WIKA WMI Series Скачать руководство пользователя страница 5

 

 

                                                                

 

 
 
Install 

WIKA 

WMI

 

Series Magnetic Level Indicators 

according to the type connection ordered.  Ensure all 

gaskets or sealants are in place, and then tighten all fasteners to the proper torque.  For wiring instructions of a 
transmitter or switch unit, refer to the installation manual for that device.  If no manual is available or is missing, 
please contact the factory for a replacement copy. 
 

IMPORTANT! 

 
Once the level gauge is attached to the application and the vent and drain connections are confirmed to be closed, 
utilize the following 

procedure for start up

, ESPECIALLY FOR 

HIGH PRESSURE

 AND TEMPERATURE 

APPLICATIONS! 
 
1.

 

Slowly open the top Valve first.  This will allow for equalization of pressure in the chamber to the process. 

2.

 

Slowly open the bottom Valve.  Liquid can now fill the chamber gradually. 

 

Failure to follow this procedure can lead to damage of the float! 

 
The tank level should be raised to maximum height to check the upper connection for leaks.  If applicable, verify 
that all switch operation is correct and that the transmitter indicates the correct level. 
 

WARNING 

 

Once the pressure in the Gauge Chamber has been equalized with the process pressure, DO NOT open 

the vent or drain connections.  Damage to the float can occur! 

 
See the section entitled “Maintenance” to learn the proper procedure for removing this instrument from service. 

 

Functional Test 

 

The best way to provide a functional test for this instrument is to raise and lower the level of the material in the 
tank, and, therefore, the gauge.  Many times this is not possible.  If this is the case, utilize one of the following 
options. 
 
1.

 

Make sure the chamber is isolated from process conditions by closing the valves at the connection points. Drain 
off any remaining liquid in a manner compatible with plant requirements.  As most floats will be buoyant upon 
water, slowly fill the level gauge through the vent connection.  Observe the movement of the visual indicator as 
the gauge fills with water.  If applicable, monitor the outputs of switches and transmitters accompanying this 
instrument. 

2.

 

If it is not possible to fill the gauge with water or another liquid, either open the drain connection or remove the 
bottom flange.  Carefully manipulate the float with a piece of instrument tubing or a device that affects the 
movement of the float in the chamber.  Observe the movement of the visual indicator as the float moves.  If 
applicable, monitor the outputs of switches and transmitters accompanying this instrument. 

3.

 

Often times there will not be enough ground clearance to insert an object to manipulate the float.  If this is the 
case, such a test can be completed prior to installation while the instrument is lying on the floor. 

 

Содержание WMI Series

Страница 1: ...NSTALLATION AND OPERATION MANUAL WIKA WMI Series Magnetic Level Indicator Please retain for future usage Contact WIKA Instrument Corporation 950 Hall Court Deer Park TX 77536 www wika com 1 800 570 4454 ...

Страница 2: ...e measured As the liquid level increases and decreases in the chamber the float rises and falls with the liquid level This float contains a magnet assembly The force or flux of the magnet assembly contained in the float affects a visual indicator mounted outside of and isolated from the float chamber This same magnetic force can also affect optional switches or transmitters mounted outside of the ...

Страница 3: ...he shipping container carefully inspect each instrument to ensure that it has arrived complete and ready for installation Note that the process conditions are listed on the tag mounted at the base of the indicator assembly Make sure that these process conditions match the application for which this gauge is designed Should there be damage to The WMI Series Magnetic Level Indicator try to take digi...

Страница 4: ...on valves between the Level Gauge and the process tank This will allow for gradual pressurization of the Level Gauge chamber as well as facilitate any future maintenance necessary The gauge should be mounted level to ensure proper float travel without friction The WIKA WMI Series Magnetic Level Indicator arrives complete with the float installed No further assembly should be required Included with...

Страница 5: ...ction entitled Maintenance to learn the proper procedure for removing this instrument from service Functional Test The best way to provide a functional test for this instrument is to raise and lower the level of the material in the tank and therefore the gauge Many times this is not possible If this is the case utilize one of the following options 1 Make sure the chamber is isolated from process c...

Страница 6: ...the gauge Caution Take care to not allow the float to drop on the floor This can cause damage to the float and or the magnet assembly 5 Clean out chamber with a brush and wash with water if compatible Make sure there are no remaining solid particles Look for items or debris that will inhibit the movement of the float Further inspect the gauge chamber to ensure that it is free from unexpected corro...

Страница 7: ...f its use Seller makes no warranties as to the equipment manufactured by it which extend beyond the description of such equipment on the face hereof WIKA Instruments Corporation s obligation to correct defects in such equipment by repair or replacement in accordance with the foregoing provisions is in lieu of any other warranties expressed or implied as to such equipment WIKA Instruments Corporati...

Отзывы: