6 Commissioning

If the pump is supplied separately, i.e. if 

it is not integrated in a system that has 

been mounted by us, then the config-

uration type at the time of delivery is 

either Mode 1-3 or Mode 2, depending 

on the type of pump control desired.

As a reminder: A programming key is  

used to switch from 

Mode 1-3 to Mode 

2 (or vice-versa); an after-sales service 

employee must be called in.

 6.1 Settings

  -  In manual mode: 

Mode 1 (see Figs. 1, 2).

 

   The duty point of the pump is reached with the 

aid of the potentiometer 

(see Fig. 9, Pos. 19) by 

setting the speed of the motor between 40% and 

100% of the maximum speed.

 

   We recommend that the motor speed be set to 

70 % for commissioning.

  -   The pump can be brought to a standstill (fre-

quency converter under tension) with the remote 

control unit (switch). 

  -   In pressure regulation operating mode: 

Mode 2  

(see Figs. 6, 7, 8). 

It is possible to regulate the pressure of the 

pump through the addition of a pressure sensor 

and a diaphragm pressure vessel. The sensor 

must exhibit an accuracy of <1% and be used in 

a range between 30% and 100% of its measure-

ment range; the reservoir has a useable volume 

of at least 8 litres.

 

  

No water in the diaphragm pressure vessel. 

Pump up the diaphragm pressure vessel to a 

pressure that is 0.3 bar less than the control 

pressure of the pump (diaphragm pressure ves-

sel and sensor kit included as accessories in the 

scope of delivery).

The setpoint for the pressure regulation is speci-

fied in two types: 

 

  •  The setting of the potentiometer indicates for 

the setpoint for a value between 0 and 100% of 

the measurement range of the sensor. We rec-

ommend that the potentiometer be set to  

100% for commissioning.

 

  •  An external signal can be connected (0-10 V 

or 0-20 mA) for setting the setpoint by remote 

control 

(see Chapter 5.3 - Electrical connec-

tions). 

 

   NOTE:  The function «Detection of zero volume 

flow» makes it possible to stop the pump.

  -   Via external control per frequency: 

Mode 3 (see 

Fig. 10).

The potentiometer has no function in Mode 3, but 

it must nonetheless be set to 100%. The pump is 

controlled by an external signal.

Specifications concerning commissioning: see 

instruction manual for the pressure boosting sys-

tem.

During normal operation, the status of the LEDs 

is as follows: (see Fig. 9, Pos. 17 + 18)

  6.2  Preparatory flushing

Because our pumps are hydraulically tested in 

the factory, it is possible that there is still water 

in their interiors. For reasons of hygiene, it is 

therefore recommended that they be flushed 

out prior to use in a potable water network.

  6.3  Filling - bleeding

Never permit the pump to run dry, not 

even for a brief moment.

Pump in intake mode (see Fig. 2)

  -  

Close the stop valve on the pressure side 

(Pos. 3)

open the inlet/bleeder screw 

(Pos. 5)

  -   Gradually open the valve that is located on the 

pipework at the entry to the pump 

(Pos. 2) 

and carry out the complete filling of the pump. 

Retighten the screw firmly after water begins to 

emerge and ventilation is complete.

Danger of injury to personnel!

A jet of water can escape from the ventilation 

opening when hot water is being pumped. 

Initiate all necessary precautionary measures to 

ensure that personnel and the motor/frequency 

converter are protected!

Pump in suction mode (see Fig. 1) Two different 

cases are possible.

1st case (see Fig. 4.1)

  -   Close the stop valve on the pressure side 

(see Fig. 1, Pos. 3).

  -  

Open the stop valve on suction side 

(see Fig. 1, 

Pos. 2).

  -  

Unscrew the inlet/bleeder screw 

(see Fig. 1, Pos. 5),  

that is located on the pump housing.

  -   Fill the pump and suction line completely with the 

aid of a funnel inserted into the opening.

  -   The filling procedure is finished when water 

escapes and ventilation is complete.

  -   Screw the inlet/bleeder screw back on.

2nd case (see Fig. 4.2)

The filling can be made easier if a pipe equipped 

with a cock 

(Pos. 12) Ø 1/2» and a funnel 

is mounted perpendicularly on the suction line 

of the pump.

  -   Close the stop valve on the pressure side 

(see Fig. 1, Pos. 3).

 - 

 Open the stop valve on suction side 

(see Fig. 1, 

Pos. 2).

 - 

 Open cock 

(see Fig. 4, Pos. 12) and inlet/bleeder  

screw 

(see Fig. 1, Pos. 5).

  -   Fill pump and suction line completely, until bub-

ble-free water escapes from the filling opening.

  -   Close the cock 

(see Fig. 4, Pos. 12) (it can remain 

mounted on the pipe), remove the pipe and screw 

the inlet/bleeder screw back in.

Frequency converter voltage 

on  

off 

load/pump in operation
Frequency converter voltage 

on  

off 

load/pump in standstill

Status of the LEDs 

green LED  red LED

ATTENTION!

ATTENTION!

WILO SE 04/2016

Содержание Economy MHIE 1 Series

Страница 1: ...d Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbouw en bedieningsvoorschriften es Instrucciones de instalaci n y funcionamiento it Istru...

Страница 2: ...Fig 1 Fig 3 Fig 2 Fig 4 Fig 5 or ou or ou...

Страница 3: ...Fig 6 Fig 7 Fig 8 or ou or ou...

Страница 4: ...Fig 9 Fig 10...

Страница 5: ...he failure to observe these instruc tions could lead to the following hazards Failure of important functions of the pump instal lation Hazards to personnel resulting from electrical mechanical or bact...

Страница 6: ...table water network Pos 10 5 1 Installation Install the pump at a readily accessible location which is protected against external influences excessive rain or sunlight frost and which is as near as po...

Страница 7: ...standard specifications The electrical properties frequency voltage nominal current of the motor frequency convert er are indicated on the name plate of the motor of the pump A check is to be made as...

Страница 8: ...r of the frequency converter Mains connection Connect three lines of the cable to the 3 connection terminals of the board Phase Neutral Earth Connecting the inputs outputs 3 operating modes exist see...

Страница 9: ...0 V 24 V 24 V 2 3 4 5 6 7 8 9 10 11 12 13 14 0 V 4 20 mA 24 V 0 V 0 10 V 24 V 2 Connection of the potentiometer Connection terminals Inputs outputs of the frequency converter Diagram Adjusting the se...

Страница 10: ...ble connections It is possible to start or stop the pump with the external control potential free contact this function takes precedence over the other functions This external control can be removed b...

Страница 11: ...3 1 6 3 1 4 3 1 7 3 1 5 4 ATTENTION Operating modes Mode 1 Mode 3 0 20 mA Mode 3 0 10 V Mode 2 PI control sensor 4 20 mA Mode 2 PI control sensor 0 10 V Mode 2 PI control sensor 4 20 mA External contr...

Страница 12: ...0 V Input voltage V Pressure in of the sensor measurement range 100 0 2 20 Setpoint 0 20 mA Range in which the frequency converter stops Input current level mA Pressure in of the sensor measurement ra...

Страница 13: ...instruction manual for the pressure boosting sys tem During normal operation the status of the LEDs is as follows see Fig 9 Pos 17 18 6 2 Preparatory flushing Because our pumps are hydraulically test...

Страница 14: ...on the pump shield 7 Maintenance The pump s must be de energised and all non authorised restarts must be pre vented before any maintenance work is done Never undertake maintenance work while the pump...

Страница 15: ...ontact your local professional tradesmen or the Wilo after sales service in your vicinity ATTENTION Display Frequency converter beha viour Fault possible causes Elimination Green LED Red LED Reaction...

Страница 16: ...intained b The suction line has a smaller circ umference than that of the pump c Suction strainer and suction line are partially blocked a Check correct setting of the nominal values setpoints matchin...

Страница 17: ...any Die Seriennummer ist auf dem Typenschild des Produktes nach Punkten b c von 1 7 4 2 und 1 7 3 des Anhanges I der Maschinenrichtlinie angegeben The serial number is marked on the product site plate...

Страница 18: ...k nemzeti jogrendbe t ltetett rendelkez seinek WILO SE vakuuttaa ett t ss vakuutuksessa kuvatut tuotteet ovat seuraavien eurooppalaisten direktiivien m r ysten sek niihin sovellettavien kansallisten l...

Страница 19: ...4 30 ES Maszyn 2006 42 WE Kompatybilno ci Elektromagnetycznej 2014 30 WE WILO SE WILO SE estne prehlasuje e v robky ktor s predmetom tejto deklar cie s v s lade s po iadavkami nasleduj cich eur pskych...

Страница 20: ...2785961 info wilo kz Korea WILO Pumps Ltd 618 220 Gangseo Busan T 82 51 950 8000 wilo wilo co kr Latvia WILO Baltic SIA 1019 Riga T 371 6714 5229 info wilo lv Lebanon WILO LEBANON SARL Jdeideh 1202 2...

Страница 21: ...Pioneering for You WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: