Additional operating instructions TC82, TC83, intrinsically safe designs (Ex i)

8

3. Commissioning, operation

DANGER!

Danger to life from explosion

Through working in flammable atmospheres, there is a risk of explosion which 

can cause death.

 

Only carry out set-up work in non-hazardous environments!

 

Do not open the instrument while under voltage.

DANGER!

Danger to life from explosion

By using a measuring insert without a suitable connection head (case), an 

explosion risk occurs which can cause fatalities.

 

Only use the measuring insert in the connection head designed for it.

DANGER!

Danger to life due to loss of explosion protection

If the corresponding tightening torques are not observed, this can lead to a 

loss of the explosion protection.

 

Ensure the tightening torques in accordance with chapter 3.2.

WARNING!

Damage to the measuring instrument by operation outside the upper or 

lower limits of the operating temperature

Failure to observe the permissible operating temperature, also taking into 

account convection and radiation, can even cause damage to the thermometer 

during mounting.

 

The upper and lower limits of the specified operating temperature range 

must not be exceeded.

WARNING!

Potential electrostatic charging hazard

There is a risk of electrostatic discharges for group IIIC EPL Db.

 

For application in areas requiring EPL Db equipment and in areas with 

high or repeated charging processes, special protective measures must be 

taken.

Observe the special conditions (see chapter 4 “Special conditions for use (X conditions)”).

3. Commissioning, operation

Содержание TC82

Страница 1: ...tz Betriebsanleitung Additional operating instructions for hazardous areas Ex i Models TC82 TC83 Zusatz Betriebsanleitung f r explosionsgef hrdete Bereiche Ex i Typen TC82 TC83 BVS 20 ATEX E 044 X IEC...

Страница 2: ...WIKA is a registered trademark in various countries WIKA ist eine gesch tzte Marke in verschiedenen L ndern Prior to starting any work read the operating instructions Keep for later use Vor Beginn all...

Страница 3: ...y safe designs Ex i 3 Contents Contents Declarations of conformity can be found online at www wika com 1 Ex marking 4 2 Safety 6 3 Commissioning operation 8 4 Special conditions for use X conditions 1...

Страница 4: ...sure Ui DC 30 V Ii 110 mA Pi 500 mW Li Ci negligible 40 85 C 60 85 C T5 T1 II 2 G Ex ia IIC T 2 Gb 40 80 C 60 80 C T6 II 2 G Ex ia IIC T6 Gb Variant 2 Empty enclosure electronic See electronics 3 See...

Страница 5: ...transmitter 3 See transmitter 3 II 2 G Ex ia IIC T 3 Gb II 2 D Ex ia IIIC T 3 Db 1 For variant 1 and 2 The low ambient temperature 40 C applies to models with Limatherm or Rosemount cases The low amb...

Страница 6: ...enclosures however shall be suitable in accordance with EN IEC 60079 0 clause 8 Non metal enclosures or powder coated enclosures shall additionally comply with the electrostatic requirements of EN IEC...

Страница 7: ...instructions see data sheet War 2 3 Responsibility of the operator The responsibility for classification of zones lies with the plant operator and not the manufacturer supplier of the equipment 2 4 P...

Страница 8: ...rques are not observed this can lead to a loss of the explosion protection Ensure the tightening torques in accordance with chapter 3 2 WARNING Damage to the measuring instrument by operation outside...

Страница 9: ...the connection of the connection head and the neck tube or protection tube If the thermometer and the protection tube are already connected the seals will already be mounted if ordered The plant oper...

Страница 10: ...nstrument please observe that the threads are not skewed Assure that the purge gas connection is tighten and no gas can escape so that there is no carry through between zones Connection head selectabl...

Страница 11: ...r or digital display the permissible ambient temperature ranges specified in their certificates also apply to the entire instrument Cable glands Requirements for meeting ingress protection Only use ca...

Страница 12: ...and cable 6 12 mm Ex e Natural finish IP66 3 M20 x 1 5 NPT 60 4 40 80 C Stainless steel cable gland cable 7 12 mm Natural finish IP66 3 M20 x 1 5 NPT 60 4 40 80 C Stainless steel cable gland cable 7 1...

Страница 13: ...ons TC82 TC83 intrinsically safe designs Ex i 13 3 6 1 Thermocouples with B type terminal terminal block ceramic Only 1xTC permitted 3 6 2 Thermocouples with 7 8000 type terminal terminal block 1210G6...

Страница 14: ...Positive Negative K Green White Yellow Red J Black White White Red E Violet White Violet Red N Pink White Orange Red T Brown White Blue Red 3 7 Temperature carry over from the process A heat backflow...

Страница 15: ...ely the maximum surface temperatures of devices for the use in explosive dust atmospheres and the permissible ambient temperature shall be taken from the corresponding certification and shall be consi...

Страница 16: ...be 3 N A Metal support tube 4 N A Ceramic protection tube 5 N A Terminal block 6 No 2 Transmitter option 7 No 2 Field transmitter 8 N A Process connection 9 N A Purge option only TC82 10 N A Marking p...

Страница 17: ...n the enclosure does not occur with variant 1 However an impermissible heat backflow from the process which can exceed the operating temperature of the enclosure or the temperature class must be preve...

Страница 18: ...C 60079 11 and have no internal ignition source of their own A heating in the enclosure cannot happen therefore a thermal ignition is avoided The relevant clearances and creepage distances for the ter...

Страница 19: ...n in accordance to EN IEC 60079 0 and EN IEC 60079 11 It shall have at least type of protection ia and shall be appropriate for EPL Gb or EPL Db The installation conditions or specific conditions of u...

Страница 20: ...EN 14302224 01 01 2023 EN DE Additional operating instructions TC82 TC83 intrinsically safe designs Ex i 20 Annex EU declaration of conformity...

Страница 21: ...2023 EN DE Inhalt Inhalt Konformit tserkl rungen finden Sie online unter www wika de 1 Ex Kennzeichnung 22 2 Sicherheit 24 3 Inbetriebnahme Betrieb 26 4 Besondere Bedingungen f r die Verwendung X Con...

Страница 22: ...0 V Ii 110 mA Pi 500 mW Li Ci vernachl s sigbar 40 85 C 60 85 C T5 T1 II 2 G Ex ia IIC T 2 Gb 40 80 C 60 80 C T6 II 2 G Ex ia IIC T6 Gb Variante 2 Leergeh use Elektronik Siehe Elektronik 3 Siehe Elekt...

Страница 23: ...tter 3 II 2 G Ex ia IIC T 3 Gb II 2 D Ex ia IIIC T 3 Db 1 F r die Varianten 1 und 2 Die niedrige Umgebungstemperatur von 40 C gilt f r Typen mit Limatherm oder Rosemount Geh usen Die niedrige Umgebung...

Страница 24: ...gaben im Transmitterzertifikat beachtet werden Leichtmetallgeh use m ssen jedoch nach EN IEC 60079 0 Abschnitt 8 geeignet sein Nichtmetallische Geh use oder pulverbeschichtete Geh use m ssen zus tzlic...

Страница 25: ...plosionsschutzes Grenzwerte und technische Angaben einhalten siehe Datenblatt 2 3 Verantwortung des Betreibers Die Verantwortung ber die Zoneneinteilung unterliegt dem Anlagenbetreiber und nicht dem H...

Страница 26: ...lust des Explosionsschutzes f hren Anzugsdrehmomente gem Kapitel 3 2 sicherstellen WARNUNG Besch digung des Messger tes durch Unter oder berschreiten der zul ssigen Betriebstemperatur Bei Missachtung...

Страница 27: ...g f r die Verbindung zwischen Anschlusskopf und Halsrohr oder mehrteiligem Schutzrohr Bei Zusammenbauten von Thermometer und mehrteiligem Schutzrohr sind diese Dichtungen bereits vormontiert sofern be...

Страница 28: ...antet werden Sicherstellen dass der Sp lgasanschluss fest sitzt und kein Gas entweichen kann so dass es zu keiner Zonenverschleppung kommt Anschlusskopf w hlbar Beispiel Gewinde Anzugsdrehmomente in N...

Страница 29: ...nsmitter oder Digitalanzeige gelten die in deren Zertifikaten angegebenen zul ssigen Umgebungstemperaturbereiche auch f r das Gesamtger t Kabelverschraubungen Voraussetzungen zur Erreichung der Schutz...

Страница 30: ...ssing vernickelt Kabel 6 12 mm Ex e Blank IP66 3 M20 x 1 5 NPT 60 4 40 80 C Kabelverschraubung CrNi Stahl Kabel 7 12 mm Blank IP66 3 M20 x 1 5 NPT 60 4 40 80 C Kabelverschraubung CrNi Stahl Kabel 7 12...

Страница 31: ...re Ausf hrungen Ex i 31 14302224 01 01 2023 EN DE 3 6 1 Thermoelemente mit Anschlusssockel Klemmentyp B Keramik Nur 1xTC zul ssig 3 6 2 Thermoelemente mit Anschlusssockel Klemmentyp 7 8000 1210G6GNCX...

Страница 32: ...nus Pol Plus Pol Minus Pol K Gr n Wei Gelb Rot J Schwarz Wei Wei Rot E Violett Wei Violett Rot N Rosa Wei Orange Rot T Braun Wei Blau Rot 3 7 Temperaturverschleppung aus dem Prozess Ein W rmer ckfluss...

Страница 33: ...und die zul ssige Umgebungstemperatur sind der entsprechenden Zertifizierung zu entnehmen und einzuhalten 3 Bei Ger ten die die elektrostatischen Anforderungen der EN IEC 60079 0 nicht erf llen ist ei...

Страница 34: ...chlusskopf 2 Nr 4 Halsrohr 3 N A Metallisches Halterohr 4 N A Keramik Schutzrohr 5 N A Klemmsockel 6 Nr 2 Transmitter Option 7 Nr 2 Feldtransmitter 8 N A Prozessanschluss 9 N A Sp lfunktion Option nur...

Страница 35: ...indet bei Variante 1 nicht statt Jedoch ist ein unzul ssiger W rmer ckfluss aus dem Prozess welcher die Betriebstemperatur des Geh uses oder die Temperaturklasse berschreitet durch geeignete W rmeisol...

Страница 36: ...EN IEC 60079 11 und haben keine eigene interne Z ndquelle Es kann keine Erw rmung im Geh use auftreten so dass eine thermische Z ndung vermieden wird Die entsprechenden Luft und Kriechstrecken f r di...

Страница 37: ...IEC 60079 11 besitzen Sie m ssen mindestens ber die Z ndschutzart ia verf gen und f r Ger te mit dem Schutzniveau EPL Gb oder EPL Db geeignet sein Die Installationsbedingungen oder spezifischen Nutzu...

Страница 38: ...DE WIKA Zusatz Betriebsanleitung TC82 TC83 eigensichere Ausf hrungen Ex i 38 14302224 01 01 2023 EN DE Anlage EU Konformit tserkl rung...

Страница 39: ...14302224 01 01 2023 EN DE Additional operating instructions TC82 TC83 intrinsically safe designs Ex i 39...

Страница 40: ...lexander Wiegand SE Co KG Alexander Wiegand Strasse 30 63911 Klingenberg Germany Tel 49 9372 132 0 info wika de www wika de 40 Additional operating instructions TC82 TC83 intrinsically safe designs Ex...

Отзывы: