Troubleshooting - Infrared Sensors
I� Faucet does not function (red light does not appear when user steps in front of sensor)
A�
No power to sensor. Make certain that power is on. Check transformer leads and connections.
Repair or replace as necessary�
B� Willoughby 700150 IR Sensor not operating� Replace Willoughby 700150 IR Sensor�
II� Faucet does not function (red light appears when user steps in front of sensor and solenoid
does not click)
A� Debris in solenoid; disassemble, clean, and flush�
B� Solenoid not wired correctly;
check solenoid connections.
C.
Solenoid problem; replace solenoid�
III�
No water when activated (valve clicks)
A�
Make certain that water is turned on.
B�
Valve clogged. Clean or replace filter.
IV� Very low flow or slow dribble
A�
Check supply stop(s); open if closed.
B� Debris in filter; remove, clean, and reinstall�
C.
Debris in aerator or spray head; remove, clean and reinstall�
D� Disassemble solenoid; clean and flush�
V�
Continues to run (with power
on and red light flashing)
A� Non-permanent target in range after user leaves� Remove non-permanent target� If this
target is a new permanent target (i�e�, a new wall or partition), turn off 24 volt power for
fifteen (15) seconds. Turn power back on and
let the sensor complete start-up mode�
B� Sensor failure; replace sensor�
VI�
Continues to run (ev
en with power disconnected)
A�
Solenoid valve installed backwards.
B�
Debris in solenoid, won’t close properly; re
move operator and clean� Reassemble in the
same manner�