background image

}

User Manual 5.02 (2016-10) 5

Subject to change

Series FK120

Option:

 

Electric spring return actuator

  

 

 

with 70°C release element and terminal box.

 

EM-1 

10 Nm

 

EM-2 

15 Nm

 RM-1 

10 Nm

 

Power consumption up to 20 W including heating;  

I

rated

 

 

0.7 A; I

max 

 

1 ms

 

 2.5 A

 

Runtime: Opening 

 

30 s, closing 

 

10 s.

 

CLOSED and OPEN position indicators via limit swit

-

ches for 

 3 A at 24 V AC/DC and 

 0.25 A at 250 V 

 

AC/DC; at least 5 V, 10 mA.

 

The 12 x 0.5 mm² halogen-free connection cable must be wired 

in the terminal box! All of the contained voltages must be the 

same!

Option:

 

Electric spring return actuator

  

 

with 70°C release element; IP54.

 

M220-7

  230 V AC; 7 VA/6 W; I

max 

 10 ms

 = 0.15 A.

 M24-7

  24 V AC/DC; 7 VA/5 W; I

max 

 5 ms

 = 5.8 A.

 

Runtime: Opening 40 to 75 s, closing 

≈ 

20 s.

 

CLOSED/OPEN position indicators via limit switches 

for 0.5 A at 

 250 V AC or for 1 mA up to 3 A at 5 up to 

250 V DC.

 

Halogen-free connection cable; 1 m long; 2 x 0.75 mm² 

and 6 x 0.75 mm². The AMP connector plugs are 

detachable.

Option: 

with 95°C release element.

Enclosed 

release element

The actuators can be rotated into suspen

-

ded and vertical positions on site.

Terminal box

FK90 fire dampers

Release mechanisms and actuators (2)

Thermal-mechanical release mechanism 

 

with 70°C release element.

Option:

   with coated 70°C release element.

Option:

  with 

explosion-protected limit switch

 

E-Ex

  with normally open contact and normally closed  

 

contact for 6 A at 

 

 250 V AC  

 

 

 

or 0.25 A at 

 230 V DC; IP65;  

 

 

 

2 m connection cable 4 x 0.75 mm².

 

One or two can be attached for the CLOSED and/or OPEN 

position indicator.

- designs

Building area

 where a dangerous, potentially explo

-

sive atmosphere may occur in normal operation...

... as a mixture of air and combustible gases, mists or vapours...

... in the form of a cloud of combustible dust contained in the air...

... occasionally

... temporarily or not at all.

... occasionally

... temporarily or not at all.

Zone

1

2

21

22

Identification of the fire damper

II 2 G c IIc T6/T5

II 3 G c IIc T6/T5

II -/2 D c T80°C/T95°C

II -/3 D c T80°C/T95°C

Thermal-mechanical release mechanism

 with or 

without 

explosion-protected limit switch

X

X *

)

X

X *

)

Motor drive

EM-1

 or

 EM-2

X

X *

)

X

X *

)

RM-1

-

X

-

X

   Ambient temperatures: -20°C … +40°C for T6 and T80°C/-20°C … +50°C for T5 and T95°C                                                                                                   *

)

 Can also be used in this zone!

24 to 240 V AC/DC; IP66.

Use of explosion-protected designs

Enclosed 

release element

Enclosed 

relea-

se element

Содержание FK90

Страница 1: ...series FK120 Heights up to 1000 mm Fire resistance period up to 120 minutes Fire classification EI 30 60 90 120 ve ho i o S C10ooo Hygiene certificate Environmental Product Declaration according to IS...

Страница 2: ...arge free cross section Maximum volume flows Minimum pressure drop Extremely low sound power level Connection holes for profiles from 20 mm in height Two control openings inspection openings for viewi...

Страница 3: ...tability free dom of damper blade movement minimum pressure drop and low noise level Option Casing with epoxy resin powder coating Replaceable damper blade made of high temperature re sistant corrosio...

Страница 4: ...ld smoke extraction are country specific Electric spring return actuators also close the fire dampers if the supply voltage is interrupted They reopen the fire dampers as soon as the voltage is presen...

Страница 5: ...n ded and vertical positions on site Terminal box FK90 fire dampers Release mechanisms and actuators 2 Thermal mechanical release mechanism with 70 C release element Option with coated 70 C release el...

Страница 6: ...ocations must not be changed on site H J3 K K400 K500 200 170 225 160 250 145 275 135 4 300 120 17 325 110 29 350 95 42 375 85 54 400 70 67 450 45 92 500 20 117 17 550 142 42 600 7 167 67 650 32 192 9...

Страница 7: ...637 0 684 0 780 0 876 1050 0 117 0 142 0 167 0 192 0 217 0 268 0 318 0 368 0 418 0 469 0 519 0 569 0 620 0 670 0 720 1100 0 122 0 149 0 175 0 202 0 228 0 281 0 334 0 386 0 439 0 492 0 545 0 598 0 650...

Страница 8: ...m m 0 0 5 1 B 1 2 0 0 M e t a l d a m p e r b l a d e B 1 5 0 0 m m 1 4 0 0 v 12 m s A Volume flow m h v 12 m s A Operating pressure User Manual 5 0 2 2016 10 8 Subject to change Series FK120 FK90 fir...

Страница 9: ...400 800 500 600 Width B mm 200 250 300 350 400 500 600 700 800 Height H mm Volume flow V m h 225 275 200 300 400 600 800 1000 2000 3000 4000 6000 8000 10000 20000 30000 40000 50000 150 900 1000 900 10...

Страница 10: ...Afree 0 098 m Dps 29 Pa vA 7 4 m s LWA 47 dB A Sound power level LW Oct for the octave mid frequencies f Hz 63 125 250 500 1000 2000 4000 8000 LWA dB A 47 47 47 47 47 47 47 47 DL7 4 m s dB 5 6 1 3 6...

Страница 11: ...always located to the H side on the casing of the fire dampers see page 6 FK90 fire dampers Installation in rigid walls and ceilings and in metal stud walls 1 with cladding on both sides The fire damp...

Страница 12: ...rete in solid construction Rigid walls and ceilings must have bulk density 450 kg m Metal stud walls should be clad on both sides in two or more layers with 12 5 mm GKF plasterboard Installation openi...

Страница 13: ...nd tested periodically to ensure they are functioning correctly The intervals largely depend on the system operation Rele vant regulations should be followed FK90 fire dampers series FK120 are mainten...

Страница 14: ...Option Explosion protected limit switch EX CLOSED EX OPEN Option Electric actuators M220 9 V M24 9 V M220 7 M24 7 Option Electric explosion protected actuators EM 1 RM 1 EM 2 see pages 5 and 6 FK90 f...

Страница 15: ...metal stud walls Enclosed maintenance free thermal release mechanism 70C 95 C or 100 C for manual single handed operation corrosion resistant release element with two electrical limit switch es for s...

Страница 16: ...nventional control systems in buildings is complex Special plug and play functionality allows control systems for fire dampers to be designed built and connected in parent hierarchy without any measur...

Отзывы: