Operating instruction FWS-RVM/U-L

Operating instruction FWS-RVM/U-L

1  Preface 

....................................... 1

2  Safety hints 

..................... 1

3  Principle of operation 

................. 1

4  Installation 

...................................... 1

5  Electrical connection 

................... 2

6  Switch point adjustment 

......... 3

7  Maintenance 

........................ 3

8  Fault finding hints 

........................... 3

9  Specifications 

............................... 4

2 Safety hints

9 Specifications

The flowmonitors type RVM/U-L prove themself through

reliability  and  simple  handling.  To  use  the  advantages

of  the  instrument  to  the  full  extent,  please  take  notice

of the following:

Every  person,  in  charge  of  commissioning  and 

operating  this  instrument,  must  have  read  and

understand  this  operating  instruction  and 

specially the safety hints!

2.1 General hints

The instructions contained in the operating instructions

must  be  followed  to  ensure  a  safe  operation  of  the

instrument.  Further,  the  additional  Legal-  and  safety-

regulations  for  the  individual  application  must  be 

observed.  Accordingly  this  applies  for  the  use  of 

accessories as well. 

 

2.2 Application as directed

The  instruments,  type  RVM/U-L,  serve  as  monitors 

for  continuous  flow  of  gaseous  media. Any  other  use 

counts  as  nondirected.  If  not  indicated  otherwise,  the 

scaling of the instruments refer to air. Special applica-

tions,  where  intermittent  loads  (e.a.  cyclic  operation) 

could occur, should be discussed and checked with our 

technical Staff.

With  every  start  up  it  should  be  watched  that  the 

shutoff  valves  are  opened  slowly,  this  is  to  avoid  line 

shock, which can damage the instrument.

In general should fast changes of the operating conditi-

ons (pressure, temperature, flow) be avoided.

The instruments, type RVM/U-L, must not be used as 

single source to avoid dangerous situations on machi-

nery and in plants. 

Machinery and plants must be constructed in that way, 

that faulty conditions do not lead the operators into dan-

gerous situations.

2.3 Qualified personnel

The instruments, type RVM/U-L, must only be installed 

by  qualified personnel, which is capable of using these 

instruments  in  a  professional  manner.  Qualified  per-

sonnel  are  such  persons,  which  are  familier  with  the 

erection,  installation,  commissioning  and  operation  of 

these  instruments  and  which  hold  a  corresponding 

qualification for this function.

3 Principle of operation

The instruments type RVM/U-L operate on the principle 

of  the  float  type  flow  indicator.  Through  the  flowing    

medium  a  float  is  set  in  motion,  whose  integrated 

magnets  create  a  magnetic  field.  The  position  of  the 

float  is  detected  with  the  switch  contact.  The  float  is 

reseted to the starting point by means of a spring, which 

allows the installation in any position in a system. The 

instruments  are  adjusted  for  the  installation  with  flow 

from bottom to top. The weight of the float influences the 

measuring result, therefore a different mounting position 

will show discrepancies to the actual flow 

4 Installation

4.1 Process connection

Caution! To avoid the damage of the flowmonitor or the 

installation the following requirements must be fulfilled 

under any circumstances:

-  suitable process connection has to be provided 

-  connection size to be checked

-   thread depth to be checked

-  suitable  sealing  material  to  be  used  (liquid  sealing 

material will damage the flowmonitor if it gets inside) 

-  professional sealing

4.2 Enviroment conditions

-   The flowmonitor must not be used as a supporting 

part in a pipe construction.

-  The  medium  must  not  contain  any  solid  particles. 

Magnetic particles will accumulate at the magnetic 

float and effect the function. 

-  Before employment of anti-freeze and anti-corrosive 

check compatibility.

Warning! The following requirements must be adhered 

to,  otherwise  the  function  of  the  flowmonitor  will  be 

affected or the measuring results will be falsified:

-  External  magnetic  fields  will  influence  the  switch 

contact. Keep sufficient distance to magnetic fields 

(e.a. Electricmotors).

-  Piping, process connections or supports made from 

ferromagnetic material influence the magnetic field 

of the flowmonitor. Keep a space of 100mm to those 

materials (e.a. steel).

-  The accuracy is influenced by cross-section chan-

ges,  branches  or  elbows  in  the  piping.  Provide  a 

straightening  section  of  10x  DN  upstream  and  5x 

DN downstream of the instrument. Never reduce the 

pipe diameter direct ahead of the instrument!

-  With liquids ensure through suitable steps the de-

areation of the instrument.

Content

1 Preface

-1-

-4-

All rights reserved

SW

D

B

G

DN

T

L

RVM/U-L-4

17

17

47

1/4“

8

10

65

RVM/U-L-2

27

31

52

1/2“

15

14

90

RVM/U-L-1

41

47

76

3/4“

1“

20

25

21

17

152

130

Overall dimensions mm

RVM/U-L-1

RVM/U-L-2

RVM/U-L-4

Operating Data

RVM/U-L-1

RVM/U-L-2

RVM/U-L-4

Pressure: brass

PN 250 bar

PN 250 bar

PN 300 bar

Pressure: stainl. steel

PN 300 bar

PN 350 bar

PN 350 bar

Pressure drop.:

0,02 - 0,4 bar

0,02 - 0,3 bar

0,02 - 0,2 bar

Temperature max.:

100°C (optional 160°C)

Accuracy:

±10% of final value

Electrical Data:

SPST N.O.

SPDT

SPST N.O.

SPDT

SPST N.O.

SPDT

IP65 (

plug connection DIN43650 Form A or C

)

max. 250V 

• 3A •

100 VA

max. 250V 

• 1,5A • 

50VA 

(1)

max. 230V • 

3A • 60VA

max. 250V 

• 1,5A • 

50VA 

(1)

max. 200V • 

1A • 20VA

max. 200V • 

1A • 20VA

IP67 (with 1m sealed in cable) 

M 12x1 plug

Temperature max. 85°C

not available

max. 125V • 

3A • 60VA

max. 125V • 

1,5A • 50VA

max. 125V • 

1A • 20VA

max. 125V • 

1A • 20VA

 Atex II 2G EEx m II T6 max. 80°C               

(2m sealed in cable IP67)

max. 250V • 

2A • 60VA

max. 250V • 

1A • 30VA

max. 250V • 

2A • 60VA

max. 250V • 

1A • 30VA

not available

EEx m II T6 max. 80°C

max. 250V • 

2A • 60VA

max. 250V • 

1A • 30VA

max. 250V • 

2A • 60VA

max. 250V • 

1A • 30VA

not available

Output signal:

The contact switches off, if minimum flow is below setpoint

Power supply:

not necessary (reed contacts)

Cable diameter for IP65:

6 - 8 mm

4 - 6,5 mm

Grade of pollution:

2 (EN 61058-1)

Other plug types or cable lengths on request

Materials

brass

stainl. st.

Wetted parts:

brass

1.4571 (316 ti)

Spring 

(wetted parts)

1.4571 (316 ti)

Magnets 

(wetted parts)

hard-ferrite

Seals 

(with reducers only)

NBR (other on request)

Viton (other on request)

(1) Minimum load 3VA

B R

VMU_L

  0006 10-09 E M

WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30
DE-63911 Klingenberg/Main