1.
Main functions:
Turn your device on and off at desired humidity
Settings are stored even when powered off.
Humidity calibration correction
High and low humidity alarm
2.
Specifications:
Max Load: 10A (1100W @110V or 2200W @220V)
Humidity Accuracy: 1%
Probe measurement range: 1%~100% RH
Working temperature for the controller: -40°F~176°F / -40°C ~ 80°C
Working humidity for the controller panel: less than 85%
Working mode: Humidification mode OR Dehumidification mode
Power supply: AC 110V ~ 240V, 50/60Hz
Power consumption: less than 3W
3.
Indicator Instruction:
4.
Key Operation Instruction
SET:
Press SET for 3 seconds to enter settings menu. In the settings menu, press SET once to enter a
parameter setting. After specifying a value for a parameter, press SET once to go back to the menu.
POWER:
In setting process (SET indicator is ON), press POWER once to save and quit setting. When it’s not
in working process (SET indicator is off), press POWER for 3 seconds to turn off the controller. Then press
POWER once again to turn it on.
UP/DOWN:
In setting process (SET indicator is on), press UP/DOWN to select parameter or adjust value of a
parameter.
Holding the button allows for rapid number adjustments.
Use UP/DOWN to check the Hb and Lb value. When it’s not in setting process (SET indicator is off), hold UP
to check Hb (Higher bound of your desired humidity range), hold DOWN to check Lb (Lower bound of your
desired humidity range).
Restore default setting:
When the controller is powered on, pressing POWER for 3 seconds to shut off the
controller. Then press POWER once to turn on the controller. When the screen displays 888s, press SET and
UP buttons at the same time until the display is back to normal reading. Then all settings will be restored to
default.
Alarm Switch:
The alarm function is disabled by default. It will be enabled if you specify a value for AL or
AH. After alarm sounds, press any of the buttons to disable the alarm.
Please note that in order to enable
the alarm function again, you need to cut off the power and turn on controller again.
SET indicator is on
In setting process
SET indicator is off
In control process
WORKING indicator is on Supplying output power
WORKING indicator is off No output power