background image

 

 

 

Servicing 

All servicing activities must be carried out by a qualified service technician or a service agency.  The home owner may not 
service the furnace. The home owner must read this section to be informed of the periodic maintenance and checks the 
required.  All servicing (except on vent system) must be carried out with the external casing removed.  After any servicing, the 
external casing must be reinstalled properly and the grounding wire of the external casing reconnected. 

 

Checking and Adjusting the Gas Manifold Pressure 

The furnace comes set from the factory at the correct HI and LO gas manifold pressures as shown in “Technical Data”.  It is 
recommended to check the pressures periodically (minimum once a year).  If adjustment is required, this can be done by 
adjusting screws “C” and “D”.  (Figure 8)   A test gauge must be connected as explained in “Checking the Gas Manifold 
Pressure”.   
 
Proceed as follows: 

1.  Place the furnace on and in the HI mode (knob in HI position). 

2.  Completely turn down screw "C" (HI - LO operator adjustment) by turning it clockwise.  Do not force. 

3.  Adjust the HI pressure by turning the screw D (pressure regulator) to the value given in the "Specifications" table.  Turn 

clockwise to increase the pressure, turn counterclockwise to decrease it. 

4.  Switch the furnace to LO mode (button MAX-MIN down). 

5.  Loosen screw "C" until the correct value for the LO pressure is achieved. 

6.  Switch the furnace between LO to HI mode to verify that both the HI and LO pressures are correct.  A tolerance of plus or 

minus 0.1 in. w.c. on the pressure value is acceptable. Readjust starting from point 1 if needed. 

7.  Disconnect the test gauge and firmly tighten the screw of the gauge connection.  Check for gas leaks with a soapy water 

solution and correct any leaks prior to operating the furnace. 

The HI and LO pressures must be adjusted as explained above.  Never try to adjust them independently from each other. 
 

Checking, Removing and Reassembling of the Vent Air Intake System 

It is essential that the vent air intake system is examined periodically (minimum once a year) to verify it is clean from dust and 
deposits of solid materials such as leaves or nests.  The vent air intake system is checked from outside.  Proceed as follows: 

1.  Remove the vent cap by removing the three outer screws.  (Figure 7). 

2.  Remove the inner flue pipe.  Do not use tools; the pipe can be extracted by hand. 

3.  Remove dust and deposits from the vent cap and flue pipes.  Deposits in the air pipe must be taken outside.  

Do not push 

them inside the furnace.

  The outer air pipe may not be removed from outside. 

4.  Check the O-ring gasket in the flue pipe.  If it is damaged in must be replaced (Part No. WFN-RNG003). 

5.  Reinstall the flue pipe from outside. Do not use glue or sealants. 

6.  Reinstall the vent cap on the flue pipe. Do not use glue or sealants. Tighten the three outer screws. 

 

Lubrication of Moving Parts

This furnace does not require lubrication.  Do not try to lubricate any part of the furnace such as motors bearings, keys, knobs, 
screws, etc. 
 

Flame Visual Check 

Correct and proper operation of the burner may be checked by examining the burner flame. Check the burner flame anytime the 
external casing is removed from the furnace.  The flame may be examined through the flame viewer. (Figure 8)  The flame must 
be stable and have blue color.  Some small yellow tips are acceptable with propane gas.  If the flame is yellow or has excessive 
turbulence, check the gas manifold pressure and the vent air intake system. If all these are acceptable, call a qualified service 
technician for a complete check of the furnace.  Call also your gas supplier to check the composition of the gas in use. 

15 

Содержание 2903511

Страница 1: ...losion may result causing property damage personal injury or loss of life Williams Furnace Co 250 West Laurel Street Colton CA 92324 U S A MODEL Natural Gas Only 2903512 MODEL Propane Gas Only 2903511...

Страница 2: ...d repair should be done by a QUALIFIED SERVICE TECHNICIAN The installation must conform to local codes or in the absence of local codes the installation must conform to the National Fuel Gas Code ANSI...

Страница 3: ...lified service technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water Safety Information for Users of LP Gas Propane LP Gas is a...

Страница 4: ...is a good safety measure under any condition If at any time you do not smell the LP Gas odorant and you should assume you have a leak Then take the same immediate action recommended above for the occa...

Страница 5: ...th CAN CSA C22 2 No 3 Installations in the State of Massachusetts All installations in the State of Massachusetts must use the following requirements when installing maintaining or operating direct ve...

Страница 6: ...ne of the terminal 18 inches 46 cm minimum E Clearance to unventilated soffit 12 inches 30 cm minimum clearance to vinyl soffit 36 inches 90 cm minimum F Clearance to outside corner 12 inches 30 cm mi...

Страница 7: ...ipe in the wall through the hole provided in the support bracket Place the round adhesive gasket around the hole so that the air pipe remains in its position 6 Attach the supporting bracket with the s...

Страница 8: ...ace 14 Position the vent cap and attach it with the screws Figure 7 15 Connect the female end of the three prong plug to the furnace connection on the bottom of the furnace 16 Connect the gas supply l...

Страница 9: ...s pressure and settings Minimum Burner Pressure Setting a Set LOW burner capacity by pressing button Z2 b Connect a micro manometer to the test gauge B Figure 8 c Rotate the internal screw D Figure 8...

Страница 10: ...he inlet pressure to the gas valve a plugged tapping accessible for test gauge connection is provided on the gas valve Figure 8 2 The appliance and its individual shutoff valve must be disconnected fr...

Страница 11: ...pressure must be checked both in Hi and Lo input The gas manifold pressure must be as shown in the Technical Data Differences of plus or minus 0 1 in w c are accepted If the Hi or Lo gas manifold pres...

Страница 12: ...SSURE SWITCH FLAME SENSOR SPARK IGNITER 2 pcs COMBUSTION BLOWER MOTOR FLAME VIEW LAMP GREEN LAMP SB TR Z1 Z2 Z3 Z8 Z9 L1 L2 GND LOCK OUT LAMP RED LAMP TRANSFORMER 120 24 V RESET AND SUMMER WINTER SWIT...

Страница 13: ...ot try to light any appliance Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neightbor s phone FOR YOUR SAFETY READ BEFORE OPERATING W...

Страница 14: ...rnace will operate in heating mode according to the thermostat and or clock s program When the button is down the appliance will provide ventilation MIN MAX BUTTON For faster heating keep this button...

Страница 15: ...solution and correct any leaks prior to operating the furnace The HI and LO pressures must be adjusted as explained above Never try to adjust them independently from each other Checking Removing and...

Страница 16: ...s 4 Check air flow switch 5 Clean and check exhaust flue pipe and air intake pipe 6 Check for gas leaks on all connections 7 Check and adjust gas pressure Check red O Ring Gasket NRNG003 If it is dama...

Страница 17: ...tion Programmable day blocks 1 2 3 4 5 Monday Friday 1 2 3 4 5 6 Monday Saturday 1 2 3 4 5 6 7 Monday Sunday 6 7 Saturday Sunday KEY A On Off Switch Pos I The appliance is controlled by the room therm...

Страница 18: ...7 Figure 10 D a triangular shaped indicator proceeds one day at a time Number 1 stands for Monday number 2 stands for Tuesday etc C To set the time press the Hour Selector button h Figure 10 E to set...

Страница 19: ...ght Press the Program Selector Figure 10 C button and select the program to be cancelled B Simultaneously press the Program Selector Figure 10 C and SKIP button Figure 10 G for at least 2 seconds The...

Страница 20: ...nd summer winter switch The switch is closed if there is no ignition block 4 Check Z2 Hi Lo flame and fan speed switch Button down Minimum velocity Button up Maximum velocity TROUBLESHOOTING STEP 2 Po...

Страница 21: ...wirings and connections If they are OK replace the thermostat STEP 4 8 Check Z9 Room thermostat Close the thermostat by a clockwise rotation 9 Check M1 Overheat thermostat automatic reset The thermos...

Страница 22: ...e the transformer Point 14 EV1 Valve closed during ignition Z2 down Check wirings connections and voltage If everything is OK replace the gas valve Point 15 RP7 No spark during ignition Check electrod...

Страница 23: ...inter Switch Part Number P332571 Z8 Z3 Timer and Manual Program Mode Switch Part Number P332570 Z2 Hi Lo Flame and Fan Speed Switch Part Number P332569 SF SB Green and Red Lamps Part Number P332538 P3...

Страница 24: ...ion Blower Motor Part Number P332514 M1 Overheat Thermostat Part Number P332522 M2 Fan Thermostat Part Number P332496 Fan Blades 4 pieces Part Number P332572 Left P332638 Right M Fan Motor 2 Pieces Pa...

Отзывы: