Installation and operating instructions Wilo-DrainLift XS-F
21
5 Product information
5.1 Type key
Please state all the information on the system name plate when ordering spare parts.
Fig. 1: Application limits
The flow rate in the pressure pipe must be at least 0.7 m/s. For
safe operation, the maximum geodesic delivery head of 4 mWS
must not be exceeded. Fig. 1 shows the resulting application
limits and delivery distances (maximum pressure pipe lengths DN
32 / DN 25) depending on the pipe diameter.
For best results, the pressure pipe should be laid first vertically
and then horizontally (including two 90° bends and an integrated
non-return valve).
When installed according to the regulations and properly used,
the unit complies with the EMC safety requirements of EU direc-
tive 89/336 EEC and is suitable for domestic use on the public
electricity mains.
Proper use includes compliance with the instructions in this
manual.
Any other use is considered improper.
4,0
DN 32
2 m
11 m
20 m
29 m
39 m
48 m
57 m
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0
H[m]
65 m
DN 25
4,0
3 m
7 m
11 m
15 m
19 m
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0
H[m]
23 m
Example:
DrainLift XS-F
DrainLift
Lifting unit
XS
Size
-F
Front-wall
5.2
Technical data
Connected voltage
[V]
1~230,
±
10%
Power consumption P
1
[kW]
0,4
Rated current
[A]
1,8
Mains frequency
[Hz]
50
Protection class
IP 24
Speed
[¹/min]
2610
Operating mode
S 3 30% (3 min. operation – 7 min. pause)
Max. total delivery head
[mWS]
See name plate
Max. permitted geodesic delivery head
[mWS]
4
Max. volume flow
[m³/h]
See name plate
Max. fluid temperature
[°C]
35
Gross volume
[l]
7,9
Dimensions incl. non-return valve
(WxDxH)
[mm]
515x168x410
Weight
[kg]
6,5
Pressure port
[DN]
32 (outer diameter AD 40)
Inlet ports
[DN]
50, 100
Ventilation
[DN]
50
CE
WILO AG Dortmund
Nortkirchenstr. 100, 44263 Dortmund
07
EN 12050-3
DN 25 Sewage lifting unit for limited use
Lifting power
- see rating plate
Noise level
< 70 db(A)
Corrosion
protection
- inox/composite corrosion-resistant
materials