background image

Blind cap

E-CLOSED

Release mechanism

(always fitted on the H-side)

Control openings

(inspection openings)

No spacing required

Visible side

Visible side

Visible side

Visible side

User Manual 5.02 (2016-10) 11

Subject to change

Series FK120

Actuator on the left

Horizontal damper blade axle

Actuator below

Actuator on the right

Actuator above

Actuator underneath the ceiling

Actuator above the ceiling

Vertical damper blade axle

Horizontal damper blade axle

Vertical installation positions

Operation side

Non-operation side

Operation side

Non-operation side

The release mechanisms and actuators are always located to the H-side on the casing of the fire dampers  

⇒ 

 see page 6

FK90 fire dampers 

Installation in rigid walls and ceilings and in metal stud walls (1) with cladding on both sides

The fire dampers are

EI 30/60/90/120 (v

e

- h

o

, i 

 o) S C

10ooo

classified and labelled.

 

The effective fire resistance period is 

 

dependent on the installation. 

Minimum thicknesses W, D [mm]

 are required:

All dimensions in mm

Fire resistance period in 

minutes

30

60

90

120

Rigid walls

100

100

Rigid ceilings

•  

with H ≤ 800 and B ≤ 1500

100

115

Rigid ceilings

•  

with H > 800 and B ≤ 1000

115

Metal stud walls

with 

≤ 

1000 mm stud spacing

95

95

Horizontal installation positions

The drive positions of right, left, up and down all relate to the visible side.

Typical installation with mortar

 

in masonry walls. 

"Flange-to-flange" installation.

Содержание FK90

Страница 1: ...series FK120 Heights up to 1000 mm Fire resistance period up to 120 minutes Fire classification EI 30 60 90 120 ve ho i o S C10ooo Hygiene certificate Environmental Product Declaration according to IS...

Страница 2: ...arge free cross section Maximum volume flows Minimum pressure drop Extremely low sound power level Connection holes for profiles from 20 mm in height Two control openings inspection openings for viewi...

Страница 3: ...tability free dom of damper blade movement minimum pressure drop and low noise level Option Casing with epoxy resin powder coating Replaceable damper blade made of high temperature re sistant corrosio...

Страница 4: ...ld smoke extraction are country specific Electric spring return actuators also close the fire dampers if the supply voltage is interrupted They reopen the fire dampers as soon as the voltage is presen...

Страница 5: ...n ded and vertical positions on site Terminal box FK90 fire dampers Release mechanisms and actuators 2 Thermal mechanical release mechanism with 70 C release element Option with coated 70 C release el...

Страница 6: ...ocations must not be changed on site H J3 K K400 K500 200 170 225 160 250 145 275 135 4 300 120 17 325 110 29 350 95 42 375 85 54 400 70 67 450 45 92 500 20 117 17 550 142 42 600 7 167 67 650 32 192 9...

Страница 7: ...637 0 684 0 780 0 876 1050 0 117 0 142 0 167 0 192 0 217 0 268 0 318 0 368 0 418 0 469 0 519 0 569 0 620 0 670 0 720 1100 0 122 0 149 0 175 0 202 0 228 0 281 0 334 0 386 0 439 0 492 0 545 0 598 0 650...

Страница 8: ...m m 0 0 5 1 B 1 2 0 0 M e t a l d a m p e r b l a d e B 1 5 0 0 m m 1 4 0 0 v 12 m s A Volume flow m h v 12 m s A Operating pressure User Manual 5 0 2 2016 10 8 Subject to change Series FK120 FK90 fir...

Страница 9: ...400 800 500 600 Width B mm 200 250 300 350 400 500 600 700 800 Height H mm Volume flow V m h 225 275 200 300 400 600 800 1000 2000 3000 4000 6000 8000 10000 20000 30000 40000 50000 150 900 1000 900 10...

Страница 10: ...Afree 0 098 m Dps 29 Pa vA 7 4 m s LWA 47 dB A Sound power level LW Oct for the octave mid frequencies f Hz 63 125 250 500 1000 2000 4000 8000 LWA dB A 47 47 47 47 47 47 47 47 DL7 4 m s dB 5 6 1 3 6...

Страница 11: ...always located to the H side on the casing of the fire dampers see page 6 FK90 fire dampers Installation in rigid walls and ceilings and in metal stud walls 1 with cladding on both sides The fire damp...

Страница 12: ...rete in solid construction Rigid walls and ceilings must have bulk density 450 kg m Metal stud walls should be clad on both sides in two or more layers with 12 5 mm GKF plasterboard Installation openi...

Страница 13: ...nd tested periodically to ensure they are functioning correctly The intervals largely depend on the system operation Rele vant regulations should be followed FK90 fire dampers series FK120 are mainten...

Страница 14: ...Option Explosion protected limit switch EX CLOSED EX OPEN Option Electric actuators M220 9 V M24 9 V M220 7 M24 7 Option Electric explosion protected actuators EM 1 RM 1 EM 2 see pages 5 and 6 FK90 f...

Страница 15: ...metal stud walls Enclosed maintenance free thermal release mechanism 70C 95 C or 100 C for manual single handed operation corrosion resistant release element with two electrical limit switch es for s...

Страница 16: ...nventional control systems in buildings is complex Special plug and play functionality allows control systems for fire dampers to be designed built and connected in parent hierarchy without any measur...

Отзывы: