User manual 5.14 - OR4 basic / OR4 pro (C6584.005.038-09)

Order data

Smoke detector OR4 basic/OR4 pro

Issue 2021-12

Subject to error/change

4.3 

Specification text 

4.3.1  OR4 basic

Smoke detector with general type approval for activation and tripping of fire dampers 

and smoke protection dampers. Smoke detector for detection of smoke in ventilation 

ducts, for activation of fans and for transmitting signals to fire alarm systems or the 

building management system. Casing with flow insert and protective screen. Smoke switch 

and analysis electronics with floating relay outputs. Additional input without galvanic 

isolation. Smoke switch with automatic tracking of the response threshold in order 

to achieve a long service life. Removable without using tools for straightforward 

inspection and cleaning. Button for function test and for resetting after smoke 

detection. LEDs for visualisation of operating statuses and the soiling of the smoke 

switch as a percentage in multiple stages. Alarms and faults saved in case of power 

failure.
Suitable for installation at a short distance from disruption points (1.5 x hydraulic 

diameter). Installation not dependent on position or direction of air flow in 

rectangular ventilation ducts with an edge length of 100 mm or more and in ventilation 

pipes with a diameter of 100 mm or more.

.....  pcs.   

Supply voltage:    

230 V AC / 24 V AC/DC

 

 

 

Manufacturer:  

 

WILDEBOER

 

 

 

Type/series:  

 

OR4 basic

 

 

 

VdS approval: 

 

G221008

4.3.2  OR4 pro

Smoke detector with general type approval for activation and tripping of fire dampers 

and smoke protection dampers. Smoke detector for detection of smoke in ventilation 

ducts, for activation of fans and for transmitting signals to fire alarm systems or the 

building management system. Casing with flow insert, protective screen and integrated 

flow sensor for flow monitoring. Smoke switch and analysis electronics with galvanically 

isolated and floating inputs and outputs. Smoke switch with automatic tracking of the 

response threshold in order to achieve a long service life. Removable without using 

tools for straightforward inspection and cleaning. Button for function test and for 

resetting after smoke detection. LEDs for visualisation of operating statuses and the 

soiling of the smoke switch as a percentage in multiple stages. LCD display screen 

for diagnostics, display and setting of all operating parameters. With galvanically 

isolated RS485 interface (protocols: BACnet, Modbus) for connection to GLT.
Suitable for installation at a short distance from disruption points (1.5 x hydraulic 

diameter). Installation not dependent on position or direction of air flow in 

rectangular ventilation ducts with an edge length of 100 mm or more and in ventilation 

pipes with a diameter of 100 mm or more.

.....  pcs.   

Supply voltage:    

230 V AC / 24 V AC/DC

 

 

 

Manufacturer:  

 

WILDEBOER

 

 

 

Type/series:  

 

OR4 pro

 

 

 

VdS approval: 

 

G221008

Содержание OR4 basic

Страница 1: ...OR4 basic OR4 pro WILDEBOER BAUTEILE GMBH Issue 2021 12 Smoke detector according to DIN EN 54 27 with VdS recognition and DIBt approval Z 78 6 250 USER MANUAL 5 14 ...

Страница 2: ...reas of application for smoke detectors Smoke detector As per DIN EN 54 27 with VdS approval Smoke detectors As per DIN EN 54 27 with VdS and DIBt German Institute for Construction Engineering approval In this document RL4 basic RL4 pro OR4 basic OR4 pro OR32 INFO ERROR RUN TEST RESET INFO ERROR RUN OK INFO ERROR RUN TEST RESET INFO ERROR RUN OK Area of application For detection of smoke in ventil...

Страница 3: ...or quick accessibility and functional test without use of tools Integrated flow monitoring Enclosed casing for electronics Replaceable protective screen for protection from soiling RM4 smoke switch with automatic tracking of the response threshold for longer service life LEDs LCD display screen for visualisation of operating statuses soiling and setting operating parameters TEST locally or using t...

Страница 4: ...utomatic alarm threshold tracking for extended service life 3 Flow insert OR4 basic For optimum flow through of the smoke switch OR4 pro For optimum flow through of the smoke switch with integrated flow sensor 4 Protective screen For protection of the smoke switch from coarse soiling 5 Protective film For protection of the smoke switch and the protective screen from soiling during the construction...

Страница 5: ...ternal normally open contact for Reset Test 2 x semiconductor input for external normally open contact for Reset Test for flow sensor On Off Specification 24 V DC SELV 11 mA EN 61131 2 type 1 Signal voltage 0 0 5 V DC SELV Signal voltage 1 15 30 V DC SELV Galvanically isolated Yes potential group GLT interface outputs OR4 basic OR4 pro Quantity 1 x changeover contact relay Soiling display at 70 6 ...

Страница 6: ...Installation 3 1 Installation details The OR4 can be installed with any alignment in ventilation ducts regardless of the direction of air flow horizontally vertically or at an angle The continual through flow and thus effective smoke detection must be guaranteed in the process The corner area on rectangular ventilation ducts must not be used for installation INFO ERROR RUN OK INFO ERROR RUN OK INF...

Страница 7: ...on socket to the saddle pipe aligning the installation socket to the direction of the air in the process Prick the saddle pipe slightly with the retaining screw and pre drill it without the installation socket Ø 3 mm Then fit the installation socket again and secure it with screws Apply sealant provided by the user to the saddle socket so that it is airtight INFO ERROR RUN OK Insert the saddle pip...

Страница 8: ... K drill ing tem plat e for mou ntin g soc ket R K Art N r B750 0 090 006 00 ww w w ild eb oe r de Measure the centre point of the installation opening and stick on the drilling template Drill the fastening holes for installation of the installation socket 3 3 mm Create the installation opening for the installation socket Ø 94 98 mm INFO ERROR RUN OK Insert the installation socket into the install...

Страница 9: ...uired inner installation dimension For activation of fire dampers and smoke protection dampers for ventilation ducts For monitoring ventilation duct in conjunction with a fire detection system or the building management system For activation of fans Alarms and faults saved in case of power failure DIBt approval Z 78 6 250 VdS approval G 221008 Equipment variant Optional basic OR4 basic variant pro...

Страница 10: ... ORSTU18 DN 200 ORSTU20 DN 224 ORSTU22 DN 250 ORSTU25 DN 280 ORSTU28 DN 315 ORSTU31 DN 355 ORSTU35 DN 400 ORSTU40 DN 450 ORSTU45 DN 500 ORSTU50 DN 560 ORSTU56 DN 630 ORSTU63 DN 710 ORSTU71 DN 800 ORSTU80 4 x sealing cover for installation socket ZUB 0475 4 2 Spare parts Illustration Description Order data 1 x RM4 smoke switch ZUB 0471 20 x protective screen ZUB 0470 2 x R K installation socket ZUB...

Страница 11: ... more pcs Supply voltage 230 V AC 24 V AC DC Manufacturer WILDEBOER Type series OR4 basic VdS approval G221008 4 3 2 OR4 pro Smoke detector with general type approval for activation and tripping of fire dampers and smoke protection dampers Smoke detector for detection of smoke in ventilation ducts for activation of fans and for transmitting signals to fire alarm systems or the building management ...

Страница 12: ...gnal OR4 basic OR4 pro 1 3 L 2 4 N GND 2 Alarm interface Connection Signal OR4 basic OR4 pro 1 6 L 2 7 N GND 3 8 ALARM NO 4 9 ALARM NC 5 10 N GND 3 GLT interface Connection Signal OR4 basic OR4 pro 1 2 RM4 70 soiled NO GND 3 RM4 70 soiled NC Warning 4 RESET 3 sec TEST 3 sec Alarm fault 5 Flow present 6 Ready for operation 7 RM4 70 99 soiled 8 RM4 100 soiled 9 RESET 3 sec TEST 3 sec 10 Activate flo...

Страница 13: ...or input Specification Semiconductor 24 V DC SELV 11 mA EN61131 2 type 1 Galvanic isolation Potential group isolated from the analysis electronics Signal voltage 0 0 5 V DC SELV Signal voltage 1 15 30 V DC SELV GLT interface outputs OR4 basic OR4 pro Quantity 1 x changeover contact relay 6 x semiconductor outputs Specification EN61131 2 Galvanic isolation Yes Potential group isolated from the anal...

Страница 14: ...Page 14 16 User manual 5 14 OR4 basic OR4 pro C6584 005 038 09 Annex Smoke detector OR4 basic OR4 pro Issue 2021 12 Subject to error change Notes ...

Страница 15: ...Page 15 16 User manual 5 14 OR4 basic OR4 pro C6584 005 038 09 Annex Smoke detector OR4 basic OR4 pro Issue 2021 12 Subject to error change Notes ...

Страница 16: ...l info ulm wildeboer de Internet www wildeboer de Utrecht office Telephone 31 30 767 0150 E mail info utrecht wildeboer eu Internet www wildeboer de nl Factory administration Telephone 49 4951 950 0 E mail info wildeboer de Internet www wildeboer de HAMBURG HANNOVER BERLIN LEIPZIG FRANKFURT COLOGNE STUTTGART ULM MUNICH MAKE USE OF OUR STRENGTHS UTRECHT WEENER EMS ...

Отзывы: