ERROR CODE

BOOSTER BEHAVIOUR

TROUBLESHOOT

E011 DRY RUN

The controller starts the pump every 

30 minutes over 24 hours. If dry 

running remains, it switches off the 

pump.

Check the hydraulic supply.

If a set point pressure higher than the 

pressure the pump can deliver is pro-

grammed, the controller will consider it 

as dry running.

E021 OVERLOAD

After the alarm detection the control-

ler will try 4 times to 

Check that the rotor is not locked.

start the pump. After these 4 trials 

the pump is switched off. 

Check the state of the fuses..

Check the input data in the controller

E025 DISCONNECT MOTOR

Motor will not start.

Check the motor winding.

Check the supply cables. 

Check that the Imax is not set to off in 

the menu (Table 2)

E040 P SENSOR DEFFECT

The controller stops.

Contact the technical service depart-

ment.

E031 OVER T°

If the temperature is too high, the 

controller will stop the motor from 

running. 

Check that the water temperature does 

not exceed 40°C.

Check that the ambient temperature 

does not exceed 50°C.

E023 SHT CIRCUIT

After the alarm detection the 

Check the motor connections and wind-

ings. If the problem remains contact the 

manufacturer.

controller will try 4 times to start the 

pump. After these 4 trials the pump is 

switched off.

E071 EEPROM

If the controller detects a defect on 

its internal memory this error will be 

displayed.

Contact the technical service depart-

ment.

E005 HIGH VOLTAGE

If the controller detects an overvolt-

age, it stops over some seconds and 

then starts again.

Check the controller supply voltage.

E004

If the controller detects an under 

voltage, it stops the pumps.

Check the controller supply voltage.

LOW VOLTAGE

[WHITE SCREEN]

No function and nothing on the 

screen.

Check the controller supply voltage and 

circuit breakers in (Fig 1).

Check the 20A fuses

Table 3 - Drive Fault Codes & Troubleshooting

Содержание 29993227

Страница 1: ...V608 29993231 Centrum SV1004 29993232 Centrum SV1006 29993233 Centrum DV406 29993234 Centrum DV408 29993235 Centrum DV605 29993236 Centrum DV608 29993237 Centrum DV1004 29993238 Centrum DV1006 2999323...

Страница 2: ...3 1 Fault Contacts 4 4 3 2 Low Water Cut Protection 4 4 3 3 Dry Run Protection 5 4 3 4 Master Slave Function 2 3 pump only 5 5 Installation 5 1 Local 5 5 2 Hydraulic Connections 5 5 3 Electrical Conn...

Страница 3: ...entioned 2 2 Risks Incurred by Failure to Comply Failure to comply with the safety precautions could result in personal injury or damage to the pump or installation It could also invalidate any claims...

Страница 4: ...ows down to a complete stop 4 2 3 Automatic Mode 3 Pump Only All controls and settings on a 3 pump set are done via the Speedcentre controller Fig 3 and are communicated to the drives Settings can be...

Страница 5: ...below Fig 5 The incoming mains connection must comply with local regulations As a protection measure the booster must be earthed according to the regulations i e according to the local regulations an...

Страница 6: ...tions The full warranty document is downloadable at www wilo co uk click on local information then downloads Before requesting a site visit the following information must be available to the service t...

Страница 7: ...nic Control Drive Fig 3 Speedcentre 3 pump only Manual Mode Inverter On Green LED Automatic Mode Alarm Red LED Menu Pump Running Yellow LED Enter Pump in Automatic Mode Green LED Value Setting Up Valu...

Страница 8: ...8 Fig 5 1 Wiring Schematics 1 Pump System Fig 4 Pump Schematics...

Страница 9: ...9 Fig 5 2 Wiring Schematics 2 Pump System...

Страница 10: ...10 Fig 5 3 Wiring Schematics 3 Pump System...

Страница 11: ...running hours Hrs Pump Cycles Total number of pump cycles one cycle one run and stop Power On Number of times the drive has been powered on Max Pressure Maximum pressure of the installation Bar Short...

Страница 12: ...OVER T If the temperature is too high the controller will stop the motor from running Check that the water temperature does not exceed 40 C Check that the ambient temperature does not exceed 50 C E02...

Страница 13: ...Pumps not primed Check that the suction strainer does not let air in or the tank filling point is too close from the strainer A pump is obstructed by particles Have the pump dismantled and cleaned Vo...

Страница 14: ...V406 1 16 E KS 400 50 4193858 HELIX V408 1 16 E KS 400 50 4156034 HELIX V605 1 16 E KS 400 50 4156038 HELIX V608 1 25 E KS 400 50 4150543 HELIX V1004 1 16 E KS 400 50 4150546 HELIX V1006 1 16 E K 400...

Страница 15: ...netic Compatibility Directive WEEE Directive ROHS Directive As well as following harmonized standards If the above mentioned series are technically modified without our approval this declaration shall...

Страница 16: ...Wilo UK LTD Second Avenue Centrum 100 Burton on Trent Staffordshire DE14 2WJ T 44 0 1283 523000 E sales uk wilo com www wilo com gb en Copyright Wilo UK LTD 2020...

Отзывы: