18
FORSAIRE COUNTERFLOW DIRECT VENT GAS WALL HEATER
INSTALLING YOUR FURNACE
HELPFUL HINT
After wire nuts are screwed to wires, a small strip of
electrical tape can be applied over wire nut at its base and
onto wires to make a very solid connection.
GROUNDING
The appliance when installed must be electrically
grounded in accordance with local codes and ordinances
or in their absence, with National Electrical Code (ANSI/
NFPA 70) or Canadian Electrical Code (CSA C22.1) if an
external electrical source is utilized. This appliance is
equipped with three-prong (grounding) plug for your
protection against shock hazard and should be plugged
directly into a properly grounded three-prong receptacle.
Do not cut or remove the grounding prong from this plug.
A ground lug is installed for the ground connection. Use
a copper conductor (#AWG) from the unit to a grounded
connection in the electric service panel or a properly
driven and electrically grounded ground rod.
ELECTRICAL POWER SUPPLY
Remove three-prong (grounding) service cord from the
envelope parts package to be installed in the furnace.
Remove 7/8 inch diameter (22mm) knockout at the left or
right bottom side panel to route the three-prong service
cord to an electrical outlet.
1. Insert the nylon cap attached to the end of the three-
prong service cord thru the 7/8-inch diameter
knockout into the burner control assembly area and
insert it into the nylon plug attached to the outer
casing bottom. If desired, you may route the
thermostat wire alongside of the service cord and thru
the same opening or choose another entry into the
burner control assembly area.
2. Attach 7/8-inch diameter strain relief around the three-
prong service cord and thermostat wire (if thermostat
wire is routed thru the knockout). Insert the 7/8-inch
strain relief into the 7/8-inch hole in the side panel
of furnace.
REPLACEMENT PART LISTING:
DESCRIPTION
PART
NUMBER
Service
cord
P323335
WARNING:
Do not insert the three-prong
(grounding) service cord inside the burner control
assembly area more than 10 inches (245mm). This
could cause damage to the electrical cord resulting in
electrical shock hazard and/or fire.
A branch circuit including this furnace must not exceed 15
Amperes. Run a separate 115V, 60Hz. 15 Ampere circuit from
a separate circuit breaker or fuse in your service panel.
WALL THERMOSTAT WIRING
Run thermostat wire to the furnace. Connect thermostat
to the two wires marked “Thermostat” extending from
top of furnace, using two wire nuts provided. See Wiring
Diagrams on
Pages 28 and 29
. Refer to
Page 12, Figure 16
also.
Replace the fan to the original position on the motor shaft,
and tighten securely. Replace the fan shroud, making sure
it is centered vertically on the fan.
Tighten the screws securely.
Replace the top front panel and secure with thumbscrew.
COMPLETE WIRING DIAGRAMS ON PAGES 28 AND 29
.