7. Maintenance, cleaning and recalibration
7.1 Maintenance
These gas density monitors are maintenance-free.
The indicator and switching function should be checked once or twice every year. For
this the instrument must be disconnected from the gas compartment to check with a
pressure testing device (e.g. WIKA BCS-10).
Repairs must only be carried out by the manufacturer.
The instruments must not be opened, since this can lead to indication and switch point
errors.
7.2 Cleaning
CAUTION!
Physical injuries and damage to property and the environment
Improper cleaning may lead to physical injuries and damage to property
and the environment. Residual media in the dismounted instrument can
result in a risk to persons, the environment and equipment.
▶
Carry out the cleaning process as described below.
1. Before cleaning, correctly disconnect the instrument from the pressure supply, switch
it off and disconnect it from the mains.
2. Use the requisite protective equipment.
3. Clean the instrument with a moist cloth.
Electrical connections must not come into contact with moisture!
CAUTION!
Damage to the instrument
Improper cleaning may lead to damage to the instrument!
▶
Do not use any aggressive cleaning agents.
▶
Do not use any hard or pointed objects for cleaning.
4. Wash or clean the dismounted instrument, in order to protect persons and the
environment from exposure to residual media.
Information on returns can be found under the heading “Service” on our
local website.