20
WIKA operating instructions models SC58, SC64
14054366.02 02/2016 EN/DE
EN
Parameters Functional
description
Setting range
Standard
setting
A1
Switching mode K1
0: Heating contact
1: Cooling contact
2: Alarm function
3: Alarm function inverted
0
A3
Function on sensor error 0: Off when error
1: On when error
0
A8
Display mode
(Parameter is displayed
with a resolution of
0.1 °C)
0: Integer
1: resolution 0.5 °C
2: resolution 0.1 °C
1
A19
Parameter lock
0: no lock
1: A-parameter locked
2: A-/P-parameter locked
0
A30
Type of alarm function
0: Limit alarm, relative
1: Limit alarm, absolute
2: Band alarm, relative
3: Band alarm, absolute
0
A31
Special function for
alarm
0: not active
1: Display flashes
3: Error display (F3.),
display flashes
4: as 3, save
0
A32
Type of display
0: Actual value display
1: Set-point display
0
A40
Hysteresis mode with
heating or cooling
function
0: symmetric
1: one side
1
A50
Minimum action time,
control contact “On”
0 ... 999 sec.
0 sec.
A51
Minimum action time,
control contact “Off”
0 ... 999 sec.
0 sec.
A54
Control contact delay
after “Power on”
0 ... 999 sec.
0 sec.
A56
Alarm suppression time
after “control ON” or
set-point change
0 ... 60 min.
20 min.
7. Configuration