background image

10

Front vent only

Front vent with 

dual top vents

Dual top vents

No front vent

Front vent with 

single top vent

Clean Face Option 

(See diagram on page 14)

The clean face option allows the elimination of the air inlet louver that is located directly below the doors in the unit 
face. Dual 8” flexible ducts are connected to the front side of the fireplace in the pre cut holes. The flexible duct 
may run up to 6’ down or to the side of the fireplace. This duct should never run upward. Use part #CFK, which 
includes all the parts necessary for this installation. This duct may be run down to the ceiling of a lower area to 
enhance circulation of air within the home. When creating a clean face installation, the dual top vent (part #TVK) 
must also be ordered to complete the installation. The minimum interior chase framing should be 66” wide if the 
flexible ducting is routed within the chase. A blower is available to boost air circulation with the clean face option. 
It is a variable speed, 210 CFM, 8” round, inline blower. This blower should be located directly behind the inlet vent 
housing and attached to the flexible plastic duct. Make sure this blower is accessible for service in your installation. 

Facing

Combustible material may be installed flush to the exterior sides of the fireplace face leaving a 3/8” gap. It may 
not project in front of or over the steel fireplace face. A 4” piece of Micore, which is provided, must cover the area 
directly above the top of the unit to the header. 

Non-combustible materials may be placed across the face of the fireplace such as brick, stone or tile. Facing kits are 
available from your dealer to attach manufactured stone or brick to the face of the fireplace. See your dealer for the 
appropriate one.

To use a manufactured facing product, attach one of the facing kits to the framing structure surrounding the 
fireplace. Do not securely attach this to the fireplace face as cracking of the mortar may occur due to thermal 
expansion of the steel during operation. Self-tapping metal screws may be used to attach the facing kit in several 
areas of the steel front taking care not to tighten the screws.

Содержание The GranView

Страница 1: ...Installation and Operation Instructions Keep these instructions for future use GranView Clean Burning Zero Clearance Fireplace The 800 367 7976 wilkeningfireplace com 9608 State 371 NW Walker MN 5648...

Страница 2: ...Home Installation Requirements 8 Doors for the GranView 9 Heated Air Ducting Options 9 Clean Face Kit 10 Facing 10 Blower Installation and Electric Wiring Diagram 11 Unit Diagrams 12 15 Installing th...

Страница 3: ...er gas logs gas starters or flame colorants Do not use coal or charcoal in this fireplace unit 6 Do not connect this appliance to a chimney flue that is serving another appliance 7 Never use gasoline...

Страница 4: ...e stop spacer and roof flashings may be placed directly on or next to normal construction materials The minimum recommended interior chase width is 55 The minimum chase depth is 24 The interior chase...

Страница 5: ...ducting of heated air Raised hearths must extend 16 in front of and 8 to each side of the fireplace opening Floor level hearths may have a minimum of a 16 noncombustible protrusion but 20 is recommen...

Страница 6: ...is employed Install and seal a storm collar to the section of chimney penetrating the flashing to prevent moisture from entering the chimney structure The roof penetration must meet the minimum cleara...

Страница 7: ...This is done to reduce the chance of smoke migrating from one chimney to the other The Chase Enclosure The chase is a framed structure created to encase the fireplace and chimney system A chase should...

Страница 8: ...h material to be installed on Use the Micore board provided to protect a raised combustible hearth structure or combustibles located below the finished hearth for floor level installations Any part of...

Страница 9: ...Co must be used for all top vent applications A minimum clearance of 6 must remain between the top of the top vent assembly and the finished ceiling The bottom of the top vent must be a minimum of 6 a...

Страница 10: ...variable speed 210 CFM 8 round inline blower This blower should be located directly behind the inlet vent housing and attached to the flexible plastic duct Make sure this blower is accessible for serv...

Страница 11: ...is mounted to the base of the fireplace at center 4 behind the lower grill using the wing nuts provided in the blower kit The blower assembly has two predrilled holes in the plate that slide over the...

Страница 12: ...5 to standoffs 43 unit face 1 4 3 18 11 3 16 48 50 5 37 4 2 Top standoff 24 to standoff 8 13 21 8 13 Side standoff 4 air supply 8 clean face inlet 9 14 7 12 9 18 7 4 Side standoff 4 heat duct connecti...

Страница 13: ...s Shown with optional top vent framing Finished frame opening 45 6 minimum to louver 11 11 Louver 55 Interior chase width recommended Outside air vent Create S trap Side mantel leg trim 16 6 16 8 2x4...

Страница 14: ...nts can go to front side or back of the fireplace chase Top vent kit 12 minimum if vents are installed in hearth Upper steel baffle with holes Baffle support tabs Baffle 7 Air tubes Angle refractory p...

Страница 15: ...add 5 to total width for this upstairs fireplace If ducting to the left no additional width is required 17 inch offset shown 12 raised hearth shown 12 raised hearth shown 30 degree no offset support...

Страница 16: ...onnect them on the top center edge Place the four side pieces in place part 4 start by sliding the front ones in position before each back one Place the refractory panel part 5 over the top edge of th...

Страница 17: ...added to the installation do so now see page 11 for the on board blower Reinstall the lower grill 8 Install the doors See page 9 9 Finish facing of the fireplace and hearth area See page 10 11 10 Ins...

Страница 18: ...ed position Verify that the doors are fully closed summon the fire department alert your family of the possible danger and evacuate the premises A chimney fire is a serious condition that may result i...

Страница 19: ...ill exhaust the fire and create a buildup of gasses in the combustion chamber Front Clearance Keep any combustible materials at least 3 feet away from the front of this fireplace This includes furnitu...

Страница 20: ...nual inspection before the first fire of the year to verify that all components are working properly and that the chimney is ready for use We recommend contacting a Certified Chimney Sweep or your dea...

Страница 21: ...me With the advent of tighter homes it has become apparent that the lower levels of these homes will have a lower pressure level than the upper areas This is caused by the stack effect of the house th...

Страница 22: ...lure to use or install this fireplace as stated in this manual will void all warranties and may create a dangerous condition which may result in loss of property or life Never plug the outside air sup...

Страница 23: ...cludes enough for entire door assembly GVDGK Glass Panel for Rectangular Tudor GVRCGTD Glass Panel for Arched Tudor GVACGTD Glass Panel for Rectangular Single Door GVRCGSD Removable Log Retainer GVLR...

Страница 24: ...Wilkening Fireplace Co Walker Minnesota Visit our website at wilkeningfireplace com...

Отзывы: