WIKA operating instructions model TFS135
8. Specifications
8. Specifications
Specifications
Temperature ranges
Nominal Switching
Temperature (NST)
50 ... 130 °C
Note:
The nominal switching temperature can be
selected in steps of 5 K. It is preset on delivery and
cannot be changed.
Switch point accuracy
±5 K
Reset Switching
Temperature (RST)
Typically 15 ... 40 K below the switching
temperature
To ensure a safe reset of the switch at low
switching temperatures, care must be taken
that the temperature difference between the
measuring point and environment is high
enough; since otherwise the switch cannot cool
back down to the reset switching temperature
and thus the instrument will not be able to
return to its normal state.
Ambient temperature
The maximum permissible ambient temperature
depends on the electrical connection.
Note:
Due to short installation length there is a risk that
the temperature at the connector will rise up to an
inadmissibly high value. This absolutely must be
taken into account when designing the measuring
point. The temperature at the connector must not
exceed the above mentioned temperature range.
- Rectangular connector
per EN 175301-803
-30 ... +85 °C
- Circular connector
M12 x 1
-25 ... +55 °C
Operating pressure
Max. 50 bar
Содержание TFS135
Страница 22: ...EN 14216392 02 11 2019 EN DE FR 22 WIKA operating instructions model TFS135...
Страница 42: ...DE 14216392 02 11 2019 EN DE FR 42 WIKA Betriebsanleitung Typ TFS135...
Страница 62: ...14216392 02 11 2019 EN DE FR 62 WIKA operating instructions model TFS135...
Страница 63: ...WIKA operating instructions model TFS135 14216392 02 11 2019 EN DE FR 63...