![Wilo COR-1HELIX VE5203/3/VR Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/wilo/cor-1helix-ve5203-3-vr/cor-1helix-ve5203-3-vr_installation-and-operating-instructions-manual_982862021.webp)
English
26
WILO SE 07/2010
6.5
Scope of delivery
• Single-pump pressure boosting system
• Installation and operating instructions of the sin-
gle-pump pressure boosting system
• Installation and operating instructions of the
pump
• Installation and operating instructions of the con-
trol device
• Factory acceptance test certificate (in accordance
with EN 10204 3.1.B)
• Installation plan if applicable
• Electrical wiring diagram if applicable
• Installation and operating instructions of the fre-
quency converter if applicable
• Additional sheet with the factory setting of the
frequency converter if applicable
• Installation and operating instructions of the sig-
nal transmitter if applicable
• Spare parts list if applicable
6.6
Accessories
Accessories must be ordered separately if needed.
The accessories included in the Wilo range include
the following:
• Open break tank
• Larger diaphragm pressure tank (on the suction
side or discharge side)
• Safety valve
• Dry-running protection:
• Protection against low water level (WMS)
(Fig. 6a and 6b) in inlet mode (at least 1.0 bar)
(already fitted to the system if part of the order)
• Float switch
• Low-water warning electrodes with level relay
• Electrodes for tank operation (special accesso-
ries on request)
• Flexible connection lines
• Expansion joints
• Threaded flange
• Sound-insulating casing (special accessory on
request)
7 Installation
7.1 Installation site
• The installation is installed in the technical control
room or in a separate, dry, well ventilated and
frost-proof room that can be locked (requirement
of DIN 1988 to be observed where applicable).
• Adequately dimensioned floor drainage (drain
connection or similar) must be provided in the
installation room.
• No harmful gases must penetrate the room or be
present there.
• Adequate space must be provided for mainte-
nance work. The main dimensions are given on the
attached installation plan. The system should be
freely accessible from at least two sides.
• The installation surface must be horizontal and
flat. The bearing surface must have adequate
load-bearing capacity.
• The system is designed for a maximum ambient
temperature of +0 °C to 40 °C with a relative
atmospheric humidity of 50%.
• Installation and operation in the vicinity of living
rooms and bedrooms is not recommended.
• To avoid the transmission of structure-borne
noise and to ensure a stress-free connection to
upstream and downstream pipes, expansion joints
with extension limiters or flexible connection lines
should be used.
7.2 Installation
7.2.1 Foundation/bearing surface
The system is constructed for installation on flat
concrete floors. The base frame is mounted on
height-adjustable vibration absorbers to prevent
structure-borne noise.
NOTE:
The vibration dampers may not be fitted when the
equipment is delivered for transport reasons.
Before installing the system, make sure that all the
vibration dampers are fitted and locked by the
threaded nuts (see also Fig. 8).
If the customer also wants to secure the installa-
tion to the floor, suitable measures must be taken
to avoid structure-borne noise.
Содержание COR-1HELIX VE5203/3/VR
Страница 4: ...Fig 2a Fig 2b...
Страница 5: ...Fig 3a 20 19 25 24 21 22 20 19 26 27...
Страница 6: ...Fig 3b 19 28 20 21 19 20 21 22 23...
Страница 7: ...Fig 4 Fig 5...
Страница 8: ...Fig 6a...
Страница 9: ...Fig 6b Fig 7a Fig 7b...
Страница 10: ...Fig 8...
Страница 11: ...Fig 9 Fig 10a...
Страница 12: ...Fig 10b...
Страница 32: ......
Страница 33: ......