Installation and operating instructions Wilo-Control SC-L 43
OPERATION AND FUNCTION English
Menu 3: Pump activation
No.
Description
Display
3.2.1.1
Operating mode, pump 1
Values: OFF, MANUAL, AUTO
Factory setting: AUTO
3.2.2.1
Operating mode, pump 2
Values: OFF, MANUAL, AUTO
Factory setting: AUTO
3.2.3.1
Operating mode, pump 3
Values: OFF, MANUAL, AUTO
Factory setting: AUTO
3.2.4.1
Operating mode, pump 4
Values: OFF, MANUAL, AUTO
Factory setting: AUTO
Menu 4: Display of current settings and basic switchgear
data
No.
Description
4.1.0.0
Current operating values
4.1.1.0
Current level
4.1.2.0
Current control values
4.1.2.1
Base-load pump on
4.1.2.2
Base-load pump off
4.1.2.3
Peak-load pump 1 on
4.1.2.4
Peak-load pump 1 off
4.1.2.5
Peak-load pump 2 on
4.1.2.6
Peak-load pump 2 off
4.1.2.7
Peak-load pump 3 on
4.1.2.8
Peak-load pump 3 off
4.1.4.0
Limit values
4.1.4.1
Dry-running protection level
4.1.4.2
High water alarm level
4.2.0.0
Operating data
4.2.1.0
Total running time of the system
4.2.2.x
Running time of the individual pumps
4.2.3.0
Unit switching cycles
4.2.4.x
Switching cycles of the individual pumps
4.3.0.0
Details of switchgear
4.3.1.0
Switchgear type
4.3.2.0
Serial number (as ticker format)
4.3.3.0
Software version
4.3.4.0
Firmware version
Menu 5: Basic switchgear settings
No.
Description
Display
5.0.0.0
Basic settings
Menu 5: Basic switchgear settings
No.
Description
Display
5.1.0.0
Communication
5.1.1.0
Modbus
5.1.1.1
Baud rate
Values: 9.6, 19.2, 38.4, 76.8
Factory setting: 19.2
5.1.1.2
Slave address
Value range: 1 to 247
Factory setting: 10
5.1.1.3
Parity
Values: even, non, odd
Factory setting: even
5.1.1.4
Stop bits
Values: 1, 2
Factory setting: 1
5.1.2.0
BACnet
5.1.2.1
Baud rate
Values: 9.6, 19.2, 38.4, 76.8
Factory setting: 19.2
5.1.2.2
Slave address
Value range: 1 to 255
Factory setting: 128
5.1.2.3
Parity
Values: even, non, odd
Factory setting: even
5.1.2.4
Stop bits
Values: 1, 2
Factory setting: 1
5.1.2.5
BACnet instance device ID
Value range: 0 to 9999
Factory setting: 128
5.1.3.0
GSM**
5.2.0.0
Sensor settings
5.2.1.0
Measurement range
Value range: 0 to 12.50
Factory setting: 2.50
5.2.2.0
Sensor type
Values: 0-10 V, 2-10 V, 0-20 mA,
4-20 mA
Factory setting: 4-20 mA